|6. Conduit, Cable Basket and Ladder Fill Recommendations<br />

SECTION 6: CONDUIT, CABLE BASKET AND LADDER<br />

FILL RECOMMENDATIONS<br />

Conduit Fill Recommendations<br />

Conduit fill states the maximum amount of space that the installed cables should<br />

occupy in a given size conduit expressed as a percentage of the interior volume.<br />

When designing a conduit run, consider not only the cable being installed now but<br />

also the likelihood of having to add cables in the future.<br />

Table 6.1 (right) makes recommendations for the maximum cables to be installed<br />

in conduit.<br />

• Clearance should be ¼ inch at minimum and up to 1 inch for large cable<br />

installations or installations involving numerous bends.<br />

• When calculating clearance, make sure all cable diameters are equal.<br />

• Do not exceed recommended conduit fill requirements.<br />

• Typical OD for twisted-pair cabling is 0.25 to 0.35 inch.<br />

|68 1.800.ANIXTER