22.02.2013 Views

Untitled - Future Pipe Industries

Untitled - Future Pipe Industries

Untitled - Future Pipe Industries

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

7.4 Volume of water required<br />

Table 13 indicates the approximate volume of water required in order to fill pipes per 100 feet of pipeline.<br />

DN<br />

Inch<br />

Water volume (gal)<br />

/ 100 ft of pipeline<br />

3 39<br />

4 69<br />

6 154<br />

8 270<br />

10 430<br />

12 615<br />

14 840<br />

16 1,100<br />

18 1,390<br />

20 1,700<br />

24 2,450<br />

28 3,350<br />

30 3,850<br />

33 4,700<br />

34 4,950<br />

Table 13<br />

7.5: Initial test (method 1)<br />

After the test section is ready, the line shall be filled with water and kept under low pressure (30 psig) for at least 12 hours<br />

to allow the pipeline to stabilize and to release the entrapped air from the line. After the stabilization period, the pressure<br />

shall be raised gradually at a rate of 15 – 30 psi every half an hour, until the intended test pressure at the lowest point is<br />

reached.<br />

Unless otherwise specified by the Engineer, the test pressure shall be equal to 1.5 times the intended working pressure of the<br />

pipeline section. Once the required test pressure is reached, the pressure should be maintained for one hour, by pumping if<br />

necessary. The pump should then be disconnected and no further water permitted to enter the pipeline section for one hour.<br />

At the end of this one-hour period, the original test pressure shall be restored by pumping water from a graduated water tank<br />

and measuring the amount of water necessary to restore the test pressure. Unless otherwise specified by the Engineer, the test<br />

water loss should not exceed .03 US gallons / inch of diameter per mile of pipeline per 24 hours per psig of test pressure<br />

applied (average test pressure of section). This is equivalent to 4.5 gpd / mile / inch for a 150 psig test pressure.<br />

During the pressure test, all joints should be visually inspected (where possible), and all visual leaks should be repaired. In<br />

case the test in not satisfactory, the locations of the leaks shall be determined and rectified, and the line re-tested in the same<br />

manner as shown above. The test section shall be accepted only after successfully passing the above leakage test.<br />

Note: The Contractor should note that while pressure testing large diameter pipe on site at pressures generally above 150<br />

psi, there is a possibility of a slight rotation/pivoting of the Reka coupling. This is the result of uneven pressure against the<br />

various parts of the coupling, and is inevitable during normal joint assembly where a perfectly centered and aligned joint<br />

can never be achieved. In the unlikely event that one or more joint starts to rotate or to shift slightly during the pressure test,<br />

it is advisable to reduce the pressure, and to backfill the joints completely using selected, properly compacted backfill, prior<br />

to resumption of the pressure test. Any joint that has shifted significantly should be centered again before resuming the pressure<br />

test.<br />

38<br />

DN<br />

Inch<br />

Water volume (gal)<br />

/ 100 ft of pipeline<br />

36 5,550<br />

42 7,500<br />

48 9,900<br />

54 12,500<br />

60 15,400<br />

72 22,200<br />

80 27,500<br />

96 39,500<br />

108 49,950<br />

114 55,650<br />

120 61,700<br />

132 74,500<br />

144 88,800<br />

158 107,000

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!