Cona Srl - Catalogo Scaricatori di Condensa
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
DISPOSITIVI DI CONTROLLO PER SCARICATORI DI CONDENSA / STEAM TRAPS CONTROL DE-<br />
VICES<br />
Il <strong>di</strong>spositivo <strong>di</strong> controllo per scaricatori <strong>di</strong> condensa è progettato<br />
per controllare eventuali per<strong>di</strong>te <strong>di</strong> vapore degli scaricatori che<br />
lavorano con vapore saturo. La condensa entra nel <strong>di</strong>spositivo <strong>di</strong><br />
controllo ed è scaricata nella parte bassa; il vapore entra nel corpo<br />
dall’apertura presente sulla parte alta. Se non si verifi cano per<strong>di</strong>te,<br />
tramite il sensore presente nel corpo che è a contatto con la condensa,<br />
il <strong>di</strong>spositivo segnala “verde”. Se si verifi cano per<strong>di</strong>te <strong>di</strong> vapore<br />
nello scaricatore, la velocità del vapore all’interno del corpo<br />
aumenta e spinge la condensa al <strong>di</strong> fuori del corpo; ciò impe<strong>di</strong>sce il<br />
contatto tra la condensa e il sensore e il <strong>di</strong>spositivo segnala “rosso”.<br />
Installazione:<br />
Il <strong>di</strong>spositivo deve essere installato davanti allo scaricatore. Il sensore<br />
sul corpo deve essere installato in modo tale che la presa venga<br />
connessa con facilità. Il <strong>di</strong>spositivo, come mostrato dalla freccia su<br />
<strong>di</strong> esso, deve seguire la <strong>di</strong>rezione del fl usso.<br />
Steam trap control body is designed to control possible steam leakages<br />
of the operational steam traps working at saturated steam.<br />
<strong>Condensa</strong>te enters the control body and it is <strong>di</strong>scharged from the<br />
bottom; steam enters the body from the hole on the top. If there is<br />
no leakage, the sensor in the body is in contact with condensate<br />
so the device signals “green”. If there is any steam leakage in the<br />
steam trap, steam velocity in the body increases and it pushes the<br />
condensate out of the body; this prevents the connection between<br />
the condensate and the sensor and it signals “red”.<br />
Installation:<br />
This device must be installed before the steam trap. The sensor on<br />
the body must be installed so that the socket can easily be connected.<br />
The arrow on the body must follow the <strong>di</strong>rection of the fl ow.<br />
Con<strong>di</strong>zioni operative /<br />
Operating con<strong>di</strong>tions<br />
Pressione massima /<br />
Max. pressure<br />
[bar]<br />
Temperatura massima /<br />
Max. temperature<br />
[°C]<br />
Pressione massima <strong>di</strong> esercizio /<br />
Max. operating pressure<br />
[bar]<br />
Temperatura massima <strong>di</strong> esercizio /<br />
Max. operating temperature<br />
[°C]<br />
16<br />
250<br />
14<br />
240<br />
Materiali / Materials<br />
Ghisa sferoidale GGG 40.3 / Ductile iron GGG 40.3<br />
Connessioni / Connections<br />
Filettato / Threaded BSP (BS 21)<br />
Flangiato / Flanged DIN 2533<br />
I prodotti CONA sono soggetti ad alterazioni tecniche derivanti dal processo <strong>di</strong> produzione.<br />
81