25.03.2013 Views

instruction manual - BHEL Bhopal

instruction manual - BHEL Bhopal

instruction manual - BHEL Bhopal

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

3 COMMISSIONING<br />

SECTION 3<br />

3.1 TESTING AFTER ASSEMBLY OF THE TRANSFORMER/ REACTOR<br />

AT SITE.<br />

After the transformer/reactor has been assembled at site, it shall be<br />

tested in order to check that it has not been damaged during transport and<br />

assembly to such an extent that its future operation will be at risk. Regarding<br />

the performance of the test, refer to the testing method as per standards. The<br />

results of the test shall be documented as detailed in Clause 3.2 "commissioning<br />

checks -Transformers" and Clause 3.3 commissioning checks - Reactors.<br />

3.1.1 APPLICATION OF VOLTAGE<br />

If possible, the voltage should be increased step by step up to rated<br />

voltage. This may be done by connecting the transformer/reactor to a generator<br />

whose voltage is raised slowly. The higher the rated voltage of transformer/<br />

reactor the more important it becomes that the application of the voltage is<br />

done as described. If it is not possible to use a generator, the transformer/<br />

reactor may be connected directly to a live line.<br />

After the first application of voltage, the transformer/reactor shall be<br />

checked carefully (gas relay, temperatures, leakages).<br />

When the transformer/reactor has been is service for some weeks with<br />

normal working temperature, all sealing joints shall be re-tightened.<br />

3.1.2 ENERGISING<br />

The initial magnetising current at the time of switching will be very<br />

high. This depends on the particular moment in the cycle. The transformer<br />

should always be soaked for few hours under constant care i.e. keep it<br />

energized. If the breaker trips on differential, Buchholz or any other device,<br />

the cause must be investigated before re-energising the transformer or reactor.<br />

After successful charging, performance of the transformer/reactor , OTI, WTI<br />

readings should be monitored for 24 hours and ensured that they are as per<br />

loading.<br />

3.1.3 ANALYSIS OF GAS<br />

The gas conected in the relay will help to identify the nature of the fault.<br />

It is suggested that the following checks are made at convenient intervals or<br />

following the indication of accumulation of gas through alarm signal.<br />

1. Rate of gas collection- The greater the rate of gas collection, the more<br />

severe is the nature of the developing fault.<br />

2. Colour of the gas helps in finding the affected material as follows.<br />

Prepared By Samvet Lahari, <strong>Bhopal</strong>. Phone- 5277412

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!