B<br />

Floor/Ceilings<br />

Steel Framed<br />

2 Hour <strong>Fire</strong>-rated Construction Steel Bar Joist Framing (Refer to ULC/UL Design Directory listings for loading conditions. See page 6.) Acoustical Performance Reference<br />

Construction Detail Description Test Number STC Test Number ARL Index<br />

540 mm<br />

(21 1 ⁄4")<br />

352 mm<br />

(13 7 ⁄8")<br />

• <strong>CGC</strong> DGL Drywall Suspension System ULC Des I517 B-12<br />

• 12.7 mm (1/2�)SHEETROCK FIRECODE C Gypsum Panels<br />

screwed to Rigid X Suspension System<br />

– concrete 64 mm (2-1/2�) thick on metal lath,<br />

pan or steel floor units over bar joists<br />

– includes 3 hour unrestrained beam, air ducting<br />

and recessed lighting fixtures<br />

• 12.7 mm (1/2�) SHEETROCK FIRECODE C Gypsum Panels ULC Des I518 B-13<br />

screwed to furred or suspended channel<br />

– concrete 70 mm (2-3/4�) thick on Hambro<br />

Structural system steel joist H601, H675, TC<br />

or RTC, spaced 1200 mm (48�) o.c.<br />

– includes air ducting<br />

clg. wt. 2 • 12.7 x 610 x 610 mm (1/2� x 24� x 24�) FC-CB ULC Des I520 SC2000 B-14<br />

gypsum panels or UL Des G222<br />

• DXL, DXLA, DXLH, DXLZ, DXLZA, SDXL,<br />

559 mm<br />

(22")<br />

533 mm<br />

(21")<br />

609 mm<br />

(24")<br />

543 mm<br />

(21 3 ⁄8")<br />

or SDXLA Susp Exp Grid System<br />

– light fixtures and air ducts optional<br />

– 64 mm (2-1/2�) concrete deck on riblath or<br />

corrugated steel deck<br />

– steel bar joists, 610 mm (24�) o.c.<br />

• 15.9 mm (5/8�)SHEETROCK FIRECODE UL Des G529 B-15<br />

C Core Gypsum Panel<br />

• DGLW Drywall Suspension System<br />

– light fixture and air duct optional<br />

– 81 mm (3-1/4�) concrete deck on riblath or<br />

corrugated steel deck<br />

– also applies to 15.9 mm (5/8�) panels and<br />

70 mm (2-3/4�) concrete slab<br />

– steel bar joists, 610 mm (24�), o.c.<br />

• optional veneer plaster<br />

• 15.9 mm (5/8�) or 19.1 mm (3/4�) 300 x 300 mm UL Des G002 SC2000 B-16<br />

(12� x 12�) or 610 mm (24�) FR-83 acoustical<br />

ceiling panels in Concealed Z-Spline Grid System<br />

– light fixture and air duct optional<br />

– 64 mm (2-1/2�) concrete deck on riblath<br />

– steel bar joists, 610 mm (24�) o.c.<br />

27 <strong>CGC</strong> <strong>Fire</strong>-<strong>Resistant</strong> <strong>Assemblies</strong>