|2. Building Subsystems<br />

the TR or TE and may incorporate multiuser telecommunications outlet assemblies<br />

(MUTOAs) and consolidation points (CPs). The maximum horizontal cable length<br />

shall be 90 m (295 ft.), independent of media type. If a MUTOA is deployed, the<br />

maximum horizontal balanced twisted-pair copper cable length shall be reduced<br />

in accordance with Table 2.4.<br />

Recognized cabling:<br />

• 4-pair 100-ohm unshielded or shielded twisted-pair cabling:<br />

Category 5e, Category 6 or Category 6A<br />

• Multimode optical fiber cabling, 2-fiber (or higher fiber count)<br />

• Single-mode optical fiber cabling, 2-fiber (or higher fiber count)<br />

Workstation<br />

Workstation<br />

Information<br />

3 Meters<br />

Outlet<br />

Workstation<br />

Information<br />

3 Meters<br />

Outlet<br />

1<br />

2<br />

Information<br />

3 Meters<br />

Outlet<br />

100 Meters<br />

90 Meters<br />

90 Meters<br />

90 Meters<br />

100 Ohm, UTP/ScTP 4-pair for voice<br />

T568A or T568B wiring<br />

100 Ohm, UTP/ScTP 4-pair 62.5/125<br />

µm fiber for data or 50/125 µm<br />

fiber for data<br />

Telecommunications<br />

Room<br />

Cross-Connect<br />

6 Meters of<br />

Patch Cord<br />

Figure 2.2 – Horizontal Cable Maximum Distances<br />

and Information Outlets<br />

6. Work Area Work area (WA) components extend from the telecommunications<br />

outlet/connector end of the horizontal cabling system to the WA equipment.<br />

A minimum of two telecommunications outlets (permanent links) should be provided<br />

for each work area. Multiuser telecommunications outlet assemblies (MUTOAs),<br />

if used, are part of the WA.<br />

(See Table 2.4 for the maximum length of horizontal cables and work area cords.)<br />

|14 1.800.ANIXTER