instruction manual - BHEL Bhopal
instruction manual - BHEL Bhopal
instruction manual - BHEL Bhopal
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
{ÉÉ´É®ú ]ÅõÉƺɡòÉǨɮúºÉ B´ÉÆ Ê®úBC]õºÉÇ<br />
POWER POWER TRANSFORMERS TRANSFORMERS &<br />
&<br />
REACTORS<br />
REACTORS<br />
+xÉÖnäùÉ {ÉÖκiÉEòÉ<br />
INSTRUCTION INSTRUCTION MANUAL<br />
MANUAL<br />
ºlÉÉ{ÉxÉ, Eò¨ÉÒÉËxÉMÉ {ÉÊ®úSÉɱÉxÉ B´ÉÆ +xÉÖ®úIÉhÉ<br />
Eäò ʱɪÉä +xÉÖnäùÉ<br />
(JÉÆb÷ - 2)<br />
INSTRUCTIONS FOR INSTALLATION,<br />
COMMISSIONING, OPERATION AND<br />
MAINTENANCE<br />
(VOLUME - II)<br />
¦ÉÉ®úiÉ ½äþ´ÉÒ
{ÉÉ´É®ú ]ÅõÉƺɡòɨÉÇ®úºÉÇ B´ÉÆ Ê®úBC]õºÉÇ<br />
Eäò ºlÉÉ{ÉxÉ, Eò¨ÉÒÉËxÉMÉ {ÉÊ®úSÉɱÉxÉ B´ÉÆ +xÉÖ®úIÉhÉ Eäò<br />
ʱɪÉä +xÉÖnäùÉ<br />
INSTRUCTIONS FOR INSTALLATION,<br />
COMMISSIONING, OPERATION AND<br />
MAINTENANCE OF<br />
POWER TRANSFORMERS<br />
&<br />
REACTORS<br />
¦ÉÉ®úiÉ ½äþ´ÉÒ
ºlÉÉ{ÉxÉ, Eò¨ÉÒÉËxÉMÉ, {ÉÊ®úSÉɱÉxÉ B´ÉÆ +xÉÖ®úIÉhÉ Eäò +xÉÖnäùÉ<br />
JÉÆb÷ - II<br />
(EÖò±É JÉÆb÷ - 2)<br />
INSTALLATION, COMMISSIONING,<br />
OPERATION AND MAINTENANCE<br />
INSTRUCTIONS<br />
VOL-II of II<br />
Prepared By Samvet Lahari, <strong>Bhopal</strong>. Phone- 5277412
PREFACE<br />
<strong>BHEL</strong> Transformers and Reactors are designed, manufactured and<br />
tested with care. With proper attention during installation and use, the user<br />
should receive from it the maximum expected service.<br />
Before installing the transformers/ reactor read these <strong>instruction</strong>s<br />
carefully.<br />
These <strong>instruction</strong>s have been prepared to provide information on<br />
assembly, installation, commissioning and regular maintenance of the<br />
transformers/reactors and shall form part of Instruction Manual.<br />
These <strong>instruction</strong>s do not intend to cover operation and maintenance of<br />
the transformer under abnormal conditions.<br />
Should further information be needed or any problem arises which is<br />
not covered by these <strong>instruction</strong>s, please ask <strong>BHEL</strong> for further information.<br />
In operating the Transformer/Reactor, Care should be taken that loading<br />
limits as specified are strictly followed. For <strong>instruction</strong>s regarding, general<br />
information on accessories such as OLTC, WTI, OTI, Buchholz relay, fan,<br />
pump, etc. Vol. I may please be referred.<br />
Prepared By Samvet Lahari, <strong>Bhopal</strong>. Phone- 5277412
CONTENTS<br />
Page No.<br />
SECTION 1 GENERAL INFORMATION<br />
1.1 INTRODUCTION 11<br />
1.2 TRANSPORT OF TRANSFORMER / REACTOR 13<br />
SECTION 2 INSTALLATION<br />
2.1 RECEPTION AND ASSEMBLING OF TRANSFORMERS<br />
/ REACTORS DESPATCHED PARTLY DISMANTLED<br />
AND FILLED WITH NITROGEN 21<br />
2.2 STORING OF TRANSFORMER / REACTOR DESPATCHED<br />
FILLED WITH NITROGEN 33<br />
2.3 ASSEMBLING OF EXTERNAL PIPES 35<br />
2.4 INSULATING OIL, QUALITY AND TREATMENT 37<br />
2.5 OIL FILLING UNDER VACUUM 41<br />
2.6 OIL FILLING INSTRUCTIONS FOR CONSERVATORS<br />
WITH AIR CELL 47<br />
2.7 UNTANKING OF ACTIVE PART 53<br />
2.8 MOUNTING OF GASKETS 55<br />
2.9 WELDED COVER (IF APPLICABLE) 57<br />
2.10 EARTHING OF ACTIVE PART AND CORE<br />
INSULATION TEST 59<br />
2.11 TOUCH-UP PAINTING 69<br />
SECTION 3 COMMISSIONING<br />
3.1 TESTING AFTER ASSEMBLY OF THE TRANSFORMER<br />
/ REACTOR AT SITE 77<br />
3.2 COMMISSIONING CHECKS - TRANSFORMER 79<br />
3.3 COMMISSIONING CHECKS - REACTOR 93<br />
SECTION 4 MAINTENANCE AND OPERATION<br />
4.1 SUPERVISION OF TRANSFORMER / REACTOR 101<br />
4.2 SUPERVISION AND CONTROL OF OIL 109<br />
4.3 TROUBLE SHOUTING 109<br />
4.4 PARALLEL OPERATION 119<br />
4.5 DO'S AND DON'TS 137<br />
4.6 DISPOSAL 145<br />
Prepared By Samvet Lahari, <strong>Bhopal</strong>. Phone- 5277412
¦ÉÉMÉ-1<br />
ºÉɨÉÉxªÉ VÉÉxÉEòÉ®úÒ<br />
SECTION-1<br />
GENERAL INFORMATION<br />
Prepared By Samvet Lahari, <strong>Bhopal</strong>. Phone- 5277412
1.1 INTRODUCTION<br />
SECTION 1<br />
GENERAL INFORMATION<br />
1.1.1 POWER TRANSFORMERS<br />
Unlike shunt reactor and Neutral Grounding Reactors where standard<br />
specification is generally followed by utilities, requirements of power<br />
transformers vary depending upon the system design. Hence a tailor made<br />
product becomes the answer. Depending upon the requirements two winding/<br />
three winding/ auto connection/ split winding arrangement with ON LOAD or<br />
OFF CIRCUIT tap changer, five limbs/ three limbs core construction, welded<br />
or bolted tank construction are adopted.<br />
Variation in capacity, impedance and transport profile result in different<br />
sizes of transformer. Refer VoI I for specific requirements of the equipment.<br />
1.1.2 SHUNT REACTORS<br />
Shunt Reactors are used in high voltage systems to compensate<br />
capacitive generation from long lightly loaded overhead lines or extended cable<br />
systems and also for control of dynamic over voltages.<br />
Gapped core construction is preferred for high system voltages over<br />
coreless construction due to the high energy density that can be achieved in<br />
gapped core construction. The core sections between consecutive air gaps<br />
are moulded in epoxy resin to prevent movement between individual laminations.<br />
The spacers forming the air gaps are blocks of ceramics with a high modules<br />
of elasticity and the whole stacking of core modules is cemented together<br />
during the assembly to form a solid column without possibility of rocking , or<br />
rubbing between individual parts.<br />
The core segments are of radial laminated configuration. The radial<br />
laminations prevent fringing flux from entering flat surfaces of core steel which<br />
would result in eddy current overheating and hot spots.<br />
Five limbed core construction is adopted to achieve high zero sequence<br />
impedance. In addition to the three gapped core limbs with windings, there<br />
are two continuous outer return limbs. The two unwound side limbs help in<br />
achieving zero sequence impedance approximately equal to the positive<br />
sequence impedance. Other construction type can be a three limbed<br />
construction. For single phase reactors e.g. 800 KV class middle leg wound<br />
with two return legs type of construction is adopted.<br />
Interleaved disc winding has been used for rated voltages 220 KV and<br />
above. This type of winding configuration provides better impulse voltage<br />
distribution. For lower voltage classes a continuous disc winding or a multi<br />
layer helical winding are used. The tank is rectangular in construction with flat<br />
cover welded to the tank rim at top. The associated cooling control equipment<br />
is housed in a tank mounted weather proof marshalling box. The reactors are<br />
equipped with all standard measuring and controlling fittings and accessories<br />
as described in Volume I.<br />
Prepared By Samvet Lahari, <strong>Bhopal</strong>. Phone- 5277412
Reactors have been designed for resting on concrete foundation as shown<br />
in the foundation plan drawing. Rollers have been provided only for movement<br />
of the reactor at site.<br />
1.1.3 NEUTRAL GROUNDING REACTOR<br />
When single pole reclosing is used on lines, the Neutral Grounding Reactor<br />
is used.<br />
The Neutral Grounding Reactors are connected between neutral point<br />
of 400 kV/800 KV reactors and earth, where the neutral of shunt Reactor is<br />
suitable for 145 kV class insulation.<br />
The reactors are oil immersed type ONAN cooled (oil immersed with<br />
natural air cooling) with continuous rating of 10/15 Amps and a 10 sec. rating<br />
as indicated in the Rating Data sheet. As continuous losses of the reactors are<br />
negligible, reactor tank surface is adequate for dissipation of these losses.<br />
Hence radiators are not provided.<br />
Considering linear impedance characteristic requirement upto rated short<br />
time current a core less design with magnetic shielding of CRGO sheet has<br />
been made. The magnetic circuit, therefore consists of rectangular frame of<br />
CRGO steel lamination packets of adequate area. Area of magnetic circuit is<br />
selected such that saturation does not take place under short time current. A<br />
rigid clamping structure is provided for clamping of magnetic frame and a very<br />
low flux density is used to minimize the vibration and achieve linear impedance<br />
characteristic.<br />
The graded disc type concentric winding suitable for a rated voltage of<br />
145 kV and basic insulation level of 550 kVp has been provided without core<br />
inside. Winding is held in position by way of special insulation structure inside<br />
winding and finally kept under pressure between top and bottom yokes of<br />
magnetic frame. Return path of flux is provided by way of two return limbs.<br />
The line terminal is taken out through the tank cover via 145 kV, 800<br />
Amps OIP condenser bushing provided with suitable terminal connector. The<br />
neutral lead is taken out through the tank cover via a 36kV, 630 Amps porcelain<br />
bushing.<br />
The tank is of welded mild steel plate construction shot blasted on the<br />
inside and outside to remove scales before painting. The tank is painted on the<br />
inside with yellow paint and its outside surface is painted with two coats of<br />
primer paint and finishing coat, of light grey paint to shade 631 of IS:5. This<br />
is a standard painting scheme followed for all equipment .<br />
The fittings include a conservator with a magnetic oil gauge, pressure<br />
relief device, drain and filter valves, sampling valves, thermometer pockets,<br />
Buchholz relay, temperature indicator for oil and silicagel breather .<br />
These reactors are designed for mounting directly on plinth.<br />
1.2 TRANSPORT OF TRANSFORMER/REACTOR<br />
Power Transformers and Reactors hereinafter referred as "Transformers,"<br />
depending upon the restriction imposed by transport weight and/or other<br />
considerations, have to be transported either filled with oil or nitrogen as per<br />
the description given below. The transformer is loaded on wagon as per loading<br />
gauge drawing prepared in each case.<br />
Prepared By Samvet Lahari, <strong>Bhopal</strong>. Phone- 5277412
1.2.1 WITH OIL<br />
The Transformer is filled with oil such that about 10% of the tank<br />
volume is left clear for expansion to limit the excess internal air pressure to<br />
0.35 kg/cm 2 . Fittings dismantled before transport are packed in packing cases<br />
in line with shipping list.<br />
All openings resulting from removal of fittings for shipment are sealed<br />
with suitable gasketted blanking plates during transport.<br />
The balance oil quantity required for the complete filling of the reactor is<br />
supplied separately.<br />
A transformer despatched according to this method can be stored at<br />
site or elsewhere for one year provided, that all insulating materials are covered<br />
with oil and silicagel breather is mounted and quality of oil is maintained as per<br />
IS: 1866. Measures to be taken on reception at site are given clause 2.1<br />
1.2.2 WITH NITROGEN<br />
Large oil filled transformers/reactors are not normally oil filled during<br />
shipping due to weight limitations. To protect the active parts against moisture<br />
the transformer tank is filled with dry Nitrogen at a positive pressure of 0.175<br />
kg/cm 2 (2.5 psi) at <strong>BHEL</strong> works before despatch. The internal pressure at the<br />
time of shipment is painted on the tank.<br />
All openings resulting from the removal of fittings for shipment are<br />
sealed with suitable gasketted blanking plates during transport.<br />
A Transformer despatched according to this method should normally be<br />
stored upto 3 months after arrival at site or elsewhere.<br />
For control of gas pressure and maintaining the pressure during transport<br />
and possible storage before assembling, the transformer is equipped with an<br />
automatic device. This device is called two stage N 2 regulator and is kept in a<br />
steel box and mounted on the frame provided on tank side for keeping two<br />
back up Nitrogen cylinders. Nitrogen regulator is connected to two cylinders<br />
by copper tubes and to tank by a rubber hose as shown in the Fig. 1.1.<br />
N 2 regulator reduces cylinder high pressure of 120 to 140 kg/cm 2 to<br />
required low pressure of 0.175 kg/cm 2 in two stages. One gauge provided on<br />
the first stage indicates the cylinder pressure, whereas other gauge provided<br />
on second stage indicates the tank pressure. Regulator is fixed at factory.<br />
When tank pressure falls below 0.15 kg/cm 2 , due to leakage/fall of<br />
ambient temperature, regulator automatically feeds the gas from cylinders, to<br />
build up required pressure in the tank.<br />
The gas consumption during transport and possible storage is difficult<br />
to estimate as it depends on ambient temperature variation, possible leakages<br />
as well as on the duration of transport and storage. However, two back up<br />
cylinders are provided to meet the gas requirement. Normally one cylinder is<br />
kept open and the other shut. When the pressure of first cylinder falls to 10<br />
kg/cm 2 this should be considered as empty and immediately its valve should<br />
be closed and the valve of second cylinder should be opened.<br />
When cylinder is required to be removed for refilling, disconnect copper<br />
tubing from cylinder valve.<br />
Prepared By Samvet Lahari, <strong>Bhopal</strong>. Phone- 5277412
Use only dry Nitrogen gas to IS:1747 with 50 ppm moisture and 1%<br />
oxygen by volume.<br />
If the storage time exceeds 3 months, the transformer is filled with oil<br />
according to directions given in clause 2.5. If for some reason oil filling is not<br />
possible, then nitrogen must be continuously maintained at a positive pressure.<br />
Measures to be taken on receipt at site are given in clause 2.1.<br />
1.2.3 INSTRUCTIONS FOR FILLING DRY PURE NITROGEN GAS WITH<br />
BACK UP CYLINDERS (AT WORKS)<br />
Lower the oil level to the minimum necessary to dismantle the items<br />
(such as bushing and turrets) which must be removed for shipping.<br />
Pull 500 mm mercury vacuum after blanking off all openings.<br />
Break the vacuum by admitting dry nitrogen through a convenient valve<br />
at the top of the tank and drain the oil completely.<br />
Continue to supply nitrogen until it maintains a steady pressure of 0.17<br />
± 0.02 kg/cm 2 above the atmosphere.<br />
Pressure of nitrogen gas shall be maintained at 0.17 ± 0.02 kg/cm 2 at<br />
same reference temperature. Pressure would be monitored by taking three<br />
readings within 24 hours to ensure that there is no leakage of gas.<br />
Shut off the gas supply valve and fit dry nitrogen back up cylinders<br />
through nitrogen regulator valve.<br />
Prepared By Samvet Lahari, <strong>Bhopal</strong>. Phone- 5277412
¦ÉÉMÉ-2<br />
ºlÉÉ{ÉxÉ<br />
SECTION-2<br />
INSTALLATION<br />
Prepared By Samvet Lahari, <strong>Bhopal</strong>. Phone- 5277412
2. INSTALLATION<br />
SECTION 2<br />
2.1 RECEPTION AND ASSEMBLING OF TRANSFORMER/REACTOR<br />
DESPATCHED PARTLY DISMANTLED AND FILLED WITH NITROGEN.<br />
To ensure that a Transformer will function satisfactorily it is important<br />
that handling, lifting, storing and assembling are carried out with great care<br />
and cleanliness by experienced personnel who know the various working<br />
operations very well.<br />
This section gives <strong>instruction</strong>s how handling, lifting, storing and<br />
assembling should be carried out. For large Transformers it is recommended<br />
that the work is done by <strong>BHEL</strong> or is under supervision by experts from <strong>BHEL</strong>.<br />
2.1.1 INSPECTION<br />
In connection with receiving and unloading at site, and at the final storing<br />
place before assembling, the transformers shall be inspected carefully. External<br />
visible damages as dents, paint damages etc. may imply that the transformer<br />
has been subjected to careless handling during transport and/or re-loadings,<br />
and a careful investigation is therefore justified.<br />
After the arrival of the material at receiving points, the customer should,<br />
in case of possible damage/loss of any component, make the necessary claims<br />
with the contractors representatives under intimation to supplier so that such<br />
claims can be registered with the transport agents. Before unloading, the<br />
condition of packing and of the visible parts should be checked and possible<br />
traces of leaks verified (condenser bushings). If necessary, appropriate<br />
statements and claims should be made.<br />
Drums containing oil which have been despatched separately should be<br />
examined carefully for leaks or any sign of tampering. All drums are despatched<br />
filled up to their capacity and any shortage should be reported.<br />
In order to protect the active part against moisture, the transformer<br />
tank is filled with nitrogen during transport at an over pressure of 0.17 kg/<br />
sq.cm (2.5 psi) approximately at room temperature.<br />
Check immediately the gas pressure at the arrival. A positive pressure<br />
indicates that the tank and the transformer components respectively are tight,<br />
and that the active part including the insulation materials is dry.<br />
If there is no positive gas-pressure, transformer should be immediately<br />
filled with dry Nitrogen gas at a pressure of 0.17 kg/cm 2 (2.5 psi) without loss<br />
of time as per <strong>instruction</strong>s given para 1.2.3<br />
Otherwise, it should be checked if the core isolation is satisfactory and<br />
that accessories packed separately have not been damaged during the transport.<br />
Instructions for checking of the core isolation are given in clause 2.10<br />
2.1.2 UNLOADING<br />
Typical unloading arrangement of the transformer is shown in fig 2.1.<br />
Whenever rollers/trolleys are supplied with transformer, movement of<br />
transformer at site is carried out by mounting these rollers/trolleys. For mounting<br />
of rollers refer roller mounting drawing included in Vol.I.<br />
Prepared By Samvet Lahari, <strong>Bhopal</strong>. Phone- 5277412
Alternatively for movement of transformer from loading bay to actual<br />
site of the equipment, skidding on greased rails etc. can also be resorted to.<br />
2.1.3 STORING<br />
Dismantled equipment and components are packed to be protected<br />
against normal handling and transport stresses. The <strong>instruction</strong>s for lifting<br />
given on the packages, must be complied with to avoid damages.<br />
Goods stored outdoors must not be placed directly on the ground, and<br />
should be covered carefully with tarpaulin or similar material.<br />
Oil drums should be stored in horizontal (lying) position with both the<br />
bungs also in horizontal position.<br />
2.1.4 LIFTING<br />
Lifting devices on the transformer tank are dimensioned for lifting of the<br />
complete transformer filled with oil. The positioning of the lifting devices,<br />
permissible lifting angles, minimum height to crane hook and transformer<br />
weight, appear from the OGA drawings. Check at lifting of complete transformer<br />
that the lifting wires/ropes are not in contact with bushing or other components<br />
on the cover.<br />
For lifting with hydraulic jacks, the transformer is provided with jacking<br />
pads dimensioned for lifting of complete transformer filled with oil. The position<br />
of the pads appear on the OGA drawings. If active part is to be lifted refer<br />
<strong>instruction</strong>s given in clause 2.7.<br />
2.1.5 LOCATION AND SITE PREPARATION<br />
a) Reactor shall always be placed on concrete plinth without rollers as<br />
per foundation plan drawing whereas transformer may be even placed<br />
with rollers. Therefore it is very important to refer foundation drawing<br />
before placing the transformer/reactor on final location.<br />
b) Transformer/reactor should be placed on the foundation so that easy<br />
access is available all around and diagram plates, thermometers, valves,<br />
oil gauges, etc. can be easily reached or read. Adequate electrical<br />
clearances are also to be provided from various live points of the<br />
transformer to earthed parts.<br />
c) ONAN type transformers/reactors depend entirely upon the surrounding<br />
air for carrying away the heat generated due to losses. For indoor<br />
installation, therefore, the room must be well ventilated so that the<br />
heated air can escape readily and be replaced by cool air . Air inlets<br />
and outlets should be of sufficient size and number to pass adequate<br />
air to cool the transformer. The inlets should be as near the floor as<br />
possible and outlets as high as the building will allow. Where necessary,<br />
exhaust fans can be installed for the purpose.<br />
d) The transformers should always be separated from one another and<br />
from all walls and partitions to permit free circulation of air. In this<br />
connection reference is also drawn to IS: 10028 (Part II).<br />
Prepared By Samvet Lahari, <strong>Bhopal</strong>. Phone- 5277412
e) Where rollers are not fitted, level concrete plinth with bearing plates<br />
of sufficient size and strength can be adopted for outdoor transformers.<br />
To prevent the formation of rust, it is essential to avoid presence of<br />
air and water in the space between the plinth and the base of the<br />
transformer by use of cretex or similar bituminous compound.<br />
f) Where rollers are fitted, suitable rails or tracks should be used and<br />
the wheels locked to prevent accidental movement of the transformer.<br />
Where walls are provided, it should be ensured that the transformer<br />
gets a good ventilation as mentioned above for indoor transformers.<br />
Provision should be made for the emergency drainage of the oil from<br />
the transformers (e.g. in case of fire in neighbouring apparatus or<br />
bushing or the transformer tank), by surrounding the transformer plinth<br />
with sump filled with small pebbles.<br />
2.1.6 INTERNAL INSPECTION AND CHECK POINTS FOR ASSEMBLING<br />
THE TRANSFORMER/REACTOR<br />
(a) Check-points before starting assembly:<br />
1. Conditions of leads.<br />
2. Bracing, clamping of leads.<br />
3. Connections.<br />
4. Tapchanger checks.<br />
5. General conditions of insulation.<br />
6. Core check that it has not moved in transit.<br />
7. Core-ground; this is checked with the megger after removing earth<br />
connection.<br />
8. CTs, including the secondary leads and their passage through metal<br />
parts.<br />
9. Check that shipping frame for bushings have been removed.<br />
10. Check that coil position has not moved in transit.<br />
11. Check for dirt, metal swarf, moisture.<br />
12. Check that the bushing leads set without being too close to ground<br />
or other points of different potential.<br />
(b) Check-points during Assembly<br />
By means of the Part list and the transformer/reactor OGA, the assembling<br />
of a fully completed transformer is carried out according to the following<br />
<strong>instruction</strong>s. The following precautions are to be taken:<br />
(i) Fire-fighting equipment shall be available at the oil-treatment<br />
equipment as well as at work on and adjacent to the transformer .<br />
(ii) Welding work on or adjacent to the transformer shall be avoided, but<br />
if this is not possible, the work shall be supervised by fire-protection<br />
personnel.<br />
(iii) Smoking on or near the transformer shall not be allowed.<br />
(iv) Transformer tank, control cabinet etc. as well as assembling and oiltreatment<br />
equipment shall be connected with the permanent earthing<br />
system of the station.<br />
Prepared By Samvet Lahari, <strong>Bhopal</strong>. Phone- 5277412
(v) Check that there is no overpressure in the transformer when blanking<br />
plates or connection lids are to be opened.<br />
(vi) All loose objects, tools, screws, nuts etc., shall be removed from the<br />
transformer cover before opening the connection and blanking lids.<br />
(vii) All loose objects (tools, pencils, spectacles etc.,) shall be removed<br />
from the boiler-suit pockets etc. before starting the work through<br />
man holes.<br />
(viii) Tools to be used inside the transformer/reactor -e.g. for tightening of<br />
screw-joints- shall be fastened to the wrist or another fixed point by<br />
means of cotton tape or string.<br />
(ix) Tools with loose sleeves and tools with catches must not be used at<br />
work inside the transformer.<br />
(x) Greatest possible cleanliness shall be observed at work inside the<br />
transformer/reactor, and at handling of parts to be mounted inside<br />
the transformer.<br />
(xi) Fibrous cleaning material should not be used as it can deterioate oil<br />
when mixed with it.<br />
(xii) All components despatched separately should be cleaned inside and<br />
outside before being fitted.<br />
(xiii) A transformer/reactor is best protected from damp hazard by<br />
circulating warm, dry, deaerated oil through it until it temperature is<br />
5° C to 10 0 C above ambient. This should be done before allowing<br />
external excess to the interior of the tank. The warm oil should be<br />
circulated all the time transformer is open to atmosphere,<br />
(xiv) Oil pump & all joints in the oil pipe work should be airtight to avoid<br />
entrance of air through leakage joints.<br />
(xv) The active part (core and winding) should be exposed to the<br />
surrounding air as short time as possible. Open therefore only one<br />
blanking plate or connection lid at a time for remounting of bushings,<br />
valves etc.<br />
(xvi) Objects which-despite all precaution are dropped inside transformer/<br />
reactor, must absolutely be brought up from the equipment.<br />
(xvii) Check that the oxygen content inside the transformer tank is minimum<br />
20% if a person is to enter the tank.<br />
2.1.7 ASSEMBLY OF WHEELS<br />
Mounting of wheels under reactor/transformer is to be done as per roller<br />
arrangement drawing. The reactor however in service, is to be placed on<br />
plinth with anti-earthquake fastening without rollers. Transformer placement<br />
can be with or without rollers as per applicable OGA/foundation drawing.<br />
2.1.8 ASSEMBLY OF BUSHINGS<br />
In case the bushings are mounted on turrets on the transformer/reactor<br />
cover, they are either delivered mounted on their turret or -incase of large<br />
bushings dismantled from the turrets.<br />
Prepared By Samvet Lahari, <strong>Bhopal</strong>. Phone- 5277412
The turrets are often individually adapted; check therefore that they are<br />
re-mounted in correct places, which appear from the OGA drawing and ,part<br />
list.<br />
Assembling of bushings is carried out according to the detailed<br />
information documents available.<br />
2.1.9 ASSEMBLY OF VALVES<br />
Valves which may affect the loading gauge, or will be subjected to<br />
damages, should be dismounted before delivery. Re-mount the valves -the<br />
positionings appear from the OGA drawing and part list. The gasketting surfaces<br />
shall be cleaned well and new gaskets fitted. Check that all valves are closed.<br />
2.1.10 ASSEMBLY OF COOLING DEVICES<br />
Valves which are not dismantled like shut-off valves for radiators, coolers<br />
and possible headers shall be provided with blanking plates during the transport.<br />
Remove the blanking plates when the assembling of the coolers is to be<br />
started. Check first that the valves are closed.<br />
Check that each radiator and possible header are assembled in the correct<br />
positions according to OGA drawing. In case of OFAF or OFWF cooler mounting<br />
shall be done as per the relevant leaflet given in Vol.I<br />
The shut-off valves against the transformer tank shall be closed until<br />
the oil-filling is started.<br />
2.1.11 ASSEMBLY OF OIL CONSERVATOR<br />
The conservator, which may be with or without aircell is assembled<br />
either on the transformer, or on a separate frame. Before the conservator is<br />
assembled it shall be checked that belonging equipment -e.g. Oil-level indicator<br />
-functions satisfactorily.<br />
The breather is connected to the oil conservator, and it is very important<br />
that joints and couplings in the pipe between breather and conservator are air<br />
tight. Refer Clause 2.6 for detailed <strong>instruction</strong> for oil filling.<br />
2.1.12 ASSEMBLY OF PIPE WORK<br />
Pipes with flanges for connection of conservator, radiators, as well as<br />
pipes for equalising of turrets etc. are mostly delivered completely ready for<br />
assembling according to OGA & part list.<br />
In certain cases -e.g. at a separately assembled oil conservator -certain<br />
fitting and welding of pipes and flanges on site is however required. Instruction<br />
for such assembly of external pipes is given in Clause 2.3<br />
2.1.13 FLANGES, BLANKING PLATES<br />
When re-mounting blanking plates, connection flanges etc., the gasketting<br />
surface shall be cleaned well and new gaskets fitted.<br />
Prepared By Samvet Lahari, <strong>Bhopal</strong>. Phone- 5277412
2.1.14 ACCESSORIES<br />
Accessories like cooling fans, pumps, OLTC and components for<br />
supervision and control, oil-level indicator, flow indicators, gauges, Buchnolz<br />
relay, PRV, thermometers etc. are assembled according to leaflet/description<br />
valid for the components (refer Vol. I).<br />
2.1.15 CONTROL CABLING<br />
Re-assemble the control cables according to the drawing of wiring system<br />
and connect the cable ends to terminal blocks in instruments, terminal boxes,<br />
junction boxes and control cabinets according to valid connection diagram.<br />
2.1.16 GASKETS<br />
The sealing system normally used against oil and gas in <strong>BHEL</strong>'s<br />
transformers and belonging components has rubber gaskets in grooves and<br />
nitrile rubber bonded cork gaskets at other places. Refer clause 2.8 for general<br />
information and assembly <strong>instruction</strong>s for gasket mounting.<br />
2.1.17 OIL FILLING<br />
The completely mounted Transformer is oil-filled according to directions<br />
in Clause 2.5 & 2.6. The oil shall be treated according to Clause 2.4.<br />
The lower and upper shut-off valves for radiators/coolers and possible<br />
headers shall be open during evacuation and oil-filling.<br />
If coolers are placed on suspension beams, which are mounted at right<br />
angle to the tank, the suspension beams shall be supported against the ground<br />
during the evacuation. Also radiators mounted on the tank wall shall be<br />
supported in a similar way.<br />
The hose for filling of oil is connected to the bottom valve of the<br />
transformer which must not be opened until the hose has been deaerated and<br />
completely filled with oil.<br />
2.1.18 CLEANING & PAINTING<br />
The transformer and its equipment are cleaned carefully from dirt, oil,<br />
lubricating grease, and damaged surfaces are touch-up painted with the primer<br />
paints and finish paints delivered as per clause 2.11.<br />
2.1.19 EXCHANGE OF BUSHING<br />
When exchanging a damaged bushing or other component on the cover<br />
of a fully oil- filled transformer, we should proceed according to the following:<br />
Close the valve in the pipe between the transformer and the oil<br />
conservator. Pump oil from the transformer tank into the oil conservator so<br />
that the oil quantity which need be drained off to lower the oil-level enough<br />
below the transformer cover is pushed to the conservator. As the oil is being<br />
transferred from tank to conservator, fill up the tank with dry nitrogen via a<br />
suitable valve on the cover or in turrets.<br />
Exchange the faulty bushing and transfer then the oil from the conservator<br />
to the tank by opening the valve in the pipe between conservator and main<br />
tank. De-air the bushings and turrets.<br />
Prepared By Samvet Lahari, <strong>Bhopal</strong>. Phone- 5277412
2.2 STORING OF TRANSFORMER/REACTOR DESPATCHED FILLED WITH<br />
NITROGEN<br />
2.2.1 STORING BEFORE COMPLETE ASSEMBLING<br />
The storing place should be easily accessible for inspection and<br />
maintenance of the transformer. The bedding for the equipment should be<br />
larger than its bottom surface and dimensioned for the load. The transformer<br />
is placed on boardings or beams so that good ventilation is obtained underneath<br />
the transformer bottom.<br />
Before storing, the transformer is inspected according to directions in<br />
Clause 2.1 "Reception and assembling of transformer/reactors despatched<br />
partly dismantled and filled with nitrogen".<br />
A transformer without remarks may be stored up to 3 months after<br />
arrival at the site without oil-filling. During the storing time, the inert gas<br />
(nitrogen) filling shall be maintained and pressure regulated, so that exposure<br />
of active part to atmosphere is avoided.<br />
If the storage time is judged to exceed 3 months, the transformer should<br />
be provided with oil conservator including oil-level indicator and breather, and<br />
oil-filled according to Clause 2.5. "Oil filling under vacuum". Certain valves<br />
must be re-mounted to enable the oil-filling being carried out. Furthermore, at<br />
the time at oil-filling of a completely assembled transformer, certain rules in<br />
Clause 2.5 & 2.6 must be complied with absolutely.<br />
Wherever possible it would be most desirable to keep the transformer<br />
energized even at a low voltage so that its temperature is higher than the<br />
ambient temperature. The low voltage may be applied under open circuit or<br />
short circuit conditions. It may be ascertained whether partial cooling is required<br />
in such a case. The oil quality should also be periodically monitored. If for<br />
some reason, oil filling cannot be carried out after a storage period longer than<br />
3 months, the nitrogen pressure shall be maintained and supervised carefully.<br />
If the storage time without oil exceeds 18 months <strong>BHEL</strong> should be consulted<br />
about measures to be taken.<br />
2.2.2 STORING OF COMPONENTS AND ACCESSORIES BEFORE<br />
COMPLETE ASSEMBLING<br />
Independent of the duration of the storing time, the directions below<br />
apply for dismounted components and accessories, as well as for material to<br />
be used in connection with the assembling work.<br />
(a) Storing indoors<br />
In such a room, the following articles should be stored:<br />
(i) Insulation material as paper, pressboard, bakelite, wood, cotton tape<br />
etc.<br />
(ii) Insulated details as paper-insulated conductors, pressboard insulated<br />
shielding bodies etc.<br />
(iii) Chemicals as solvents, glues, varnishes, hardeners etc.<br />
(iv) Breathers, drying agents.<br />
(v) Terminal boxes, connection boxes, control cabinets.<br />
(vi) Gas relays, oil-level indicators, thermometers, pressure valves etc.<br />
Prepared By Samvet Lahari, <strong>Bhopal</strong>. Phone- 5277412
(vii) MBox, OLTC motor drive, Fans, Pumps, Instruments & fittings.<br />
(Heating elements provided shall be connected to supply)<br />
(b) Storing outdoors<br />
The below components may be stored outdoors. They should be placed<br />
above ground and covered with tarpaulin etc.<br />
(i) Oil-conservator with blanking plates for all openings.<br />
(ii) Radiators and coolers with blanking plates for all openings.<br />
(iii) Structures, A frames, Pipe supports, Supports for oil-conservators,<br />
radiators, control cabinets etc.<br />
2.2.3 SUPERVISION<br />
During the storing time, the storing place, transformer/reactor<br />
components and accessories are inspected regularly. Tap changer if provided<br />
should be operated at 6 monthly intervals. Two or three runs from one end of<br />
the range to the other and back are sufficient. Observations, readings, measures<br />
and dates should be noted and <strong>BHEL</strong> should be contacted for directions about<br />
possible measures. Check at even intervals -and further more at weather<br />
changes as rain, storm, frost or thawing the foundation material (boardings,<br />
beams etc.) and the condition of the ground.<br />
Inspect the transformer/reactor periodically with regard to possible<br />
external faults and/or rust-damage.<br />
Check also that screws and nuts in sealing joints (covers, lids etc.) are<br />
tightened. Check every second week that the connected-in heating elements<br />
in control cabinets function.<br />
If the Transformer is inert gas filled, one shall check every second week<br />
the overpressure or inert gas consumption.<br />
If the reactor is oil-filled, one shall take oil-samples after 6 months, and<br />
then min. once a year. The oil is investigated with regard to Electric Strength<br />
(BDV) and moisture content.<br />
Inspect periodically stored components and accessories with regard to<br />
possible , external damages and/or rust damages. If any touching up of paint<br />
is required it should be carried out as per clause 2.11. Check at the same time<br />
that insulation material and insulated details are not damaged or have become<br />
dirty.<br />
2.3 ASSEMBLING OF EXTERNAL PIPES<br />
2.3.1 This technical description shall be applied at assembling of<br />
transformers, when external pipes, for some reasons, are not fully completed<br />
at delivery but require some kind of machining or fitting at site.<br />
At the design occasion it is judged which details that can be made fully<br />
completed in the workshop and which details that must be fitted into position<br />
at site. Fully completed details are delivered with complete surface treatment.<br />
Details of the pipe work despatched can be seen at shipping list.<br />
2.3.2 BREATHER PIPE<br />
The pipe is normally made of 15 NB painted steel pipe. The pipe shall be<br />
cleaned carefully after machining. Supplementary surface treatment is, not<br />
required normally.<br />
Prepared By Samvet Lahari, <strong>Bhopal</strong>. Phone- 5277412
It is very important that the pipe is tight. Possible leakage will cause<br />
moisture on the transformer with the service disturbances.<br />
Mounting of the breather pipe shall be as per OGA drawing.<br />
2.3.3. OIL CONSERVATOR<br />
For position of conservator along with necessary supports, refer OGA<br />
drawing.<br />
2.3.4 OIL CONSERVATOR PIPE<br />
The pipe has dimension 80 mm usually and has welded flanges. The<br />
pipe shall be painted internally with a yellow, oil-resistant paint, and externally<br />
with a paint specified on the drawing. The pipes shall always incline upwards<br />
minimum 2/3 degrees from the transformer.<br />
2.3.5 EQUALISING PIPES<br />
The pipe system in connection with the transformer cover is as a rule<br />
manufactured in workshop. The pipe between transformer and conservator<br />
may be pre-assembled.<br />
The pipe is provided with weld-flanges. No pipe part is allowed to be so<br />
long that internal inspection and cleaning is difficult to carry out. Besides<br />
straight extensions, each pipe part may contain one bend.<br />
The pipes shall always be placed with minimum 2/3 degrees inclining<br />
upwards from the transformer. Internal surface treatment is with yellow oil<br />
resistant paint. External surface treatment is made as specified on the drawing<br />
as per specification. Cleanliness is extremely important.<br />
2.3.6 COOLERS<br />
The positioning of the radiators/coolers is indicated on OGA drawing.<br />
These are positioned so that the highest point of the oil-pipe system is always<br />
positioned below the bottom level of the conservator.<br />
The pipe system is provided with filter valves at the start and finish to<br />
enable pumping the oil through the system.<br />
All places where air may be collected are provided with air release plugs/<br />
valves.<br />
2.3.7 COOLER PIPES<br />
The pipe having dimensions as per OGA drawing and may be provided<br />
with weld- flanges, expansion joints. No pipe part is allowed to be so long that<br />
internal inspection and cleaning will be difficult.<br />
The pipes shall be placed so that air release plugs will be positioned at<br />
the highest point of the pipe part. The pipes shall be painted internally with a<br />
yellow, oil-resistant paint and externally according to the paint as per<br />
specification.<br />
2.4 INSULATING OIL, QUALITY AND TREATMENT<br />
2.4.1 QUALITY<br />
The oil to be filled in transformer generally complies with the<br />
requirements of the customer's specification. The characteristics of fresh oil<br />
as per IS: 335 "Specification for New Insulating Oil" are given below:<br />
Prepared By Samvet Lahari, <strong>Bhopal</strong>. Phone- 5277412
CHARACTERISTICS AND PARAMETERS OF NEW<br />
INSULATING OIL<br />
Sr.No. Characteristics Unit Requirement<br />
1. Appearance The oil shall be clear,<br />
transparent & free from<br />
suspended matter or<br />
sediments.<br />
2. Density at 29.5°C gm/cc 0.89<br />
3. Kinematic Viscosity<br />
at 27° C (max.) Cst 27<br />
4. Interfacial tension<br />
at 27oC (Min) N/m 0.04<br />
5. Flash Point (Min) oC 140<br />
6. Pour Point (Max) oC -6<br />
7. Neutralisation value<br />
(Total acidity), (Max) mg/KOH/g 0.03<br />
8. Corrosive sulphur : Non-corrosive<br />
9. Electric strength<br />
(breakdown voltage)<br />
(Min)<br />
(a) New untreated oil, kV (rms) 30<br />
(If the above value is not<br />
obtained the oil shall be<br />
filtered in laboratory).<br />
(b) After filtration kV (rms) 60<br />
10. Dielectric dissipation<br />
factor (tan δ) at 90°C<br />
(Max) 0.002<br />
11. Water content (Max) ppm 50<br />
12. Specific resistance (Min)<br />
at900C ohm-cm 35x1012 at27OC ohm-cm 1500 x 1012 13. Oxidation stability<br />
a) Neutralisation value<br />
(Max) mg/KOH/g 0.4<br />
b) Total sludge after<br />
oxidation (Max) mg/KOH/g 0.10%<br />
14. Ageing characteristics<br />
after accelerated ageing<br />
(open beaker method<br />
with copper catalyst).<br />
a) Resistivity (Min)<br />
at 900C ohm-cm 0.2x 1012 at 270C ohm-cm 2.5 x 1012 b) Tan δ at 90°C (Max) 0.2<br />
c) Total acidity (Max) mg/KOH/g 0.05<br />
d) Sludge content by weight (Max) 0.05%<br />
15 Presence of oxidation Oil shall not contain<br />
inhibitor oxidation inhibitor<br />
Note: Methods of test shall be as per IS: 335<br />
Prepared By Samvet Lahari, <strong>Bhopal</strong>. Phone- 5277412
2.4.2 SUPPLY AND TESTING<br />
The transformer oil is despatched directly to site from oil refinery. The<br />
oil is thoroughly inspected and tested at oil supplier's works in presence of<br />
<strong>BHEL</strong> and/or customer's representative or their authorised representatives.<br />
Test certificate giving values obtained for all characteristics is issued.<br />
2.4.3 HANDLING<br />
The oil drums should be carefully handled at site, details of which are<br />
given in Clause 9.1of IS:1866.<br />
2.4.4 RECONDITIONING<br />
Transformer oil is usually contaminated during handling, transport and<br />
storage due to ingress of moisture and solid impurities. Hence, oil shall be<br />
vacuum filtered separately at 50 0 C to 60 °C using a suitable filtration machine<br />
and a spare clean tank before filling in the transformer. Details of filtration are<br />
given in Clause 9.2 of IS:1866. Oil treatment shall be terminated when the<br />
following parameters are attained.<br />
TABLE 2.1<br />
kV Class of transformer Recommended Permissible limit<br />
Electric Strength Moisture Content<br />
(BDV) in kV (Min) ppm (Max)<br />
Upto 145 60 20<br />
245 65 15<br />
420 70 15<br />
Storage tank shall be as per typical arrangement shown in Fig 2.2<br />
Electric strength and moisture content shall be determined following<br />
the test procedure of IS: 335.<br />
2.5 OIL FILLING UNDER VACUUM<br />
2.5.1 APPLICATION<br />
Transformers and Reactors with vacuum-proof tanks shall be filled with<br />
oil according to this method.<br />
2.5.2 STORING TIME<br />
Generally it applies that Transformers and reactors which during transport<br />
are filled with dry nitrogen on arrival at the site shall be evacuated and oil<br />
filled. Before storing, the equipment shall be inspected according to the<br />
directions given in Clause 2.1 "Reception and assembling of transformer/reactor<br />
despatched partly dissembled and filled with nitrogen". During the storing<br />
time, overpressure shall be maintained, and nitrogen consumption checked<br />
according Clause 2.2.<br />
Prepared By Samvet Lahari, <strong>Bhopal</strong>. Phone- 5277412
2.5.3 FLOW CHART FOR HANDLING<br />
In Annexure 2.1 is given a flow chart of handling procedures. The pressure<br />
should be measured at different times. The pressure is OK if it is maintained<br />
according to <strong>instruction</strong>s given in Clause 2.2. Reference is also drawn to para<br />
9.0 of IS: 1866 regarding handling and filling of oil.<br />
2.5.4 UNITS<br />
Annexure 2.1 gives the relation between different units.<br />
2.5.5 EVACUATION<br />
The transformer tank (excluding cooler bank & conservator) shall be<br />
evacuated to a pressure of 1.00 torr. max. The pressure shall be maintained<br />
for the time given in Table 2.2.<br />
TABLE 2.2<br />
VACUUM TREATMENT<br />
System Voltage Evacuate and hold Standing time after oil<br />
vacuum for circulation before<br />
application of voltage<br />
kV hours hours<br />
Upto 145 12 12<br />
145 & upto 420 24 48<br />
Above 420 36 120<br />
The equipment required for vacuum treatment and oil-filling under vacuum<br />
should generally be as per Annexure 2.2. The transformer tank and electrical<br />
terminals shall be earthed for safety reasons.<br />
No electrical test on the Transformer is permitted during the evacuation.<br />
Fig. 2.3 shows a typical example of pipe work and valve positioning.<br />
Oil conservators are not evacuated. Valve 7 shall be closed. Valve 6<br />
shall be open unless a breather is fitted.<br />
2.5.6 OIL FILLING<br />
2.5.6.1 OIL QUALITY<br />
The transformer/reactor shall be filled under vacuum with oil which has<br />
been purified and degassed according to Clause 2.4<br />
2.5.6.2 OIL FILLING IN MAIN TANK<br />
The oil shall be heated to a temperature of 50 0 - 60°C measured at the<br />
filter outlet valve. The pressure during the filling shall be max. 1 torr. During<br />
the oil-filling, a transparent plastic tube (5) can be used as an oil-level gauge.<br />
The tube which should be a wall thickness of 5-8 mm, may be connected to a<br />
top and a bottom valve on the transformer.<br />
Prepared By Samvet Lahari, <strong>Bhopal</strong>. Phone- 5277412
Oil-filling of the tank is done through valve (12) at a low level on the<br />
transformer and at a maximum rate of 4-5 kL/hour. The pressure in the oil<br />
pipes shall be kept positive and shall be checked by a manometer 13 (if<br />
provided). When the oil-level has reached about 50 mm below the cover/the<br />
vacuum pump is stopped it is preferred that dry nitrogen is introduced in the<br />
tank by opening valve (8). Valve (7) is then opened .and valve (6) closed and<br />
the filling is continued in tank and conservator until the correct oil- level has<br />
been reached in the conservator.<br />
Conservator supplied with rubber air cell shall be filled according Clause<br />
2.6. For oil filling in diverter switch assembly of a OLTC refer leaflet (Vol.1).<br />
Separate vacuum-proof cooler system/radiators can be evacuated for<br />
about 1-2 hours and filled separately with purified and degassed oil. The oil is<br />
then circulated through the vacuum filter at least twice via drain valves as<br />
near as possible to the transformer. When the oil circulation has been completed<br />
the valves between coolers and main tank shall be opened.<br />
Care should be taken to keep all air release plugs and valves open to<br />
allow escape of trapped air during oil filling operation. These valves/plugs<br />
should be closed after completion of oil filling.<br />
2.5.7 HOT OIL CIRCULATION<br />
To facilitate oil-penetration and absorption of possible gas bubbles, the<br />
temperature of transformer shall-after completed oil-filling-be increased by<br />
circulating the oil through the vacuum filter and with circulation direction<br />
according to Fig. 2.4.<br />
The oil will be circulated through a vacuum filtration machine till the<br />
parameters are attained as per table 2.3 below.<br />
TABLE 2.3<br />
kV Class of<br />
Transformer<br />
Recommended Permissible Limits<br />
Electric Moisture Resistivity * Tan delta*<br />
Strength Content at 90oC at 90oC (BDV) in<br />
kV (min)<br />
ppm (Max) (Ohm-cm)<br />
Upto 72.5 40 25 1x1012 0.05<br />
145 50 20 1x1012 0.05<br />
245 and 420 60 15 1x1012 0.05<br />
* Subject to availability of testing facility at site.<br />
Method of test for Electric Strength and moisture content shall be as<br />
per IS:335.<br />
CAUTION:<br />
The temperature during oil circulation should not increase beyond 70 o C<br />
otherwise this may cause oxidation of oil.<br />
Prepared By Samvet Lahari, <strong>Bhopal</strong>. Phone- 5277412
2.5.7.1 SAMPLING<br />
Oil sampling at various stages shall be done in accordance with IS:<br />
6855. when samples are taken from transformer tank, oil will be drawn from<br />
bottom of the tank. When it is desired to know gas content and composition<br />
of dissolved gases in transformer oil before commissioning for reference<br />
purposes (required for interpretation of Dissolved Gas Analysis results during<br />
service), sampling shall be done as per IS 9434.<br />
2.5.8 STANDING TIME<br />
Standing time is the time between 'finished oil circulation' and<br />
'energisation'. The time appears form table 2.2.<br />
2.5.9 FINAL OIL FILLING OF TRANSFORMERS/REACTORS DESPACTCHED<br />
OIL FILLED.<br />
Smaller transformers/reactors are often factory-filled with degassed oil<br />
up to about 10% below the cover and transported in this condition. The final<br />
filling up to the correct level in the conservator is made at site.<br />
2.5.9.1 TRANSFORMERS/REACTORS WITH SYSTEM VOL TAGE < 36 KV<br />
Previously degassed oil (e.g., at the factory) stored in tight drums may<br />
be used for the filling. Check the dielectric strength of the oil which should be<br />
as per Cluase 2.4.4. If accepted, the oil is pumped into the conservator and in<br />
this way fed into the tansformer. To prevent any free water in the drums from<br />
entering the reactor the opening of the suction tube must lie 0.1 m above the<br />
lowest point in the drum. A suitable valve on the cover and/or valves or upper<br />
tightening nuts at the bushings have to be opened for complete removal of air<br />
below the cover and in the bushings. When the oil is seeping out at these<br />
points, shut the valves and tighten the nuts at the bushings.<br />
2.5.9.2 TRANSFORMERS/REACTORS WITH SYSTEM VOLTAGE > 36 KV<br />
The filling is performed as described above, but at least a paper filter<br />
must be used for drying the oil.<br />
2.6 OIL FILLING INSTRUCTIONS FOR CONSERVATORS WITH AIR CELL<br />
2.6.1 INTRODUCTION<br />
In all transformers specially in high voltage class, maintenance of<br />
insulating oil notably its dielectric property forms one of the determining factors<br />
of reliability of equipment in service. Oxidation and contamination of<br />
transformers/reactor oil can be avoided in a simple and effective way by use<br />
of above oil preservation system. The complete system is known as<br />
"Conservator with Air Cell".<br />
In this oil preservation system a flexible air cell made of oil resistant<br />
nitrile rubber is placed inside the conservator and floats on the oil surface. The<br />
air cell inflates or deflates as the oil level in the conservator falls or rises<br />
depending on the ambient temperature and load on the reactor. The inside of<br />
the rubber bag (Air Cell) is put into communication with atmosphere by means<br />
of a silica gel breather which ensures dry atmosphere inside the air cell. In<br />
addition to the above this system provides following advantages.<br />
(i) It avoids saturation of absorbed gases.<br />
Prepared By Samvet Lahari, <strong>Bhopal</strong>. Phone- 5277412
(ii) As no gas is used in this system, which operates at constant<br />
pressure, this formation of gas bubbles at low ambient temperature<br />
and load is eliminated. The system thus preserves the oil quality<br />
particularly its dielectric properties.<br />
The conservator with air cell is provided with a magnetic oil gauge<br />
having one electrical contact. The indication shown on the dial physically<br />
corresponds to the oil level in the conservator which is due to balance of<br />
static pressure between the oil of the conservator and the atmospheric air<br />
inside the air cell. This system is also provided sometimes with a set of pressure<br />
and vacuum valves. These valves operate to pass either oil or air in the event<br />
of over filling or under filling the conservator during installation.<br />
2.6.2 DESCRIPTION OF OPERATION<br />
Figure 2.5 indicates the general arrangement of oil preservation system,<br />
The oil connection between conservator and transformer tank is made through<br />
Buchbolz relay and valves are provided in between.<br />
The flexible air cell is connected to the top of the conservator through<br />
gasket ted joint. Under normal condition air cell is completely surrounded by<br />
oil and floats in the conservator. The air cell inflates/deflates as the oil volume<br />
changes. The float of the MOG which is always in contact with under side of<br />
the air cell moves up and down and indicates the oil level. The cell will sink in<br />
the remote event if it is damaged and MOG alarm will operate. The conservator<br />
then functions as a conventional conservator without effecting the performance<br />
of the transformers/reactor.<br />
2.6.3 INSTALLATION<br />
This system is shipped separately from main tank. The air cell is shipped<br />
fitted in the conservator. A low positive pressure of less than .07 kg/sq.cm (1<br />
psi) is maintained to avoid excessive movement of air cell in the conservator<br />
during transit. MOG is also shipped fitted on the conservator. Install the<br />
conservator and associate parts except breather as per transformers/reactor<br />
outline drawings and assemble oil pipe work.<br />
2.6.4 OIL FILLING<br />
The following procedure is recommended.<br />
(i) Close and blank the valve (14) to isolate the conservator from main<br />
tank. Fill the oil in transformer under vacuum upto Buchholz level as<br />
per <strong>instruction</strong>s given else where. '<br />
(ii) After filling the oil in transformer and breaking the vacuum, oil can<br />
be filled in the conservator either through reactor or by drain valve<br />
(4).<br />
(iii) Remove the inspection cover (11) provided on the side of the<br />
conservator and check the air cell assuring that it is inflated. The air<br />
cell must remain in fully inflated condition during oil filling operation.<br />
If the air cell is found deflated fit the inspection cover and inflate the<br />
air cell with dry air/nitrogen gas to 0.035 kg/sq.cm max. through<br />
connection (8). A gauge may be put by removing plug (10). After<br />
filling close these connections.<br />
Prepared By Samvet Lahari, <strong>Bhopal</strong>. Phone- 5277412
(iv) Remove air release plugs (5) (6) and (7) provided on top of the<br />
conservator.<br />
(v) Slowly pump the oil through the main reactor/drain valve (4).<br />
Temporarily stop filling operation when oil starts coming from opening<br />
(5) and (6) after ensuring that no air bubbles come out through these<br />
air release holes. Fit the two air release plugs.<br />
(vi) Continue oil filling till oil start coming from air release plug (7) stop<br />
oil after ensuring that no air bubbles come out. Fit the plug (7).<br />
(vii) Now release the air pressure held inside the air cell from point (8)<br />
and continue oil filling until magnetic oil gauge (3) indicates 35°Clevel.<br />
(viii) Remove oil pump and connect air cell to breather (9) from point (8).<br />
Also remove pressure gauge and put plug (10).<br />
(ix) The system is now properly filled. Air release plugs (5), (6) and (7)<br />
are fitted in normal operation.<br />
2.6.5 PRECAUTIONS<br />
(i) Oil filling in the conservator and also draining whenever required<br />
must be done very slowly. During oil filling, pressure in the air ce]l<br />
should not exceed 0.1kg/sq.cm (1.5 psi).<br />
(ii) If a pressure or vacuum is ever applied to the main reactor tank the<br />
conservator must be disconnected and a blanking plate fitted on<br />
shut off valve.<br />
(iii) Do not weld on conservator to avoid damage to the air cell.<br />
(iv) Once all the air has been driven out during oil filling in the conservator<br />
do not remove air release plugs (5), (6) and (7). Otherwise air will be<br />
sucked inside the conservator.<br />
2.6.6 MAINTENANCE<br />
Little maintenance work will normally be required except routine visual<br />
inspection. However, it is desirable to check the breather opening to ensure it<br />
is not blocked. Further silicagel should be regenerated/replaced when its colour<br />
changes from blue to pink.<br />
2.6.7 AIR CELL<br />
Air cell is made from Nylon fabric coated with Nitrile rubber, In the<br />
event it becomes necessary to replace or test the air cell for leaks the following<br />
method is recommended.<br />
(i) De-energise the transformers/reactor.<br />
(ii) Isolate the conservator by closing the valves (14).<br />
(iii) Drain the oil from the conservator through the valve (4) by removing<br />
air release plugs (5) and (6).<br />
Prepared By Samvet Lahari, <strong>Bhopal</strong>. Phone- 5277412
(iv) Remove inspection cover (11) if necessary, Install the pressure gauge<br />
on point (10).<br />
(v) Pressurise the air cell (2) by dry air/nitrogen to a max. pressure of<br />
1.5 psi and seal. Check the pressure for 6 hours.<br />
(vi) If leaks are found, air cell to be repaired by patching or replaced by a<br />
new air cell.<br />
(vii) For taking out the air cell from conservator, remove the air cell flange<br />
and loops from hooks provided on inside of the conservator top.<br />
Collapse the air cell slowly and fold, remove it from conservator very<br />
carefully.<br />
(viii) In the event air cell is not available immediately, conservator may be<br />
used as a conventional conservator.<br />
2.6.8 OIL PRESSURE TEST<br />
Oil pressure test on fully erected Transformer/Reactor to be conducted<br />
as per annexure 2.3 before hot oil circulation.<br />
2.7 UNTANKING OF ACTIVE PART<br />
2.7.1 GENERAL<br />
If for some reason it becomes necessary to untank the active part (core<br />
and windings) of a large reactor/transformer, it ought to be done under<br />
supervision by <strong>BHEL</strong> erectors. Universal <strong>instruction</strong> for the untanking procedure<br />
cannot be given, as the design practices of large equipment vary. The following<br />
general directions are, however, applicable in most cases.<br />
The untanking must be done indoors. If there is no suitable hall available,<br />
lifting can be done in the temporarily arranged room. e.g. a tent. The oil & the<br />
internal parts of the transformer must not in any case be exposed to rain or<br />
humidity.<br />
In case of bell shaped transformer, only bell cover is lifted for access to<br />
active part.<br />
2.7.2 OIL DRAINAGE<br />
Drain off the oil from the transformers/reactor either partly or completely.<br />
2.7.3 DISCONNECTING<br />
Disconnect leads to bushings, current transformers, winding temperature<br />
devices and earthing leads between active part and cover or tank side.<br />
Disconnections mentioned above can usually be made through handholes<br />
in cover or tank side.<br />
2.7.4 REMOVAL<br />
Remove all large bushings, cover mounted conservator and lightning<br />
arrestors (if provided). Break all connections between cover and tank-piping to<br />
oil conservator and cooler thermometers etc.<br />
Remove the cover bolts. If the cover is welded to the tank flange, free<br />
the cover according to directions given in Clause 2.9.<br />
Prepared By Samvet Lahari, <strong>Bhopal</strong>. Phone- 5277412
2.7.4.1 COVER<br />
When lifting the cover use the cover-lifting eyes which are designed for<br />
a minimum angle of 60 degrees between sling branches and the horizontal<br />
plane. The length of the sling should therefore be sufficient for at least this<br />
angle.<br />
Place the cover on suitable wooden supports and in such a way that<br />
thermometer pockets, small bushing etc. underneath the cover are not damaged.<br />
No grinding or cleaning up of the tank flange is to be carried out before<br />
the active part is lifted out of the tank.<br />
2.7.4.2 UNTANKING<br />
Loosen locking devices, if any, between top core clamps and tank side.<br />
Lift the active part by means of lifting eyes or lifting lugs provided on<br />
the top core clamps. The untanking height is shown on the outline drawing.<br />
To avoid damages on the active part it is important that it is centered carefully<br />
in the tank during lifting procedure.<br />
After untanking, place the active part on a horizontal foundation.<br />
2.7.5 RETANKING<br />
Grinding or/and cleaning up of the tank flange has to be done before the<br />
active part is lowered into the tank. Check that the tank inside is free from<br />
contaminations.<br />
Retanking is then done in the reverse order that is outlined above. Note<br />
that guiding pins or blocks are welded to the tank bottom to prevent the<br />
active part from moving in the tank. When lowering the active part, check that<br />
it fits exactly the guiding pins or blocks.<br />
2.7.6 REASSEMBLING<br />
Wipe the underside of the cover free from any dirt or foreign matter<br />
before lifting it into correct position above the reactor tank. Lower the cover<br />
the last few inches exactly into position without sliding on the gaskets.<br />
Reassemble bolts nuts of supporting devices. Weld the cover when the<br />
welded construction is used. Reassemble Bushings, conservator etc., and<br />
reconnect pipings, leads to bushings, current transformers, etc. Reassemble<br />
inspection covers.<br />
After the transformer is completely assembled, it may be necessary to<br />
dry it before oil fining- see clause 2.5.<br />
2.8 MOUNTING OF GASKETS<br />
2.8.1 The gaskets have a circular/flat cross-section and are made of oil<br />
and heat- resistant synthetic nitrile rubber/nitrile rubber bonded cork. For small<br />
gaskets, O-rings are used with diameter 3,5.0 or 8.0 mm, while round rubber<br />
cords with diameters 8,12 or 19 mm are used for large gaskets.<br />
Prepared By Samvet Lahari, <strong>Bhopal</strong>. Phone- 5277412
The groove is normally milled or turned, but for large flanges the groove<br />
is created by means of steel bars welded on top of the flange. The width of<br />
the groove is slightly smaller than the cross-section diameter of the gasket in<br />
order to keep the gasket in position during the assembling work.<br />
Opened sealing joints may be sealed again using the same gasket provided<br />
that the same has not been damaged. If the gasket has become hard or got<br />
small cracks on the surface, it is recommended to change the gasket by a new<br />
one.<br />
When handling and lifting flange, cover etc. with gasket grooves, care<br />
should be taken when using tools and lifting devices to avoid that the grooves<br />
getting damaged or deformed.<br />
Before assembling of groove gaskets, it is checked that the grooves and<br />
contact-surface in the joint are free from foreign particles and that the paint is<br />
free from thick coatings, trickles and drops.<br />
When assembling the rubber cord in the groove, the cord length shall be<br />
continuous . The gasket is given a small surplus length to compensate for<br />
shrinkage.<br />
The gasket is pressed down into the groove without stretching or<br />
slackening.<br />
To prevent the gasket from falling from the groove on vertical surfaces,<br />
the gasket may be spot-glued to the bottom of the groove.<br />
The screws in the sealing joint shall be tightened so that an even pressure<br />
is obtained on the gasket. This is obtained preferably by means of a moment<br />
spanner. Rubber gaskets in grooves need not normally be re-tightened.<br />
Above description is followed generally for turrets, inspection cover<br />
etc. For main tank rim joint, LV turrets of Generator Transformers where metallic<br />
stops are provided, nitrile rubber bonded cork is used, for which following<br />
<strong>instruction</strong>s shall apply.<br />
2.8.2 (i) Gaskets when supplied loose, have no bolt holes in them. They<br />
are usually cut to the size and shape required, although they may<br />
be supplied as straight, angled pieces from which complete gaskets<br />
can be built up.<br />
(ii) Scarfed joints should be used. A 40 mm scarf in 5 mm thick<br />
material is recommended. Joints should be located away from<br />
comers and bolt holes, and should be well bonded, smooth and<br />
free from local thickening. Neoprene solution is used as an adhesive<br />
for joints.<br />
(iii) Gaskets are best stored in hermetically sealed containers in a cool<br />
place. They must be protected from damp, oil and grease-<br />
(iv) To make a gasket joint, first clean the metal surfaces ensuring<br />
that they are free from oil, rust, scale etc. Using one of the flanges<br />
as a template, punch the necessary bolt holes. Insert the bolts<br />
and tighten the bolts sequentially, a little every time so that uniform<br />
pressure is exerted on the gasket until the gasket is compressed<br />
to about 2/3 of its original thickness. Joints should not be subjected<br />
to pressure until tightening is complete. If care is taken in making<br />
joints, and in handling the gasket, it is possible to break and remake<br />
a joint several times, using the same gasket.<br />
Prepared By Samvet Lahari, <strong>Bhopal</strong>. Phone- 5277412
(v) For making leak proof and good gasket joints, it is necessary that<br />
uniform pressure is achieved all over the gasket after matching<br />
rims/ flanges have been clamped with bolts/studs.<br />
Following <strong>instruction</strong>s be followed for proper tightening of bolts/studs.<br />
a) Tighten lightly the bolts/studs diagonally in the sequence as shown<br />
in the fig. 2.6.<br />
b) Tighten again bolts/studs in the same sequence with the torque<br />
given below :<br />
Bolt/Stud Max. Torque<br />
Size (Kg-M)<br />
M 10 1<br />
M 12 2<br />
M 16 6<br />
M 20 12<br />
M 24 20<br />
M 30 30<br />
In case of metallic stoppers tighten until metal to metal contact is achieved.<br />
c) Do not overtighten, otherwise gasket will get crushed.<br />
2.9 WELDED COVER (IF APPLICABLE)<br />
In order to obtain a good sealing between the transformer tank and the<br />
cover a welded joint is recommended. The welding is performed in a certain<br />
way to permit opening and new welding repeated a number of times. The<br />
chiselling up and re-welding will take about the same time as dismantling and<br />
reassembling of bolted cover .<br />
If the welded cover for any reason has to be removed proceed as follows:<br />
2.9.1 OPENING THE COVER<br />
When opening the cover the welding joint should be removed by a suitable<br />
grinding wheel. The cover should be clamped to the frame by means of Gclamps<br />
to prevent iron chips from penetrating into the tank. Any parts of the<br />
weld which may possibly remain on the tank flange should be removed by a<br />
chisel to enable a good result of the re-welding.<br />
2.9.2 REASSEMBLY<br />
When fitting the cover again cork-rubber gaskets, 25 x 5 or as specified<br />
are fitted on the tank flange, see fig. 2.7.<br />
The gaskets are kept in the correct position with glue base on rubber<br />
base. The cover should be clamped to the tank flange by means of G-clamps<br />
evenly distributed along the flange with about 600 mm spacing. Tack welding<br />
is carried out with about 100 mm spacing. An extra G-clamp is used during<br />
the tack welding and is moved along the flange during the progress of the<br />
work. The continuous weld is then applied. Finally the weld should be cleaned<br />
and painted.<br />
WARNING<br />
When welding, a fire-extinguishing equipment should be available, and<br />
the work supervised by fire-protection personnel.<br />
Prepared By Samvet Lahari, <strong>Bhopal</strong>. Phone- 5277412
2.10 EARTHING OF ACTIVE PART AND CORE INSULATION TEST<br />
2.10.1 REACTORS<br />
The ground-connection terminals for the reactor active part are located<br />
in a box at the tank end, close to the bottom. Please see fig. 2.8.<br />
The terminal are protected by a cover. The cover can be removed with<br />
the tank oil- filled.<br />
The terminal box contains a terminal block with three terminals.<br />
-The terminal marked CL is connected to the core laminations.<br />
-The terminal marked CC is connected to the core clamps.<br />
-The terminal marked G is connected to ground (the tank).<br />
For the core-insulation test, remove the cover. Disconnect the closing<br />
link that connects the two terminals CL-G. Use perferably 3500 V direct voltage<br />
between CL and CC + G. The tank shall be grounded during the test. The<br />
insulation value after 1 min. test- time shall be minimum 1000 kohms. There<br />
is no general requirement on the insulation level CC-G .<br />
2.10.2 TRANSFORMERS<br />
For checking core insulation incase of transformers refer Fig. 2.9 for<br />
connection details.<br />
2.11 TOUCH-UP PAINTING<br />
2.11.1 PURPOSE<br />
A basic principle at touch-up painting should be to restore a damaged<br />
paint coat on a surface to the same quality and finish as of the surrounding<br />
surface. The touch-up painting should be limited to a surface as small as<br />
possible.<br />
2.11.2 CLEANING<br />
Both damaged and surrounding surface should be cleaned so that all<br />
grease, dust and other impurities will be removed.<br />
2.11.3 GRINDING OF DAMAGES<br />
Large damages and defects are ground by means of a coarse abrasive<br />
paper, e.g. No.100. The surface is then ground with a finer paper in connection<br />
with the damage, e.g. 150 or 180. Damages that are limited to the paint coat<br />
only, should be ground off completely at which glazing can be avoided.<br />
2.11.4 PRIMER PAINTING<br />
Damages on the primer paint and grinding down to the steel surface<br />
should be painted with two coats of anti-corrosive priming paint.<br />
Prepared By Samvet Lahari, <strong>Bhopal</strong>. Phone- 5277412
2.11.5 FINISHING PAINT<br />
Two coats of finishing paint should be applied as per specification which<br />
is generally light grey shade No.631 of lS: 5. Please refer Table 2.4 for suppliers<br />
reference.<br />
TABLE 2.4<br />
SI Suppliers Suppliers Reference<br />
No. Name Anti corrosive High Quality full Oil resistant air<br />
priming paint for gloss outdoor drying synthetic<br />
outside painting finishing paint enamel<br />
1. Addison IS 2907 Shade 631 of IS 5 jasmine yellow<br />
shade no.397<br />
of IS 5 for<br />
inside painting<br />
2. Asian 32/F 3257 Apcolite synthetic -<br />
3. Berger BPL Red oxide Luxol 3H1 Glass -<br />
Zinc Chromate synthetic enamel -<br />
4. Alkali 32-781 Dulux synthetic -<br />
Chemicals enamel<br />
5. Garware PR-4460 - -<br />
6. Shalimar Sample No. 5999/1 Superlac synthetic 7377/1<br />
7. Goodlass 205/023 500 Series 548/101<br />
Prepared By Samvet Lahari, <strong>Bhopal</strong>. Phone- 5277412
ANNEXURE 2.1<br />
FLOW CHART FOR HANDLING<br />
ARRIVAL AT<br />
SITE<br />
MEASUREMENT OF<br />
PRESSURE<br />
ASSEMBLY<br />
EVACUATION AND OIL<br />
FILLING<br />
OIL-CIRCULATION<br />
THROUGH FILTER<br />
STANDING TIME<br />
ACCORDING TO TABLE 2.2.<br />
VOLTAGE APPLICATION<br />
Relationship between different units<br />
1 bar = 10 5 Pa = 750 Torr = 14.5 psi = 1.02 kg/sq.cm<br />
1 Torr = 1.33 mbar = 0.133 kPa<br />
1 kPa = 10 3 Pa = 10 mbar = 7.501 Torr<br />
1 MPa = 10 6 Pa<br />
Force Volume<br />
1 kp = 9.807 N 11itre = 0.26 US gallons<br />
1 US gallon = 3.781itres<br />
11itre = 0.22 Imp gallons<br />
1 Imp = 4.551itres gallon<br />
Temperature<br />
C = 5 x (F-32)/9<br />
F = 9 x (C+32)/5<br />
Prepared By Samvet Lahari, <strong>Bhopal</strong>. Phone- 5277412
ANNEXURE 2.2<br />
EQUIPMENT FOR OIL-FILLING UNDER VACUUM<br />
(i) High-vacuum 2 stage oil filtration plant provided with thermostatcontrolled<br />
oil heaters and vacuum-proof hoses with independant<br />
vacuum pumping system for tank evacuation. Capacity: 6000 lph.<br />
(ii) Oil-storage tanks provided with silica-gel breathers and inlet/outlet<br />
valves for oil circulation. Recommended capacity 20 kL -30 kL (Clause<br />
2.4)<br />
(iii) Vacuum gauges provided in filtration plant.<br />
(iv) Equipment for measurement of electric strength (BDV) of oil- 100 kV<br />
set.<br />
(v) Equipment for moisture content of oil.<br />
(vi) Equipment for measurement of Resistivity and Tan delta at 90o C.<br />
(vii) Oil-sampling cans or bottles.<br />
(viii) Transparent vacuum-proof tubes for checking of oil-level during oil<br />
filling.<br />
(ix) Valves, fittings, gaskets etc.<br />
(x) Dry nitrogen cylinders.<br />
Prepared By Samvet Lahari, <strong>Bhopal</strong>. Phone- 5277412
Prepared By Samvet Lahari, <strong>Bhopal</strong>. Phone- 5277412<br />
Fig. 2.1 Typical Unloading Arrangement of the Transformer<br />
ÊSÉjÉ 2.1 ]ÅõÉƺɡòɨÉÇ®ú EòÉä =iÉÉ®úxÉä EòÒ ´ªÉ´ÉºlÉÉ EòÉ xɨÉÚxÉÉ<br />
(1) HAULAGE HOLE- JÉÓSÉxÉä Eäò ʱɪÉä ÊUôpù<br />
(2) JACKING LUG- VÉäËEòMÉ ±ÉMÉ<br />
(3) JACK- VÉäEò<br />
(4) RLY. WELL WAGON- ®äú±É´Éä ´Éä±É ´ÉäMÉxÉ<br />
(5) 90 LB. RAIL - 90 B±É ¤ÉÒ ®äú±É<br />
(6) SUPPORTS TO PREVENT SLIPPING- Ê¡òºÉ±ÉxÉ ºÉä ¤ÉSÉxÉä Eäò ʱɪÉä +ÉvÉÉ®ú<br />
(7) GROUND LEVEL- ¦ÉÚ欃 ºÉiɽþ<br />
(8) THESE SLEEPERS WILL BE PUT AT SITE AT THE TIME OF UNLOADING-
Prepared By Samvet Lahari, <strong>Bhopal</strong>. Phone- 5277412<br />
1. OIL SAMPLING VALVE 15 mm 2 Nos. iÉä±É ºÉä¨{É˱ÉMÉ ´Éɱ´É 15 ʨɨÉÒ. 2 xÉÆ.<br />
2. FILLTER VALVE 50 mm 2 Nos. Ê¡ò±]õ®ú ´Éɱ´É 50 ʨɨÉÒ. 2 xÉÆ.<br />
3. DRAIN VALVE 80 mm 1 No. bÅä÷xÉ ´Éɱ´É 80 ʨɨÉÒ. 1 xÉÆ.<br />
4. DRAIN PLUG 15 mm 1 No. bÅä÷xÉ {±ÉMÉ 15 ʨɨÉÒ. 1 xÉÆ.<br />
5. MAN HOLE 1 No. ¨ÉèxÉ ½þÉä±É 1 xÉÆ.<br />
6. VACUUM APPLICATION VALVE 25 mm 1 No. ´ÉäCªÉÚ¨É ´Éɱ´É 25 ʨɨÉÒ. 1 xÉÆ.<br />
7. BUSHING MOUNTING HOLES WITH BLANKING FLANGE 3 Nos.<br />
¤ÉÖËÉMÉ ±ÉMÉÉxÉä Eäò ʱɪÉä ÊUôpù ¤±ÉåËEòMÉ }±ÉéVÉ ºÉʽþiÉ 3 xÉÆ.<br />
Fig. 2.2 Typical Arrangement of oil Storage tank<br />
ÊSÉjÉ 2.2 iÉä±É ºÉÆOɽþ Eò®úxÉä EòÒ ]ÆõEòÒ EòÉ xɨÉÚxÉÉ
1. Oil-filtering plant with heater<br />
2. Oil-storage tank<br />
3. High-vacuum pump<br />
4. Conservator<br />
5. Oil-level indicator<br />
6. Valve<br />
7. Valve<br />
8. Valve<br />
9. Valve<br />
10. Valve<br />
11. Dry-N2 container<br />
12. Valve<br />
13. Manometer<br />
Fig. 2.3<br />
ÊSÉjÉ 2.3<br />
(1) ½þÒ]õ®ú Eäò ºÉÉlÉ iÉä±É Ê¡ò±]õË®úMÉ {±ÉÉÆ]õ<br />
(2) iÉä±É ºÉÆOɽþ Eò®úxÉä Eäò ʱɪÉä ]åõEò<br />
(3) =SSÉ ÊxÉ´ÉÉÇiÉ {ɨ{É<br />
(4) EòxVÉ®ú´Éä]õ®ú<br />
(5) iÉä±É-ºiÉ®ú ºÉÚSÉEò<br />
(6) ´Éɱ´É<br />
(7) ´Éɱ´É<br />
(8) ´Éɱ´É<br />
(9) ´Éɱ´É<br />
(10) ´Éɱ´É<br />
(11) ÉÖ¹Eò xÉÉ
TRANSFORMER<br />
REACTOR<br />
]ÅõÉƺɡòɨÉÇ®ú/Ê®úBC]õ®ú ]ÆõEòÒ<br />
Fig. 2.4<br />
ÊSÉjÉ 2.4<br />
VACUUM<br />
FILTER<br />
´ÉèCªÉÚ¨É Ê¡ò±]õ®ú<br />
Prepared By Samvet Lahari, <strong>Bhopal</strong>. Phone- 5277412
OIL PRESERVATION SYSTEM WITH AIR CELL<br />
+É
Fig. 2.6<br />
ÊSÉjÉ 2.6<br />
Fig. 2.7<br />
ÊSÉjÉ 2.7<br />
Prepared By Samvet Lahari, <strong>Bhopal</strong>. Phone- 5277412
Fig. 2.8<br />
ÊSÉjÉ 2.8<br />
Prepared By Samvet Lahari, <strong>Bhopal</strong>. Phone- 5277412
NOTE:<br />
Fig. 2.9<br />
ÊSÉjÉ 2.9<br />
1. WHILE DISCONNECTING/EARTHING CONNECTION BETWEEN CORE/YOKE<br />
CLAMP & TANK, REMOVE THE LINK.<br />
1. EòÉä®ú/ªÉÉäEò C±Éä¨{É B´ÉÆ ]ÆõEòÒ EòÉ ¦ÉÚºÉÆ{ÉEÇò ʴɪÉÖHò Eò®úxÉä Eäò ʱÉB ªÉ½þ Eòb÷Ò ½þ]õÉ nåù*<br />
2. WHILE PUTTING IN SERVICE PLACE LINKS IN POSITION.<br />
2. {ÉÊ®úSÉɱÉxÉ Eäò ºÉ¨ÉªÉ ªÉ½þ Eòb÷Ò VÉMɽþ {É®ú ±ÉMÉÉ nåù*<br />
Earthing Connections from core and top yoke clamp.<br />
EòÉä®ú B´ÉÆ ]õÉì{É ªÉÉäEò C±Éä¨{É ºÉä ¦ÉÚºÉÆ{ÉEÇò ªÉÖÊHò<br />
Prepared By Samvet Lahari, <strong>Bhopal</strong>. Phone- 5277412
ANNEXURE 2.3<br />
PRESSURE TESTING OF TRANSFORMER / REACTORS AT SITE<br />
1. After completion of oil filling, lock PRV and pressurise the air cell by<br />
filling nitrogen/ dry air to 5.0 p.s.i. (0.35 Kg/cm.sq.).<br />
2. Maintain above pressure for at least 12 hours.<br />
3. Inspect all joints for leakage, if any.<br />
4. Record pressure testing as given below.<br />
5. After pressure testing unlock PRV and release the nitrogen/ dry air<br />
pressure of air cell.<br />
NOTE: In case of conventional oil preservation system (without air cell)<br />
pressurise conservator by filling nitrogen/dry air in conservator .<br />
RECORD OF PRESSURE TESTING AT SITE<br />
DATE TIME<br />
1. Date & Time of testing (a) Started on ......... .........<br />
(b) Finished on ......... .........<br />
2. Initial pressure ....................................<br />
3. Pressure after 12 hours ....................................<br />
4. Leakages observed if any YES /NO<br />
location of leakages ....................................<br />
5. If leakages are observed. Same to be arrested and pressure testing<br />
is to be repeated.<br />
Prepared By Samvet Lahari, <strong>Bhopal</strong>. Phone- 5277412
¦ÉÉMÉ-3<br />
Eò¨ÉÒÉËxÉMÉ<br />
SECTION-3<br />
COMMISSIONING<br />
Prepared By Samvet Lahari, <strong>Bhopal</strong>. Phone- 5277412
3 COMMISSIONING<br />
SECTION 3<br />
3.1 TESTING AFTER ASSEMBLY OF THE TRANSFORMER/ REACTOR<br />
AT SITE.<br />
After the transformer/reactor has been assembled at site, it shall be<br />
tested in order to check that it has not been damaged during transport and<br />
assembly to such an extent that its future operation will be at risk. Regarding<br />
the performance of the test, refer to the testing method as per standards. The<br />
results of the test shall be documented as detailed in Clause 3.2 "commissioning<br />
checks -Transformers" and Clause 3.3 commissioning checks - Reactors.<br />
3.1.1 APPLICATION OF VOLTAGE<br />
If possible, the voltage should be increased step by step up to rated<br />
voltage. This may be done by connecting the transformer/reactor to a generator<br />
whose voltage is raised slowly. The higher the rated voltage of transformer/<br />
reactor the more important it becomes that the application of the voltage is<br />
done as described. If it is not possible to use a generator, the transformer/<br />
reactor may be connected directly to a live line.<br />
After the first application of voltage, the transformer/reactor shall be<br />
checked carefully (gas relay, temperatures, leakages).<br />
When the transformer/reactor has been is service for some weeks with<br />
normal working temperature, all sealing joints shall be re-tightened.<br />
3.1.2 ENERGISING<br />
The initial magnetising current at the time of switching will be very<br />
high. This depends on the particular moment in the cycle. The transformer<br />
should always be soaked for few hours under constant care i.e. keep it<br />
energized. If the breaker trips on differential, Buchholz or any other device,<br />
the cause must be investigated before re-energising the transformer or reactor.<br />
After successful charging, performance of the transformer/reactor , OTI, WTI<br />
readings should be monitored for 24 hours and ensured that they are as per<br />
loading.<br />
3.1.3 ANALYSIS OF GAS<br />
The gas conected in the relay will help to identify the nature of the fault.<br />
It is suggested that the following checks are made at convenient intervals or<br />
following the indication of accumulation of gas through alarm signal.<br />
1. Rate of gas collection- The greater the rate of gas collection, the more<br />
severe is the nature of the developing fault.<br />
2. Colour of the gas helps in finding the affected material as follows.<br />
Prepared By Samvet Lahari, <strong>Bhopal</strong>. Phone- 5277412
Colour Identification<br />
White Gas of decomposed paper and cloth insulation.<br />
Yellow Gas of decomposed wood insulation.<br />
Grey Gas of overheated oil due to burning of iron portion<br />
Black Gas of decomposed oil due to electric arc.<br />
3. Combustibility of Gas- A small amount of gas drawn through the top<br />
pet cock if brightens the test flame, then the gas is combustible.<br />
Incombustible gas indicates air.<br />
4. Chemical Analysis of the Gas -The principles of working gas analyzing<br />
equipment is illustrated in the figure 3.1.<br />
Two solutions are prepared as detailed below and best results are obtained<br />
with freshly prepared solution.<br />
Solution 1: 5 gms of silver nitrate (AgNO ) dissolved in 100 ml<br />
3<br />
distilled water.<br />
Solution 2: A week solution of ammonia in water is slowly added to<br />
100 ml of solution 1, until a white curdled precipitate<br />
which forms first disappears in the mixture.<br />
The gas analyser loaded with these solution is then connected to the<br />
top pet cock. Small quantities of gas collected in the relay is allowed to pass<br />
through the two solutions as illustrated.<br />
The results are identified as follows:<br />
1. Both solutions are clear : Gas is air .<br />
2. Solution 1 -White precipitate<br />
turning brown on exposure to<br />
sunlight : Gas of oil decomposition.<br />
3. Solution 2 -turning to<br />
Dark brown precipitate : Gas of decomposed paper,<br />
cotton or wood insulation.<br />
Note: THE ABOVE INFORMATION ON GAS ANALYSIS ARE AS<br />
DETAILED IN IS:3638-1966. PLEASE REFER IS:3638-1966 FOR<br />
ALTERNATIVE METHOD OF CHEMICAL ANALYSIS.<br />
3.2 COMMISSIONING CHECKS -TRANSFORMER<br />
3.2.0 SCOPE<br />
This schedule covers the tests to be done at site after transformer has<br />
been installed and dried out.<br />
Prepared By Samvet Lahari, <strong>Bhopal</strong>. Phone- 5277412
3.2.1 GENERAL<br />
Check the following:<br />
Sl.No. Description<br />
1. Breather Silicagel (Blue when dry)<br />
2. Oil in the Breather housing cup.<br />
3. All valves for their correct opening and closing sequence.<br />
4. Oil level in conservator tank.<br />
5. Oil in cooling system.<br />
6. Oil level in bushings.<br />
7. Release air, wherever necessary.<br />
8. Cooling accessories (Pump motors, Fan motors etc.) for direction and O/L<br />
setting.<br />
9. Buchholz, oil level indicator, pressure gauges, thermometer,Temp. indicators<br />
etc. for operation.<br />
10. Earthing of main tank M.Box T/C driving gear, diverter, Pump Fan motor etc.<br />
11. Neutral earthing.<br />
12. Earth Resistance of Electrodes.<br />
13. Earthing of bushing test tap.<br />
14. Check oil leakage for 24 hrs.<br />
15. Check Auxiliary circuit voltage (415 V).<br />
16. Calibration of OTI/WTI with hot oil.<br />
17. Check Working of WTI/RTD repeaters at control room.<br />
18. IR of core to earth.<br />
3.2.2 INSULATION RESISTANCE TEST<br />
Sl. Description Date Time Megger IR Temp. Remarks<br />
No. in Hrs used Value o C<br />
1. Control wiring<br />
2. Tap Changer<br />
a) Motor<br />
b) Control<br />
3. Cooling system<br />
a) Motor Fan<br />
b) Motor pump<br />
c) Control wiring<br />
4. Main winding<br />
a) HV/E+LV<br />
b) IV/E+HV<br />
c) LV/E+HV+IV<br />
d) HV/IV<br />
e) IV/LV<br />
f) HV/LV<br />
(Not less<br />
than 500 V<br />
megger)<br />
(Not less<br />
than 1000V<br />
megger)<br />
NOTE :<br />
(1) While checking these values no external line, lightning arrestors etc. should<br />
be in circuit.<br />
(2) Special care should always be taken while meggering the transformer<br />
winding to ensure that there is no leakage in the leads.<br />
Prepared By Samvet Lahari, <strong>Bhopal</strong>. Phone- 5277412
3.2.3 OIL CHARACTERISTICS<br />
Take necessary precaution (regarding rinsing the bottle, cleaning hand,<br />
air bubble etc.) while withdrawing the samples (Please refer IS:6855). Each<br />
sample should be free of air bubbles and should not be tested when it is hot<br />
The sample should satisfy IS:1866.<br />
Sl. Oil Sample Time & Condition Moisture Break Resisti Tan- Rem<br />
No. From Date Time Weather in PPM down vity at 90 o C arks<br />
Voltage at 90 o C<br />
in kV (in ohm<br />
-cm)<br />
1. Tank<br />
Top Sample<br />
Bottom Sample<br />
2. Cooling system<br />
Top Sample<br />
Bottom Sample<br />
3. OLTC Diverter<br />
(each phase)<br />
3.2.4 TESTS ON CT<br />
1. Ratio<br />
2. Polarity<br />
3. Magnetising current<br />
4. IR value.<br />
3.2.5 ON LOAD TAP CHANGER<br />
Sl.<br />
No.<br />
Description Date Observation Remarks<br />
1. Visual Inspection of equipment.<br />
2. Hand operation on all taps.<br />
3. Complete wiring of the circuits.<br />
4. Limit Switch<br />
5. Over running device.<br />
6. Remote Panel wiring.<br />
7. Over load Device of Driving Motor.<br />
8. Local Operation (Electrical).<br />
9. Remote Operation (Electrical).<br />
10. Tap Position Indicator.<br />
11. Step by step contractor.<br />
12. Out of Step Relay.<br />
Note : While operating the mechanism on Electrical Control, check once again<br />
limit switches, step by step contractor, over running device etc. for<br />
their actual operation and ensure that they are functioning properly.<br />
Prepared By Samvet Lahari, <strong>Bhopal</strong>. Phone- 5277412
3.2.6 OFF CIRCUIT TAP SWITCH<br />
Tap switch handle should not be left halfway and/or unlocked.<br />
3.2.7 CONTINUITY TEST<br />
Continuity between line and neutral (for neutral end TC) or line to line<br />
(for line end TC) with multimeter on all taps and phases to be confirmed.<br />
3.2.8 MEASUREMENT OF WINDING RESISTANCE:<br />
Winding Tap No. Phase U Phase V Phase W Temp Remarks<br />
HV 1<br />
Winding 2<br />
IV<br />
Winding<br />
LV<br />
Winding<br />
3<br />
4<br />
5<br />
6<br />
7<br />
8<br />
9(a)<br />
9(b)<br />
9(c)<br />
10<br />
11<br />
12<br />
13<br />
14<br />
15<br />
16<br />
17<br />
Prepared By Samvet Lahari, <strong>Bhopal</strong>. Phone- 5277412
3.2.9 VOLTAGE RATIO TEST<br />
Ratio on all taps is to be checked by hand operation only. This can be<br />
done any time, once the tap changer is completely erected. Start the tap<br />
changer from lowest tap and then go on increasing tap by tap while checking<br />
the value instead of starting from normal tap.<br />
Tap Voltage applied Voltage Measured Ratio obtained Remarks<br />
Nos.<br />
1.<br />
2.<br />
3.<br />
4.<br />
5.<br />
6.<br />
7.<br />
8.<br />
9. (a)<br />
9. (b)<br />
9. (c)<br />
10.<br />
11.<br />
12.<br />
13.<br />
14.<br />
15.<br />
16.<br />
17.<br />
3.2.10 MAGNETISATION CURRENT<br />
a) Apply 3 phase 415 V on HV Terminals and keep LV open.<br />
Voltage Applied Current measured Remarks<br />
U-V Volts U phase m Amps<br />
V-W Volts V phase m Amps<br />
U-W Volts W phase m Amps<br />
Note: In case of single phase transformer, apply 230 V, 1 phase supply<br />
between line terminal and earth.<br />
b) Apply 3 phase 415 V on LV terminals and keep HV open.<br />
u-v volts u phase m Amps<br />
v-w volts v phase m Amps<br />
u-w volts w phase m Amps<br />
Note: In case of single phase transformer apply 230 V, 1 phase between<br />
line and earth terminal.<br />
Prepared By Samvet Lahari, <strong>Bhopal</strong>. Phone- 5277412
3.2.11 VECTOR GROUP<br />
Check the vector group of the transformer by connecting in a suitable<br />
manner.<br />
Vector Diagram of Diagram as connected Remarks<br />
group connection for test<br />
CONDITIONS TO BE PROVED VOLTAGE MEASURED<br />
1. 1.<br />
2. 2.<br />
3. 3.<br />
3.2.12 FINAL IR CHECKS<br />
The megger readings finally after the transformer is connected to the<br />
system<br />
Date ......................... Time ........................Temp .......................<br />
Windings Megger Value obtained in Remarks<br />
used Mega ohms<br />
HV/E+LV<br />
IV/E+HV+LV<br />
LV/E+HV+IV<br />
HV/IV<br />
IV/LV<br />
HV/LV<br />
3.2.13 OTHER TEST<br />
WTI Setting Set for Proved OTI Setting Set for Proved<br />
Alarm Alarm<br />
Trip Trip<br />
Fan Start<br />
Fan Stop<br />
Pump Start<br />
Pump Stop<br />
Prepared By Samvet Lahari, <strong>Bhopal</strong>. Phone- 5277412
3.2.14 PROTECTION AND ALARMS<br />
Prove the tripping of associated breakers by actual operation of the<br />
various devices and relays.<br />
UNDER NO CIRCUMSTANCES SHORTING OF ELECTRICAL<br />
CONNECTIONS SHOULD BE DONE.<br />
Sl.No. Device Set for Proved Remarks<br />
Alarm Trip Alarm Trip<br />
1. Buchholz<br />
2. Excessive Winding<br />
temperature<br />
3. Excessive Oil Temp.<br />
4. Oil flow failure<br />
5. Water flow failure<br />
6. Differential pressure<br />
(OFWF cooling system)<br />
7. Fan failure<br />
8. Low oil level<br />
(conservator tank)<br />
9. Pressure relief valve<br />
10. Differential relay<br />
11. Over current relay<br />
12. Earth fault (REF)<br />
13. Instt. Earth fault<br />
14. Inter trip, if any<br />
15. Trip free check.<br />
3.2.15 RECORD THE FOLLOWING AFTER CHARGING<br />
a) No load current at relay terminal<br />
U phase A<br />
V phase A CT Ratio<br />
W phase A<br />
b) Temperature (at the time of charging)<br />
O.T.I.<br />
oC W.T.I.<br />
oC Ambient oC c) Maximum temperature after 24 hours. o C<br />
Prepared By Samvet Lahari, <strong>Bhopal</strong>. Phone- 5277412
3.3 COMMISSIONING CHECKS REACTOR<br />
Customer W.O. No.<br />
Site Sl.No.<br />
Rating Voltage class<br />
Scope<br />
This schedule covers the tests to be done at site after reactor has been<br />
installed and dried out.<br />
3.3.1 GENERAL<br />
Check the following :<br />
Sl.No. Description Remarks<br />
1. Breather Silicagel (Blue When Dry)<br />
2. Oil in the Breather Cup.<br />
3. All valves for their correct opening and closing sequence.<br />
4. Oil level in conservator tank.<br />
5. Oil in cooling system.<br />
6. Oil level in bushings.<br />
7. Release air, wherever necessary.<br />
8. Buchholz, oil level indicator, thermometer, temp. indicators etc.<br />
for operation.<br />
9. Earthing of main tank, M. Box.<br />
10. Neutral earthing.<br />
11. Earth Resistance of Electrodes.<br />
12. Earthing of bushing test tap.<br />
13. Check oil leakage for 24 hours.<br />
14. Check auxiliary circuit voltage (415 V).<br />
15. Calibration of OTI/WTI with hot oil.<br />
16. Check Working of WTI/RTD repeaters at control room.<br />
17. IR of core to earth.,<br />
3.3.2 INSULATION RESISTANCE TEST<br />
Sl. Description Date Time Megger IR Temp. Remarks<br />
No. in hrs. used Value<br />
1. Control Wiring 500 V<br />
2. Main Winding<br />
a) HV/E >1000V<br />
Prepared By Samvet Lahari, <strong>Bhopal</strong>. Phone- 5277412
Note:<br />
(i) While checking these values no external lines, lightning arresstors<br />
etc. should be in circuit.<br />
(ii) Special care should always be taken while meggering the reactor<br />
winding to ensure that there is no leakage in the leads.<br />
3.3.3 OIL CHARACTERISTICS<br />
Take necessary precaution (regarding rinsing the bottle, cleaning hand,<br />
air bubble etc.) while-withdrawing the samples. Each sample should be free of<br />
air bubbles and should be tested when it is hot. The sample should satisfy<br />
IS:1866.<br />
SI. Oil Sample Time & Condition Moisture Break Resisti Tan- Rem<br />
No. From Date Time Weather in PPM down vity at at arks<br />
Voltage 90oC 90oC in kV (in ohmcm)<br />
1. Tank<br />
Top Sample<br />
Bottom Sample<br />
2. Cooling system<br />
Top Sample<br />
Bottom Sample<br />
3.3.4 TESTS ON CT<br />
1. Ratio<br />
2. Polarity<br />
3. Magnetising current<br />
4. IR value<br />
3.3.5 MEASUREMENT OF WINDING RESISTANCE<br />
Winding<br />
Phase U Phase V Phase W Temp. Remarks<br />
3.3.6 CURRENT MEASUREMENT<br />
a) Apply 3 phase 415 volts on HV Terminals.<br />
Voltage Applied Current measured Remarks<br />
U-V Volts U Phase m A<br />
V-W Volts V Phase m A<br />
W-U Volts W Phase m A<br />
Note: In case of single phase reactors apply 230 V, 1 phase between<br />
line terminal and earth.<br />
Prepared By Samvet Lahari, <strong>Bhopal</strong>. Phone- 5277412
3.3.7 FINAL CHECKS<br />
The megger readings finally after the reactor is connected to the system.<br />
Date Time Temperature<br />
Winding<br />
HV/E<br />
Megger used Value Obtained<br />
in megaohms<br />
Remarks<br />
3.3.8 OTHER TEST<br />
WTI Setting Set for Proved OTI Setting Set for Proved<br />
Alarm<br />
Trip<br />
3.3.9 PROTECTION AND ALARMS<br />
Prove the tripping of associated breakers by actual operation of the<br />
various devices and relays.<br />
Note: Under no circumstances shorting of electrical connections be done.<br />
Sl.No. Device Set for Proved Remarks<br />
Alarm Trip Alarm Trip<br />
1. Buchholz<br />
2. Excessive Winding<br />
Temperature<br />
3. Excessive Oil Temp.<br />
4. Oil Level<br />
(Low & Max.)<br />
5. Pressure Relief Valve.<br />
3.3.10 RECORD THE FOLLOWING AFTER CHARGING<br />
a) No load current at relay terminal<br />
U phase m A<br />
V phase m A CT Ratio<br />
W phase m A<br />
b) Temperature (at the time of charging)<br />
O.T.I.<br />
oC W.T.I.<br />
oC Ambient<br />
oC c) Maximum temperature<br />
after 24 hours.<br />
o C<br />
Prepared By Samvet Lahari, <strong>Bhopal</strong>. Phone- 5277412
Prepared By Samvet Lahari, <strong>Bhopal</strong>. Phone- 5277412
¦ÉÉMÉ-4<br />
+xÉÖ®úIÉhÉ B´ÉÆ {ÉÊ®úSÉɱÉxÉ<br />
SECTION-4<br />
MAINTENANCE AND OPERATION<br />
Prepared By Samvet Lahari, <strong>Bhopal</strong>. Phone- 5277412
SECTION 4<br />
4. MAINTENANCE AND OPERATION<br />
4.1 SUPERVISION OF TRANSFORMER/REACTOR<br />
4.1.1 GENERAL<br />
In order to avoid faults and disturbances, it is important that a careful<br />
and regular supervision and control of the reactor and its components is planned<br />
and carried out.<br />
The frequency and extent of such a supervision and control is dependent<br />
on climate, environment and service conditions etc.<br />
The directions for a certain transformer/reactor are therefore preferably<br />
based on experiences from comparable transformer/ reactor installations.<br />
A supervision and maintenance program according to schedule in<br />
ANNEXURE 4.1 is recommended.<br />
Spare transformers/reactors are supervised and maintained according<br />
to the same schedule as transformers/ reactors in service.<br />
4.1.2 GENERAL MAINTENANCE<br />
Dirt/Dust<br />
The external transformer surfaces shall be inspected regularly and when<br />
required cleaned from dust, insects, leaves and other airborne dirt.<br />
Possible Leakage<br />
After energising of the transformer, a certain settling may appear in<br />
sealing joints. These should therefore be retightened according to schedule in<br />
ANNEXURE 4.1. This applies especially to sealing joints with plain gaskets<br />
that are not placed in grooves.<br />
Rust damages, touch-up painting<br />
A regular inspection of the external surface treatment of the reactor<br />
should be carried out. Possible rust damages are removed and the surface<br />
treatment restored to original state by means of primer and finish paints.<br />
4.1.3 OIL PRESERVATION SYSTEM, MOISTURE ABSORPTION<br />
Transformer oil absorbs easily moisture from the surrounding air. The<br />
moisture absorption has been prevented by means of rubber sack in<br />
convservator which acts as a separating wall between the oil and the<br />
surrounding air.<br />
The moisture absorption is further prevented by a breather connected<br />
to the conservator. The active drying agent (silica gel) should be exchanged or<br />
regenerated when 2/3 of the agent has been red-coloured by absorbed moisture.<br />
Prepared By Samvet Lahari, <strong>Bhopal</strong>. Phone- 5277412
The breather contains also an oil-seal that prevents spontaneous air<br />
circulation. This seal should be filled with oil to the level specified.<br />
4.1.3.1 OIL LEVEL INDICATOR FOR OIL CONSERVATOR<br />
The Transformer oil conservator is provided with an oil-level indicator.<br />
At an oil temperature of 45 o C, the conservator should be half filled. If the level<br />
exceeds the value “full”, oil must be drained off. If the value is “low”, oil must<br />
be filled in, Normal oil level should be at 35 o C mark.<br />
4.1.3.2 GAS-OPERATED RELAY (BUCHHOLZ RELAY)<br />
The use of gas-operated relay as protection for oil-immersed transformers<br />
is based on the fact that faults as flash over, short-circuit and local overheating<br />
normally result in gas- generation. The gas- bubbles gathering in the gasoperated<br />
relay affect a float- controlled contact which gives an alarm signal.<br />
4.1.3.3 MOISTURE<br />
If the oil has been subjected to moist air, the moisture content and the<br />
electric strength of the oil shall be checked.<br />
4.1.3.4 SLUDGE, ACID<br />
Normally the <strong>BHEL</strong> transformers have uninhibitated oil.<br />
Sometimes inhibited oil is used. The inhibitor works so that it breaks the<br />
chain reaction by which sludge and acid are produced. This retards the ageing<br />
process and extends the utilization time of the oil.<br />
If sludge is being produced in the oil, the oil changes colour and becomes<br />
darker and turbid. The sludge can be removed by means of filtering, but if the<br />
sludge formation has started, it will increase with time. The oil should therefore<br />
be exchanged if the neutralisation value according to IS:1866 exceeds 0.5 mg<br />
KOH/g or precipitable soluble sludge is produced.<br />
The oil exchange should preferably be carried out when the transformer<br />
is warm and the oil viscosity is low.<br />
The exchange should be as complete as possible, because old oil will<br />
affect the new one, speeding up the ageing.<br />
Oil which is not too much oxidized may in certain cases be regenerated,<br />
but this is economical only for large oil quantities.<br />
4.1.3.5 OIL, MISCELLANEOUS<br />
For supplementary information about transformer oil, see clause 4.2<br />
“Supervision and control of oil”.<br />
4.1.4 TEMPERATURE SUPERVISION<br />
The service life of a transformer is highly dependent on the temperature<br />
prevailing in the core and windings under operation. It is thus important to<br />
keep the oil and winding temperatures under observation continuously. The<br />
temperatures should be read regularly and the measured values registered.<br />
These values will give guidance for judging the service life of the<br />
transformer, cooling system functions etc.<br />
Prepared By Samvet Lahari, <strong>Bhopal</strong>. Phone- 5277412
4.1.4.1 OVERLOAD<br />
A Transformer can normally be overloaded at a low ambient temperature.<br />
However, the permissible overload must not be judged only with regard to the<br />
oil temperature. We must also consider that the temperature difference between<br />
winding and oil will increase with the load. Therefore, also the winding<br />
temperature must be supervised during overloading.<br />
For determination of the overload capacity for modern transformers refer<br />
IS:6600.<br />
If the temperature in a transformer shows a tendency of rising without<br />
a corresponding increase of the load, this may be caused by a reduction of the<br />
cooling ability of the cooling equipment (dirt, dust). The thermometer should<br />
also be checked in this case.<br />
4.1.4.2 THERMOMETER FOR MEASUREMENT OF TOP-OIL TEMPERATURE<br />
The thermometer consists of a cylindrical sensing body with a flange, a<br />
capillary tube, and a thermometer housing with dial and contact-device. The<br />
measuring system is filled with a liquid, which changes its volume at<br />
temperature variations, and affects spring bellows. The movements of the<br />
bellows are transferred to the pointer and signal contacts via a link system.<br />
The thermometer is provided with two signal contacts of mercury switches.<br />
The contacts can be set independently of each other.<br />
For control and adjustment of the thermometer, see OTI leaflet.<br />
4.1.4.3 WINDING-TEMPERATURE INDICATOR<br />
The thermometer system consists of a sensitive body with assembling<br />
details, a capillary tube and a thermometer housing, which contains a scale<br />
with an indicating pointer and a max. pointer, heating and adjusting resistor,<br />
as well as contact- device for four switches.<br />
For further information about function, control and adjustment of winding<br />
temperature indicator, see WTI Leaflet.<br />
4.1.4.4 REMOTE CONTROL OF WINDING TEMPERATURE<br />
For remote control of winding temperature a resistance temperature<br />
device has been used with a heating element built into the same housing. The<br />
heating element is fed by the secondary current of a current transformer.<br />
For setting of the heating element there is a parallel connected adjusted<br />
resistor installed in the control cabinet.<br />
For further information about function and calibration, see RTD Leaflet.<br />
4.1.4.5 RADIATORS<br />
The external cooling surfaces shall be inspected regularly and when<br />
required cleaned from dust, insects, leaves or other airborne dirt. This is<br />
especially important in case of fan cooling. The cleaning is suitably carried out<br />
by means of water flushing at high pressure.<br />
Prepared By Samvet Lahari, <strong>Bhopal</strong>. Phone- 5277412
Normally, no measures are necessary for keeping the internal cooling<br />
surfaces clean as long as the oil is in good condition. If, however, sludge<br />
formation has set in, the sludge may deposit on horizontal surfaces in radiators.<br />
In such a case, the radiator should be flushed internally with clean oil.<br />
If the sludge does not loosen, we can firstly flush with petrol etc. and<br />
then with oil.<br />
4.1.4.6 CONTROL CABINET<br />
The operation of the control cabinet and devices normally included, are<br />
described in Vol. I.<br />
4.1.4.7 BUSHINGS<br />
Bushing porcelains shall be cleaned from dust and dirt regularly. In areas<br />
where the air contains impurities as salt, cement dust, smoke or chemical<br />
substances, shorter intervals are required. See also the Instructions in the<br />
special information documents about bushings that are included in vol.I.<br />
4.1.4.8 CONNECTIONS<br />
In order to avoid prohibited temperature rises in the electrical connections<br />
of the transformers/reactor, all screw-joints should be checked and re-tightened<br />
according to schedule enclosed.<br />
4.1.4.9 ACCESSORIES<br />
Separate leaflet/<strong>instruction</strong>s should be followed for various fittings (as<br />
applicable) for Fans, Pumps, Flow indicators, Pressure Gauges, Oil Gauge,<br />
Pressure reducing valve, OLTC, Off circuit tap switch, OFAF/OFWF Coolers<br />
etc.<br />
These leaflet are enclosed with Vol I.<br />
4.1.5 MAINTENANCE SCHEDULE<br />
Maintenance schedule given at Annexure 4.1 should be followed. With<br />
proper maintenance as per this schedule normal life of Transformer or reactor<br />
can be expected.<br />
4.1.6 IR TEMPERATURE RELATION<br />
It has always been the question from our customers as to how the IR<br />
value can be converted at different temperatures. We have drawn a curve<br />
(Fig. 4.1) for guidance of the operating staff on the basis of our experience.<br />
So that they can judge the IR Value at any temperature. This curve cannot be<br />
taken for absolute value but will serve as a good guide for conversions of IR<br />
values at different temperatures. A simple example is given as to how to<br />
calculate the value at different temperature.<br />
Suppose IR value of 70 o C is 300 M Ohms and we want to convert at<br />
40 o C, the curve will give you a factor K for difference in temperature i.e.<br />
(70 o C-40 o C)=30 o C.<br />
K for 30 o C temperature difference = 4.2<br />
So the value at 40 o C = 4.2x300 = 1260 M. Ohms.<br />
Value thus converted fairly tally with the actual<br />
Value when cooling the transformer. The factors are tabulated as below:<br />
Prepared By Samvet Lahari, <strong>Bhopal</strong>. Phone- 5277412
Difference<br />
in temp. 10 o C 20 o C 30 o C 40 o C 50 o C<br />
Factor K 1.65 2.6 4.2 6.6 10.5<br />
4.2 SUPERVISION AND CONTROL OF OIL<br />
4.2.1 GENERAL<br />
The oil in a reactor provides an electrically insulating and a cooling<br />
medium. The service reliability of an oil-immersed transformer/reactor is<br />
therefore mainly, depending on the oil quality.<br />
In service, oil is subjected or normal deterioration due to the conditions<br />
of use mainly due to air, water and solid particles/sediment.<br />
4.2.2 SCHEDULE<br />
The oil should be maintained as per the guidelines of IS:1866. Periodicity<br />
of test and permissible limits for important parameters of oil - electric strength,<br />
water content, resistivity, tan-delta, neutralization value, sediment and<br />
precipitable sludge, flash point and interfacial tension are given in Annexure<br />
4.2. Health of reactors can be effectively monitored by Dissolved Gas Analysis<br />
(DGA) technique described in detail in IS:9434 and IS:10593. This technique<br />
helps in detection of incipient faults in reactors.<br />
4.3 TROUBLE SHOOTING<br />
General measures for trouble shooting are described in this section.<br />
4.3.1 Items to be informed to <strong>BHEL</strong> in case of trouble.<br />
Followings are items to be informed to <strong>BHEL</strong>.<br />
1. Transformer or Reactor specifications<br />
Capacity<br />
Serial number & work order No.<br />
Year of manufacture.<br />
2. Load current (A) or load (kW)<br />
3. Operating tap position (In case of Transformer)<br />
4. Conditions at time of trouble.<br />
a) Date, time<br />
b) Trouble phenomena<br />
c) Checked items and results<br />
4.3.2 Transformer troubles and check items. Troubles, their possible causes<br />
and items to be checked are given in Table 4.1 & 4.2.<br />
4.3.3 Detective devices and their functions. Refer to table 4.3<br />
4.3.4 Check items and judging standard Refer to table 4.4.<br />
4.3.5 Detection method of oil or gas leaks. Refer to table 4.5.<br />
Prepared By Samvet Lahari, <strong>Bhopal</strong>. Phone- 5277412
Prepared By Samvet Lahari, <strong>Bhopal</strong>. Phone- 5277412
Prepared By Samvet Lahari, <strong>Bhopal</strong>. Phone- 5277412
Table 4.3: Detective devices and their functions<br />
No. Detective<br />
device<br />
Description<br />
1. Buchholz This relay detects the gas evolution due to internal trouble and<br />
relay<br />
gives alarm, and is suited to the detection of minor or slowly<br />
(1st stage) developing faults. The nature of the detected fault can be judged<br />
to an extent by analyzing the gas and oil. In case of nitrogen gas<br />
sealed transformer, part of dissolved nitrogen gas comes out due<br />
to the sudden temperature drop, which sometimes results in the<br />
actuation of this relay.<br />
2. Buchholz When a major fault suddenly takes place inside the transformer,<br />
relay<br />
oil flows suddenly from the transformer tank to the conservator.<br />
(2nd stage) The second stage of Buchholz relay is actuated by this oil flow. If<br />
the second stage of the relay functions independently, check the<br />
air breather, nitrogen gas sealing device etc. If it functions<br />
combinedly with the over current relay etc. it is suspected that a<br />
serious internal defect is existent. In such a case take all tentative<br />
measures and contact <strong>BHEL</strong> immediately.<br />
3. Pressure When the internal pressure of the transformer rises above the set<br />
relief device value, the pressure relief device functions. It also functions, though<br />
occasionally by the choking of the air breather. The self- excited<br />
pressure relief plate is subject to brittleness caused by secular<br />
change. Comprehensive judgment based on the inspection of other<br />
protective relays is the key to determining whether the function of<br />
this device is an erroneous operation or a normal operation caused<br />
by internal defect.<br />
4. Differential This relay detects the internal defect by comparing the input current<br />
relay<br />
and the output current of the transformer. If it functions combinedly<br />
with other protective devices, it is indicative, in almost all cases,<br />
of an internal fault. Note that this relay sometimes operates due to<br />
inrush current when the transformer is energized, and this is of<br />
course not an internal fault.<br />
5. Dial thermo This thermometer gives alarm when the temperature rises beyond<br />
meter alarm the preset value. Insufficient cooling effect of cooling equipment<br />
contact due to contamination of cooling fins, Stoppage of oil pumps, fans<br />
and so forth is one of the reasons that operates this device.<br />
6. Overcurrent These are intended for detecting faults in the electric system<br />
relay, ground connected with the transformer. A fault in the transformer results<br />
fault relay in the function of these relays, which is always accompanied by<br />
the actuation of protective devices of the transformer. Detection<br />
of the fault in the electric system should therefore be made on the<br />
basis of a comprehensive judgment of these functions.<br />
7. Voltmeter If a sudden change in voltage or current is noted when no<br />
ammeter abnormalities are detected in the electric system, or an abnormal<br />
unbalance of voltage or current is noted between phases, investigate<br />
the cause.<br />
8. Human Note that human senses also play an important role in fault<br />
senses<br />
detection. Following are the points to be checked by your senses.<br />
1) Discolouration or odour of insulation oil (blackening or stink). If<br />
pieces of insulating materials or copper particles are found in<br />
the oil, it is suspected that an internal defect has developed.<br />
2) Abnormal vibration or sound.<br />
Prepared By Samvet Lahari, <strong>Bhopal</strong>. Phone- 5277412
1. Measurement<br />
of insulation<br />
resistance<br />
2. Measurement<br />
of winding<br />
resistance<br />
3. Measurement<br />
of voltage ratio<br />
4. Measurement<br />
of exciting<br />
current<br />
5. Checking of<br />
insulation oil<br />
6. Measurement<br />
of dielectric<br />
loss factor,<br />
tan<br />
7. Analysis of gas<br />
accumulated in<br />
Buchholz relay<br />
8. Analysis of<br />
dissolved gas<br />
in oil<br />
Table 4.4: Check and refer standards<br />
No. Check Point Description Judging standard<br />
Grounding fault can be detected by<br />
this measurement, though to some<br />
extent. The measurement must be<br />
proceeded after disconnecting the<br />
transformer from lines and cleaning<br />
of bushing surfaces.<br />
This is a primary means to be<br />
employed for detecting the fault of<br />
windings. The resistance should<br />
preferably be measured independently<br />
by the D.C. drop of potential method.<br />
This can be conducted by applying a<br />
voltage of about 200V which can be<br />
readily obtained at job-site. Accurate<br />
measurement at job site entails some<br />
difficulties due to source voltage<br />
variation and errors of instruments.<br />
In case of 3 phase transformers, it is<br />
essential to measure the ratio phase<br />
by phase and check the variation of<br />
the ratio between phases.<br />
This measurement is very useful to<br />
detect fault in windings and/or cores.<br />
Local short- circuit in windings or<br />
cores often causes an increase in the<br />
exciting current. The test can be made<br />
by applying a low voltage (200-400<br />
volts) to a winding.<br />
Measure dielectric strength and check<br />
for carbon sludge, offensive odour<br />
and discoloration.<br />
When gas is accumulated in the<br />
Buchholz relay,its composition must<br />
be clarified by the gas chromatograph<br />
analyzer to check for the possible<br />
internal defect.<br />
Existence of internal defect can be<br />
judged, though to a limited degree,<br />
by sampling and analyzing oil by a<br />
gas chromatograph. (Refer 4.3.2).<br />
Judgment to be<br />
made by comparison<br />
with values obtained<br />
by periodical<br />
inspection.<br />
Judgment to be made<br />
by comparison with<br />
the factory test report.<br />
Judgment to be made<br />
by comparison with<br />
the factory test report.<br />
1 Comparison of<br />
the measured<br />
values with<br />
previously<br />
obtained ones.<br />
2 Significant<br />
difference in<br />
value among<br />
phases.<br />
Judgment to be made<br />
with reference to<br />
Annexure 4.1 & 4.2.<br />
Judgment to be made<br />
by comparison with<br />
values obtained by<br />
periodical inspection.<br />
Contact <strong>BHEL</strong><br />
Contact <strong>BHEL</strong><br />
Prepared By Samvet Lahari, <strong>Bhopal</strong>. Phone- 5277412
Table 4.5 Method for detecting oil or nitrogen leaks<br />
Leak Measures Description<br />
Oil leak Clean the suspected leak The following are susceptible<br />
part with thinner or gasoline to leakage.<br />
apply chalk powder to it. (1) Gasketed joints.<br />
The leak part will present (2) Welded parts.<br />
itself as a soiled spot.<br />
Nitrogen leak Step up Nitrogen gas pressure The following are susceptible<br />
(in case of to 0.17 kg/cm 2 to leakage<br />
Nitrogen sealed (1) Accessories for pressure<br />
system) relief<br />
(2) Flanges<br />
(3) Welded parts<br />
4.3.6 GAS ANALYSIS ON TRANSFORMER OIL<br />
Incipient faults in oil filled transformer are usually the result of electrical<br />
or thermal excess stress of either the transformer oil or insulating materials.<br />
It is known that such excessive stresses produce a mixture of gases<br />
characteristic of which give an indication of the type of faults, and materials<br />
associated with the faults.<br />
It is recommended that analysis of dissolved gases in transformer oil by<br />
gas chromatographic equipment is made, the time of commissioning and then<br />
after an interval of one year for transformers of 145 kV class and above.<br />
4.3.7 ANALYSIS METHOD<br />
4.3.7.1 SAMPLING OF OIL FROM TRANSFORMERS<br />
Oil in transformers can be sampled through drain or sampling valve near<br />
bottom of the tank. Special care shall be taken not to introduce air, foreign<br />
matter, or dirty oil into sampling container. For this purpose, first 0.5-1.0 litre<br />
of oil from the transformer shall be over-flown through the oil container. Shape<br />
of the sampling container may be that of shown in Fig. 4.2 and sampling<br />
method shall be in accordance with Fig. 4.3. See also IS:9497 Sampled oil<br />
shall not be exposed to air before analysis.<br />
4.3.7.2 GAS ANALYSIS<br />
Gases to be analysed and criteria for the gases found in transformer oil<br />
are tabulated in table 4.6.<br />
4.3.8 ASSESING THE TEST RESULTS<br />
Test results on gas contents in oil by some typical faults in transformer<br />
active part models are shown in table 4.7.<br />
Table 4.6 and table 4.7 may by referred to evaluate transformer condition.<br />
To analyse DGA test results, flow chart given at Appendix A of IS:10593<br />
should be followed. Standard values may be taken from CBIP Technical report<br />
no. 62 of April 88 titled "Guide for testing of Transformer by Sampling and<br />
analysis of free and dissolved gases" Ratio technique of IS:10593 should be<br />
used to know the nature of fault. IS:9434 and IS:10593 have been adopted<br />
from IEC pub 567 and IEC pub 599.<br />
Prepared By Samvet Lahari, <strong>Bhopal</strong>. Phone- 5277412
Table 4.6 Gases to be analysed and criteria<br />
1. Gases to be analysed normally O 2 , N 2 , H 2 , Co, Co 2 , CH 4<br />
2. Gases to estimate abnormality H 2 , CH 4 , C 2 H 2 , C 2 H 4 , C 2 H 6<br />
3. Gases to estimate deterioration Co, Co 2 , CH 4<br />
Table 4.7 Gas content in oil by faults<br />
Sl. Type of faults Decomposable gases in<br />
transformer oil<br />
1. Overheat of oil CH 4 , C 2 H 4 , H 2 , (C 2 H 6 , C 2 H 2 ,C 3 H 6 C 3 H 8 )<br />
2. Arcing in oil H 2 , C 2 H 2 , (CH 4 , C 2 H 4 )<br />
3. Overheat of solid insulating materials CO, CO 2 , (H 2 , C 2 H 4 )<br />
4. Overheat of oil and paper combination CH 4 , C 2 H 4 , CO, CO 2 , H 2<br />
5. Arcing of oil and paper combination H 2 , C 2 H 2 , CO, CO 2 , (C 2 H 4 )<br />
( ) shows gas contents which appear rarely.<br />
4.4 PARALLEL OPERATION<br />
(i) If it is desired to parallel a transformer which is not identical in<br />
design with <strong>BHEL</strong> transformer, it is preferable to refer the matter to<br />
<strong>BHEL</strong> for advice.<br />
(ii) The voltage ratings/ratios and impedance values at all taps should<br />
match for the two transformers that are to be paralleled. Only certain<br />
combinations of vector groups are capable of being paralleled. The<br />
table 4.8 below indicates the more common permissible combinations.<br />
Table 4.8<br />
TRANSFORMER (B)<br />
H.V. Delta Star Delta Star<br />
L.V. Star Delta Delta Star<br />
H.V./L.V.<br />
Delta/Star Yes Yes No No<br />
TRANSFORMER (A)<br />
Star/Delta Yes Yes No No<br />
Delta/Delta No No Yes Yes<br />
Star/Star No No Yes Yes<br />
Prepared By Samvet Lahari, <strong>Bhopal</strong>. Phone- 5277412
(iii) Reference to the connection diagrams of two transformers should<br />
indicate the terminals to be paralleled.<br />
(iv) The reversal of two leads on either side of a three-phase transformer<br />
will reverse the polarity changing them in sequence (e.g. form UVW<br />
to VWU or WUV) will swing the vectors through 120.<br />
(v) Phase sequence and polarity can be checked by energising both<br />
transformers on the primary side before paralleling and measuring<br />
the open-circuit voltage appearing across each pair of terminals which<br />
will ultimately be paralleled.<br />
(vi) IS:2026 and IS:10561 may also be referred.<br />
Prepared By Samvet Lahari, <strong>Bhopal</strong>. Phone- 5277412
SI Items to be<br />
inspected<br />
1. Ambient<br />
temperature<br />
2. Winding<br />
temperature<br />
3. Oil temperature<br />
4. Load amps/Load<br />
voltage<br />
1. Oil level in<br />
transformer<br />
conservator<br />
2. Oil level in tap<br />
changer diverter<br />
switch.<br />
3. Oil level in<br />
bushings.<br />
4. Pipework and<br />
accessories for<br />
leakages<br />
1. Buchholz Relay<br />
2. Dehydrating<br />
breather<br />
3. Leakages of<br />
water into<br />
cooler.<br />
1. Bushings<br />
2. Transformer oil<br />
and tap changer<br />
oil<br />
3. Cooler fan,<br />
bearing and<br />
controls,<br />
pumps.<br />
ANNEXURE 4.1<br />
MAINTENANCE SCHEDULE<br />
Inspection notes<br />
HOURLY<br />
-<br />
Check that temperature<br />
rise is reasonable.<br />
Check against rated figures<br />
DAILY<br />
Check oil level from oil<br />
gauge<br />
Check oil level from the<br />
gauge glass.<br />
Check the oil level from<br />
gauge glass/gauge.<br />
Inspect the transformer for<br />
leakages.<br />
MONTHLY<br />
Check oil level<br />
Check colour of silicagel.<br />
-<br />
QUARTERLY<br />
Examine for dirt deposition<br />
and tightness of oil filling<br />
plugs. Examine for cracks<br />
in porcelain.Clean and<br />
tighten plugs.<br />
Check for di-electric<br />
strength and moisture<br />
content.<br />
Check contacts, <strong>manual</strong><br />
control and interlocks.<br />
Action required<br />
-<br />
Shutdown the transformer and<br />
investigate, if either is persistently<br />
higher than normal.<br />
An improper tap position can<br />
cause excessive core loss. Voltage<br />
and tap position should be<br />
corrected.<br />
Top up, if found low.<br />
Top up, if found low.<br />
Top up, if found low.<br />
If leakages are observed tighten<br />
evenly the gasket joints. Replace<br />
‘O’ ring or washer suitably.<br />
Replace gasket if needed.<br />
Release collected gas/air<br />
Reactivate/replace with new<br />
charge, if found pink Investigate<br />
and rectify after taking shutdown.<br />
Cracked porcelain should be<br />
rectified/replaced.<br />
Take suitable action to restore<br />
quality of oil.<br />
Lubricate the fan bearings.<br />
Replace worn out contacts and<br />
other parts. Clean/ adjust controls<br />
and interlocks.<br />
Prepared By Samvet Lahari, <strong>Bhopal</strong>. Phone- 5277412
4. On load tap<br />
changer<br />
5. Dehydrating<br />
breather<br />
1. Transformer oil<br />
2. Cable box<br />
3. Alarm and<br />
protection<br />
circuits.<br />
4. OTI & WTI<br />
pockets<br />
5. Earth strip<br />
6. Packing gaskets<br />
of fans<br />
7. Fan motors<br />
8. Tank and<br />
accessories<br />
9. Gasket joints<br />
10. Divert servicing<br />
11. Diverter switch<br />
of on-load tap<br />
changer<br />
Examine contacts, check<br />
step by step mechanism<br />
operation, end position<br />
limit switches and brakes.<br />
Also check oil in driving<br />
gear mechanism.<br />
Check oil level in the cup<br />
and ensure air passages<br />
are free.<br />
YEARLY<br />
Check for characteristics in<br />
line with IS:1866<br />
Check for proper scaling of<br />
compound filling holes.<br />
Check for cracks in the<br />
compound (if used).<br />
Check all protections and<br />
alarm circuits by actual<br />
external initiation. Check<br />
operation of relays and<br />
their sensitivity.<br />
Check oil in the WTI and<br />
OTI pockets.<br />
Check earthing resistance<br />
Inspect the condition of<br />
packing gaskets.<br />
Check IR value of motor<br />
winding after rainy season.<br />
Noise & vibration of fans.<br />
Check painting and surface<br />
finish. Mechanical<br />
inspection of all<br />
accessories.<br />
Check the tightness of<br />
bolts<br />
One year after<br />
commissioning<br />
Check the contacts for<br />
burning or pitting marks.<br />
Replace all worn out and burnt<br />
contacts. Set limit switches in<br />
position. Clean/ replace brake shoe<br />
lining. Lubricate all bearing and<br />
coupling points suitably. (Refer<br />
Separate leaflet.)<br />
Top up, if found low. Clean air<br />
passages.<br />
Filter/replace as required to restore<br />
the quality.<br />
Replace sealing washer, if found<br />
damaged.<br />
Replace burnt out fuses Adjust the<br />
setting and check wiring circuits.<br />
Adjust relay setting, if needed.<br />
Replace damaged relays.<br />
Replenish, if required<br />
Take suitable action, if resistance<br />
is noted high.<br />
Replace if worn out or resilience<br />
lost.<br />
Dry out, if found low, check<br />
balancing of fans.<br />
Touch up/repaint, if required<br />
Replace any component found<br />
damaged.<br />
Tighten evenly all loose bolts,<br />
nuts, locking etc.<br />
Draw out diverter, clean, tighten<br />
contacts.<br />
Recondition/replace if required.<br />
Prepared By Samvet Lahari, <strong>Bhopal</strong>. Phone- 5277412
12. Diverter switch<br />
oil<br />
13. Tank cover and<br />
conservator<br />
14. Bushing top<br />
connectors.<br />
1. Oil conservator<br />
2. Transformer oil<br />
3. Buchholz relay<br />
1. Transformer and<br />
tap changer<br />
Assembly<br />
Filter oil irrespective of<br />
strength.<br />
Dirt, Dust, Surface<br />
Check contact joints<br />
TWO YEARLY<br />
General Inspection<br />
including checking the<br />
operation of gauges on it.<br />
Check heathiness of air<br />
cell.<br />
Examine values as per<br />
IS:1866<br />
Mechanical inspection of<br />
buchholz<br />
7-10 YEARLY<br />
Overall internal inspection<br />
including lifting of core and<br />
coil assembly<br />
Replenish with new oil,if oil is too<br />
much contaminated.<br />
Clean touch-up painting.<br />
Retighten.<br />
Clean, if required. Ensure proper<br />
functioning of indicator/Replace if<br />
punctured.<br />
Filter oil if required.<br />
Set floats, if required.<br />
Tighten all clamping arrangement,<br />
loose cleatings etc. Tighten all<br />
nuts and bolts and check locking<br />
arrangements and fasteners.<br />
Wash core and coil with dry<br />
transformer oil.<br />
NOTES:<br />
1. In addition to the above <strong>instruction</strong>s, reference should be made to<br />
IS:10028 “Code of practice for selection installation and maintenance<br />
of transformer’’<br />
2. Reference of IS:1866 "Code of practice for Maintenance and<br />
Supervision of Mineral insulating oil in equipments'' should be made<br />
for maintenance of oil while transformer is in service. Table 1&2 of<br />
IS:1866 are given at annexure 4.2 & 4.3 for ready reference.<br />
3. The inspection schedule specified for longer periods automatically<br />
includes those specified for shorter period.<br />
4. All maintenance test results and observations should be specifically<br />
recorded.<br />
5. Where matter given in the inspection book differs from that given in<br />
standards referred to, the transformer user should follow the <strong>instruction</strong><br />
book.<br />
6. In case of anything abnormal occuring during service, advice from<br />
<strong>BHEL</strong> should be obtained giving them complete particulars as to the<br />
nature and extent of occurrence, together with the name plate<br />
particulars in order to assist identification of the transformer.<br />
7. As efforts are being constantly made to improve designs and service,<br />
the transformer supplied may differ in minor details from data given<br />
herein.<br />
Prepared By Samvet Lahari, <strong>Bhopal</strong>. Phone- 5277412
ANNEXURE 4.2<br />
APPLICATION AND INTERPRETATION OF TESTS ON OIL IN TRANSFORMERS AND<br />
REACTORS (INCLUDING SELECTOR TANKS OF ON-LOAD TAP CHANGERS<br />
(CLAUSE 5.1 (a), 5.2, 6.0 and 7.1)<br />
Sl.No CHARACTERISTIC EQUIPMENT TEST METHOD TEST VENUE SUGGESTED PERMISSIBLE ACTION IF<br />
VOLTAGE (REF TO IEC/ISO F=FIELD INITIAL LIMIT OUTSIDE<br />
OR APPENDIX)<br />
L=LABORAT-<br />
ARY<br />
(1) (2) (3) (4) (5) (6) (7) (8)<br />
(i) Electric strength 145 kV and IS:6792-1972* F/L After filling 50 kV Recondition<br />
(breakdown above (average of 6 or re-filling (Min) or alternatively<br />
voltage-kV) brealdowns prior to If more econmic<br />
72 kV and on one cell filling energizing, 40 kV or other tests<br />
less than with 2.5 mm gap then after (Min) dictate, replace<br />
145 kV spacing) three months<br />
and after one year<br />
oil.<br />
Below 72.5 kV 30 kV<br />
(Min)<br />
(ii) water content 145 kV and IS:335-1983 L After filling 25 PPM Recondition oil<br />
(ppm) above or re-filling (Max) or alternatively<br />
prior to If more econmic<br />
Below 145 kV energizing, 35 PPM or other tests<br />
3 months dictate, replace<br />
and after one year oil.<br />
(iii) Specific resistance All voltages IS:6103-1971 L After filling 0.1X1012 Recondition if<br />
(resistivity or re-filling ohm-cm the value of the<br />
ohm-cm) at prior to (Min) at DDF permits,<br />
900C (see Note 9) energizing, 900C reclaim or replace<br />
3 months<br />
and after 2 years<br />
if not.<br />
(iv) Dielectric dissipation 145 kV and IS:6262-1971 L After filling 0.2 (Max) Reclaim or<br />
factor (tan δ) above or re-filling replace oil (limit<br />
at 900C Below 145 kV prior to 1.0 (Max) to be adopted<br />
energizing, then depends on the<br />
after 2 years type of equipment<br />
and <strong>instruction</strong>s<br />
from the<br />
manufacturer).<br />
(v) Neutralisation All voltage IS:1448 (P:2) F do 0.5 mg Reclaim or replace<br />
value (total 1967 or KOH/g oil<br />
acidity (see<br />
Note 10)<br />
L (Max)<br />
(vi) Sediment and/ All voltage Appendix A L do No sediment Recondition oil<br />
or precipitable or precipltable if sediment is<br />
sludge sludge should detected<br />
be detectable<br />
alternatively<br />
if more economic<br />
or other test<br />
dictate replace<br />
oil. Reclaim or<br />
replace oil if<br />
precipitable<br />
sludge is<br />
detected.<br />
(vii) Flash point All voltage IS:1448 (P:21) L do Decrease in Reclaim or<br />
(see Note 11) 1970 the flash point replace oil after<br />
15oC (Max) of<br />
the inital value<br />
minimum value<br />
125<br />
knowing causes.<br />
oC (viii) Interfacial All voltage IS:6104-1971 L do 0.018 N./m Reclaim or<br />
tension<br />
at 27<br />
(Min) replace oil.<br />
o PERIODICITY SATISFACTORY PERMISSIBILE<br />
OF TESTS FOR USE<br />
LIMIT SEE ALSO<br />
C<br />
(ix) Dissolved gas 145 kV and IS:9434-1979 L After filling IS:10593 Reclaim or<br />
analysis above or re-filling<br />
prior to<br />
energizing,<br />
3 months and<br />
after one year.<br />
1983 replace oil.<br />
Prepared By Samvet Lahari, <strong>Bhopal</strong>. Phone- 5277412
Note 1 The voltages indicated in col 3 are highest system voltages.<br />
Note 2 The full application of these recommendations to small transformers<br />
upto 1 MVA or below 36 kV will be technically necessary only in<br />
cases where high reliability is required. It will normally be uneconomic.<br />
In most cases, it could be limited to the simpler field tests and the<br />
periodicity of tests will be determined with relation to the reliability<br />
required. Inspection of oil in pole- mounted transformers is assumed<br />
to be uneconomic.<br />
Note 3 Characteristics are normally well above the permissible limits given<br />
in col 7 at the time of test of transformer in the manufacturer’s<br />
works. However, no separate limits have been fixed for this stage.<br />
Note 4 Higher limits may be required for electric strength and lower limits<br />
for water content prior to testing in the factory and prior to energizing<br />
the transformer. Special <strong>instruction</strong>s given by the manufacturer may<br />
be followed.<br />
Note 5 Suggested initial periodicity of tests have been given in col. 6.<br />
Subsequent intervals may vary depending on previous test results<br />
(progress of ageing) and on changed service conditions.<br />
Note 6 Instructions of equipment manufacturers should be taken into account<br />
in adoption of the recommendation of this table.<br />
Note 7 For application and interpretation of test in diverter tanks of on-load<br />
tap changers, guidance shall be taken from the manufacturer.<br />
Note 8 Alternatively an indication of the presence and effect of water content<br />
can be obtained from a resistivity comparison at 27 o C and 90 o C (see<br />
6.4.1.2).<br />
Note 9 Water content and acidity influence the values of the specific<br />
resistance. The limit is indicative only and when value falls below<br />
this limit the cause should be ascertained by other tests.<br />
Note 10 Perform test more frequently when value exceeds 0.3 mg KOH/g.<br />
For transformers subject to test (ii), method(s) it will be necessary<br />
to test more frequently to establish when neutralization value (total<br />
acidity) exceeds 0.1 mg KOH/g.<br />
Note 11 This test may also be required when an unusual odour is noted or<br />
when an internal fault has occured.<br />
Prepared By Samvet Lahari, <strong>Bhopal</strong>. Phone- 5277412
ANNEXURE 4.3<br />
GUIDELINES FOR THE CHARACTERISTICS OF OIL TO BE OBTAINED BEFORE<br />
ENERGIZING NEW TRANSFORMERS USING NEW INSULATING OILS ACCORDING<br />
TO IS:335-1983<br />
SL. CHARACTERISTIC EQUIPMENT TEST METHOD PERMISSIBLE<br />
NO. VOLTAGE (REF TO IS:OR LIMIT<br />
APPENDIX)<br />
SATISFACTORY<br />
FOR USE<br />
(1) (2) (3) (4) (5)<br />
(1) Electric strength<br />
(breakdown<br />
voltage kV)<br />
(ii) Specific<br />
resistance<br />
(resistivity ohmcm<br />
at 90 o C)<br />
(iii) Dielectric<br />
dissipation<br />
factor (tanδ) at<br />
90 o C Max.<br />
(iv) Water content,<br />
ppm Max.<br />
(v) Interfacial<br />
tension at 27 o C<br />
(Min) N/m<br />
(vi) Dissolved gas<br />
content<br />
Below 72.5 kV<br />
72.5 kV and less<br />
than 145 kV<br />
145 kV and<br />
above<br />
All voltages<br />
All voltages<br />
Below 72.5 kV<br />
72.5 kV and less<br />
than 72.5 kV<br />
145 kV and<br />
above<br />
All voltages<br />
145 kV and<br />
above<br />
IS:6792-1972<br />
IS:6103-1971<br />
IS:6262-1971<br />
IS:335-1983<br />
IS:6104-1971<br />
(Under<br />
Consideration)<br />
40 kV (rms) min<br />
50 kv (rms) min<br />
60 kV (rms) min<br />
1X10 12 ohm-cm<br />
(min)<br />
0.05<br />
25 ppm<br />
20 ppm<br />
15 ppm<br />
0.030<br />
Prepared By Samvet Lahari, <strong>Bhopal</strong>. Phone- 5277412
Prepared By Samvet Lahari, <strong>Bhopal</strong>. Phone- 5277412
Prepared By Samvet Lahari, <strong>Bhopal</strong>. Phone- 5277412
4.5 DO’S AND DON’TS<br />
4.5.1 DON’TS FOR POWER TRANSFORMER/REACTOR<br />
1. Do not energise without thorough investigation of the transformer/reactor, whenever<br />
any alarm of protection has operated.<br />
2. Do not re-energise the transformer/reactor, unless the Buchholz gas is analysed.<br />
3. Do not re-energise the transformer/reactor without conducting all pre-commissioning<br />
checks. The results must be comparable with results at works.<br />
4. Do not handle the off-circuit tap switch when the transformer is energised.<br />
5. Do not energise the transformer, unless the off-circuit tap switch handle is in<br />
locked position.<br />
6. Do not leave-off circuit tap switch handle unlocked.<br />
7. Do not leave tertiary terminals unprotected outside the tank, connect them to<br />
tertiary lightning arrestors protection scheme, when connected to load.<br />
8. Do not allow WTI/OTI temperature to exceed 55oC during dryout of transformer,<br />
and filter machine temperature beyond 60oC. 9. Do not parallel transformers which do not fulfil the condition given in clause 4.4.<br />
10. Do not use low capacity lifting jacks on transformer/reactor for jacking.<br />
11. Do not move the transformer/reactor with bushings mounted.<br />
12. Do not overload the transformer other than the specified limits as per IS:6600.<br />
13. Do not change the settings of WTI and OTI alarm and trip frequently. The setting<br />
should be done as per the site condition.<br />
14. Do not leave red pointer behind the black pointer in OTI and WTI.<br />
15. Do not leave any connection loose.<br />
16. Do not meddle with the protection circuits.<br />
17. Do not allow conservator oil level to fall below 1/4 level.<br />
18. Do not allow oil level to fall in the bushings, they must immediately to be topped<br />
up.<br />
19. Do not leave marshalling box doors open, they must be locked.<br />
20. Do not switch off the heater in marshalling box except to be periodically cleaned.<br />
21. Do not allow dirt and deposits on bushings, they should be periodically cleaned.<br />
22. Do not allow unauthorised entry near the transformer/reactor.<br />
23. Do not leave ladder unlocked, when the transformer/reactor is ‘ON’ in service, in<br />
case it is provided.<br />
24. Do not change the sequence of valve opening for taking standby pump and motor<br />
into circuit.<br />
25. Do not switch on water pump unless oil pump is switched on.<br />
26. Do not allow water pressure more than oil pressure in differential pressure gauge.<br />
27. Do not mix the oil, unless it conforms fully to IS:335.<br />
28. Do not allow inferior oil to continue in transformer/reactor. The oil should be<br />
immediately processed and to be used only when BDV/ppm conforms to IS:1866.<br />
29. Do not continue with pink silicagel, this should immediately be changed or<br />
regenerated.<br />
30. Do not leave secondary terminal of an unloaded CT open.<br />
31. Do not store transformer/reactor for long after reaching site. It must be erected<br />
and commissioned at the earliest.<br />
32. Do not keep the transformer/reactor gas filled at site for a longer period.<br />
Prepared By Samvet Lahari, <strong>Bhopal</strong>. Phone- 5277412
4.5.2 DO’S FOR POWER TRANSFORMER/REACTOR<br />
1. Check and thoroughly investigate the transformer/reactor whenever any<br />
alarm or protection operated.<br />
2. Check air cell in conservator.<br />
3. Attend the leakages on the bushing immediately.<br />
4. Examine the bushings for dirt deposits and coats, and clean them<br />
periodically.<br />
5. Check the oil in transformer and OLTC for di-electric strength and moisture<br />
content and take suitable action for restoring the quality.<br />
6. Check the oil level in oil cup and ensure air passages are free in the<br />
breather. If oil is less, make up the oil.<br />
7. Check the oil for acidity and sludge as per IS:1866.<br />
8. If inspection covers are opened or any gasket joint is to be tightened,<br />
then tighten the bolts evenly to avoid uneven pressure.<br />
9. Check and clean the relay and alarm contacts. Check also their operation,<br />
and accuracy and if required change the setting.<br />
10. Check the protection circuits periodically.<br />
11. Check the pointers of all gauges for their free movement.<br />
12. Clean the oil conservator thoroughly before erecting.<br />
13. Check the buchholz relay and readjust the floats, switches etc.<br />
14. Inspect the painting and if necessary retouching should be done.<br />
15. Check the OTI and WTI pockets and replenish the oil, if required.<br />
16. Remove the air through vent plug of the diverter switch before you energise<br />
the transformer.<br />
17. Check the oil level in the diverter switch and if found less, top up with<br />
fresh oil conforming to IS:335.<br />
18. Check the gear box oil level, if less top up with specified oil.<br />
19. Examine and replace the burnt or worn out contacts as per Annexure 4.1<br />
of Maintenance Schedule.<br />
20. Check all bearings and operating mechanism and lubricate them as per<br />
schedule.<br />
21. Open the equalising valve between tank and OLTC, wherever provided<br />
at the time of filling the oil in the tank.<br />
22. Connect gas cylinder with automatic regulator if transformer is to be<br />
stored for long, in order to maintain positive pressure.<br />
23. Fill the oil in the transformer/reactor at the earliest opportunity at site<br />
and follow storage <strong>instruction</strong>s.<br />
24. Check the door seals of marshalling Box. Change the rubber lining if<br />
required.<br />
25. Equalise the diverter compartment of the OLTC by connecting equalising<br />
pipe between flange joints provided on the tap changer head.<br />
Prepared By Samvet Lahari, <strong>Bhopal</strong>. Phone- 5277412
4.6 DISPOSAL<br />
The items to be disposed off are mineral oil, silicagel, gasket and other<br />
insulating material. For disposal of these items, following procedure is<br />
recommended.<br />
4.6.1 INSULATING OIL :<br />
The transformer oil is mineral Hydro Carbon (Petroleum) oil. No special<br />
risks are involved in the handling and use of transformer oil. Howerver, attention<br />
is drawn to the need for personnel hygiene i.e washing of skin & clothing,<br />
which has come in contact with oil by personnel dealing with these products.<br />
Hands in such cases should be washed carefully before eating and drinking<br />
and contaminated clothing should be changed. Also inhalation of fumes or<br />
vapours should be avoided.<br />
When used oil has to be disposed off, certain precautions are necessary<br />
to avoid risk of environmental pollution such as large spillage and leakage<br />
from the containers, which may otherwise result into destruction of greenary,<br />
water birds, fishes.<br />
Normally, non contaminated oil free of PCB (Poly Chlorinated Biphenyls)<br />
can be destructed by burning or sent to local authorities for asphalt production.<br />
However contaminated oil containing PCB shall be filled in drums and sent to<br />
local authorities for disposal.<br />
4.6.2 SILICAGEL :<br />
When silicagel can not be regenerated and to be disposed off, it can be<br />
dumped in a pit and covered with earth.<br />
4.6.3 GASKET AND OTHER INSULATING MATERIAL :<br />
Crok Gaskets & Nitrile Rubber Gaskets can be disposed off by burning<br />
in a place separately marked and prepared for the purpose. In case these can<br />
not be burnt, these can be dumped in a pit and covered with earth.<br />
Prepared By Samvet Lahari, <strong>Bhopal</strong>. Phone- 5277412