Instruction Booklet IM04302004E<br />
Effective October 2010<br />
Manual/automatic Reset<br />
The overload relay is factory set at “M” for manual reset operation<br />
as shown in the illustration . For automatic reset operation, turn the<br />
reset adjustment dial to the “A” position . Automatic reset is not<br />
intended for two-wire control devices .<br />
RESET<br />
ADJUSTMENT<br />
DIAL<br />
18<br />
Example of<br />
setting for<br />
manual reset .<br />
Test for Trip Indication<br />
To test overload relay for trip indication when in manual reset, pull<br />
out the blue Reset button . An orange flag will appear indicating that<br />
the device has tripped . Push Reset button in to reset .<br />
For more information, go to www .1800oldunit .com or call<br />
1-800-OLD-UNIT .<br />
Table 1. NEMA Size 0 <strong>and</strong> 1 Heater Pack Selection Table<br />
<strong>Motor</strong> FLa rating<br />
FLa Dial positions<br />
A B C D<br />
0.254<br />
0.375<br />
0.560<br />
0.814<br />
1.20<br />
1.79<br />
2.15<br />
3.23<br />
4.55<br />
6.75<br />
9.14<br />
14.0<br />
18.7<br />
23.5<br />
0.306<br />
0.452<br />
0.676<br />
0.983<br />
1.45<br />
2.16<br />
2.60<br />
3.90<br />
5.50<br />
8.17<br />
10.8<br />
16.9<br />
22.7<br />
28.5<br />
0.359<br />
0.530<br />
0.791<br />
1.15<br />
1.71<br />
2.53<br />
3.04<br />
4.56<br />
6.45<br />
9.58<br />
12.4<br />
19.9<br />
26.7<br />
33.5<br />
0.411<br />
0.607<br />
0.907<br />
1.32<br />
1.96<br />
2.90<br />
3.49<br />
5.23<br />
7.40<br />
11.0<br />
14.0<br />
22.8<br />
30.7<br />
—<br />
eaton Corporation www.eaton.com<br />
Size F<br />
St<strong>and</strong>ard<br />
trip<br />
Class 20<br />
H2001B<br />
H2002B<br />
H2003B<br />
H2004B<br />
H2005B<br />
H2006B<br />
H2007B<br />
H2008B<br />
H2009B<br />
H2010B<br />
H2011B<br />
H2012B<br />
H2013B a<br />
H2014B a<br />
a After the above referenced settings have been made, rotate the FLA dial one position clockwise for<br />
these heaters (see table). If less than one position is available, rotate dial maximum. This does not<br />
apply when these heaters are used with adapter base. Catalog No. C306TB1. Exception: does not<br />
apply to AN16DN0.<br />
Notee: For maximum ratings, see table below . Use 75°C copper conductors<br />
only . Maximum wire size—8 AWG .<br />
neMa Size amperes Size amperes<br />
0 18 — —<br />
1 27 F 32<br />
warning<br />
to provide Continued proteCtion againSt fire or SHoCk Hazard,<br />
tHe CoMplete overload relay MuSt be replaCed if burnout of<br />
tHe Heater eleMent oCCurS.<br />
M<br />
A<br />
<strong>Freedom</strong> <strong>2100</strong> <strong>Motor</strong> <strong>Control</strong> <strong>Center</strong><br />
<strong>Installation</strong> <strong>and</strong> Maintenance Manual<br />
Table 2. NEMA Size 2 Heater Pack Selection Table<br />
<strong>Motor</strong> FLa rating a<br />
FLa Dial positions<br />
a B C D<br />
Size J <strong>and</strong> K<br />
St<strong>and</strong>ard trip<br />
Class 20<br />
3.23<br />
4.55<br />
6.75<br />
9.14<br />
14.0<br />
18.7<br />
23.5<br />
29.0<br />
39.6<br />
53.9<br />
3.90<br />
5.50<br />
8.17<br />
10.8<br />
16.9<br />
22.7<br />
28.5<br />
34.0<br />
45.5<br />
60.9<br />
4.56<br />
6.45<br />
9.58<br />
12.4<br />
19.9<br />
26.7<br />
33.5<br />
39.1<br />
51.5<br />
67.9<br />
5.23<br />
7.40<br />
11.0<br />
14.0<br />
22.8<br />
30.7<br />
38.5<br />
44.1<br />
57.4<br />
74.9<br />
H2008B<br />
H2009B<br />
H2010B<br />
H2011B<br />
H2012B<br />
H2013B<br />
H2014B<br />
H2015B<br />
H2016B b<br />
H2017B b<br />
a For motor FLA values not listed, turn the dial clockwise for higher or counterclockwise for lower<br />
ratings.<br />
b After the above reference settings have been made, rotate the FLA dial one position clockwise for<br />
these heaters (see table). If less than one position is available, rotate dial to maximum. This note<br />
does not apply when these heaters are used with adapter base. Catalog No. C306TB1.<br />
Notee: For maximum ratings, see table below . Use 167ºF (75°C) copper<br />
conductors only . Maximum wire size—3 AWG .<br />
neMa Size amperes Size amperes<br />
2 45 J 60<br />
— — K 73<br />
Table 3. NEMA Size 3 <strong>and</strong> 4 Heater Pack Selection Table<br />
<strong>Motor</strong> FLa rating a<br />
FLa Dial positions<br />
A B C D<br />
Size n<br />
St<strong>and</strong>ard trip<br />
Class 20<br />
18.0<br />
24.6<br />
33.5<br />
45.7<br />
62.2<br />
84.7<br />
106.0<br />
20.2<br />
27.6<br />
37.5<br />
51.2<br />
69.7<br />
94.9<br />
118.0<br />
22.3<br />
30.5<br />
41.5<br />
56.7<br />
77.1<br />
105.0<br />
131.0<br />
24.5<br />
33.4<br />
45.6<br />
62.1<br />
84.6<br />
115.0<br />
144.0<br />
H2018<br />
H2019<br />
H2020<br />
H2021<br />
H2022<br />
H2023<br />
H2024<br />
a For motor FLA values not listed, turn the dial clockwise for higher or counterclockwise for<br />
lower ratings.<br />
Notee: For maximum ratings, see table below . Minimum wire size—6 AWG .<br />
neMa Size amperes Size amperes<br />
3 90 N 14<br />
4 135 — —