The turrets are often individually adapted; check therefore that they are<br />

re-mounted in correct places, which appear from the OGA drawing and ,part<br />

list.<br />

Assembling of bushings is carried out according to the detailed<br />

information documents available.<br />

2.1.9 ASSEMBLY OF VALVES<br />

Valves which may affect the loading gauge, or will be subjected to<br />

damages, should be dismounted before delivery. Re-mount the valves -the<br />

positionings appear from the OGA drawing and part list. The gasketting surfaces<br />

shall be cleaned well and new gaskets fitted. Check that all valves are closed.<br />

2.1.10 ASSEMBLY OF COOLING DEVICES<br />

Valves which are not dismantled like shut-off valves for radiators, coolers<br />

and possible headers shall be provided with blanking plates during the transport.<br />

Remove the blanking plates when the assembling of the coolers is to be<br />

started. Check first that the valves are closed.<br />

Check that each radiator and possible header are assembled in the correct<br />

positions according to OGA drawing. In case of OFAF or OFWF cooler mounting<br />

shall be done as per the relevant leaflet given in Vol.I<br />

The shut-off valves against the transformer tank shall be closed until<br />

the oil-filling is started.<br />

2.1.11 ASSEMBLY OF OIL CONSERVATOR<br />

The conservator, which may be with or without aircell is assembled<br />

either on the transformer, or on a separate frame. Before the conservator is<br />

assembled it shall be checked that belonging equipment -e.g. Oil-level indicator<br />

-functions satisfactorily.<br />

The breather is connected to the oil conservator, and it is very important<br />

that joints and couplings in the pipe between breather and conservator are air<br />

tight. Refer Clause 2.6 for detailed <strong>instruction</strong> for oil filling.<br />

2.1.12 ASSEMBLY OF PIPE WORK<br />

Pipes with flanges for connection of conservator, radiators, as well as<br />

pipes for equalising of turrets etc. are mostly delivered completely ready for<br />

assembling according to OGA & part list.<br />

In certain cases -e.g. at a separately assembled oil conservator -certain<br />

fitting and welding of pipes and flanges on site is however required. Instruction<br />

for such assembly of external pipes is given in Clause 2.3<br />

2.1.13 FLANGES, BLANKING PLATES<br />

When re-mounting blanking plates, connection flanges etc., the gasketting<br />

surface shall be cleaned well and new gaskets fitted.<br />