16.06.2017 Views

Cona Srl - Catalogo Scaricatori di Condensa

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

DISPOSITIVI DI CONTROLLO PER SCARICATORI DI CONDENSA / STEAM TRAPS CONTROL DE-<br />

VICES<br />

Il <strong>di</strong>spositivo <strong>di</strong> controllo per scaricatori <strong>di</strong> condensa è progettato<br />

per controllare eventuali per<strong>di</strong>te <strong>di</strong> vapore degli scaricatori che<br />

lavorano con vapore saturo. La condensa entra nel <strong>di</strong>spositivo <strong>di</strong><br />

controllo ed è scaricata nella parte bassa; il vapore entra nel corpo<br />

dall’apertura presente sulla parte alta. Se non si verifi cano per<strong>di</strong>te,<br />

tramite il sensore presente nel corpo che è a contatto con la condensa,<br />

il <strong>di</strong>spositivo segnala “verde”. Se si verifi cano per<strong>di</strong>te <strong>di</strong> vapore<br />

nello scaricatore, la velocità del vapore all’interno del corpo<br />

aumenta e spinge la condensa al <strong>di</strong> fuori del corpo; ciò impe<strong>di</strong>sce il<br />

contatto tra la condensa e il sensore e il <strong>di</strong>spositivo segnala “rosso”.<br />

Installazione:<br />

Il <strong>di</strong>spositivo deve essere installato davanti allo scaricatore. Il sensore<br />

sul corpo deve essere installato in modo tale che la presa venga<br />

connessa con facilità. Il <strong>di</strong>spositivo, come mostrato dalla freccia su<br />

<strong>di</strong> esso, deve seguire la <strong>di</strong>rezione del fl usso.<br />

Steam trap control body is designed to control possible steam leakages<br />

of the operational steam traps working at saturated steam.<br />

<strong>Condensa</strong>te enters the control body and it is <strong>di</strong>scharged from the<br />

bottom; steam enters the body from the hole on the top. If there is<br />

no leakage, the sensor in the body is in contact with condensate<br />

so the device signals “green”. If there is any steam leakage in the<br />

steam trap, steam velocity in the body increases and it pushes the<br />

condensate out of the body; this prevents the connection between<br />

the condensate and the sensor and it signals “red”.<br />

Installation:<br />

This device must be installed before the steam trap. The sensor on<br />

the body must be installed so that the socket can easily be connected.<br />

The arrow on the body must follow the <strong>di</strong>rection of the fl ow.<br />

Con<strong>di</strong>zioni operative /<br />

Operating con<strong>di</strong>tions<br />

Pressione massima /<br />

Max. pressure<br />

[bar]<br />

Temperatura massima /<br />

Max. temperature<br />

[°C]<br />

Pressione massima <strong>di</strong> esercizio /<br />

Max. operating pressure<br />

[bar]<br />

Temperatura massima <strong>di</strong> esercizio /<br />

Max. operating temperature<br />

[°C]<br />

16<br />

250<br />

14<br />

240<br />

Materiali / Materials<br />

Ghisa sferoidale GGG 40.3 / Ductile iron GGG 40.3<br />

Connessioni / Connections<br />

Filettato / Threaded BSP (BS 21)<br />

Flangiato / Flanged DIN 2533<br />

I prodotti CONA sono soggetti ad alterazioni tecniche derivanti dal processo <strong>di</strong> produzione.<br />