It is very important that the pipe is tight. Possible leakage will cause<br />

moisture on the transformer with the service disturbances.<br />

Mounting of the breather pipe shall be as per OGA drawing.<br />

2.3.3. OIL CONSERVATOR<br />

For position of conservator along with necessary supports, refer OGA<br />

drawing.<br />

2.3.4 OIL CONSERVATOR PIPE<br />

The pipe has dimension 80 mm usually and has welded flanges. The<br />

pipe shall be painted internally with a yellow, oil-resistant paint, and externally<br />

with a paint specified on the drawing. The pipes shall always incline upwards<br />

minimum 2/3 degrees from the transformer.<br />

2.3.5 EQUALISING PIPES<br />

The pipe system in connection with the transformer cover is as a rule<br />

manufactured in workshop. The pipe between transformer and conservator<br />

may be pre-assembled.<br />

The pipe is provided with weld-flanges. No pipe part is allowed to be so<br />

long that internal inspection and cleaning is difficult to carry out. Besides<br />

straight extensions, each pipe part may contain one bend.<br />

The pipes shall always be placed with minimum 2/3 degrees inclining<br />

upwards from the transformer. Internal surface treatment is with yellow oil<br />

resistant paint. External surface treatment is made as specified on the drawing<br />

as per specification. Cleanliness is extremely important.<br />

2.3.6 COOLERS<br />

The positioning of the radiators/coolers is indicated on OGA drawing.<br />

These are positioned so that the highest point of the oil-pipe system is always<br />

positioned below the bottom level of the conservator.<br />

The pipe system is provided with filter valves at the start and finish to<br />

enable pumping the oil through the system.<br />

All places where air may be collected are provided with air release plugs/<br />

valves.<br />

2.3.7 COOLER PIPES<br />

The pipe having dimensions as per OGA drawing and may be provided<br />

with weld- flanges, expansion joints. No pipe part is allowed to be so long that<br />

internal inspection and cleaning will be difficult.<br />

The pipes shall be placed so that air release plugs will be positioned at<br />

the highest point of the pipe part. The pipes shall be painted internally with a<br />

yellow, oil-resistant paint and externally according to the paint as per<br />

specification.<br />

2.4 INSULATING OIL, QUALITY AND TREATMENT<br />

2.4.1 QUALITY<br />

The oil to be filled in transformer generally complies with the<br />

requirements of the customer's specification. The characteristics of fresh oil<br />

as per IS: 335 "Specification for New Insulating Oil" are given below:<br />