|3. Twisted-Pair Cable<br />
Step 8: Preserve the wire pair twists as close as possible<br />
to the point of termination. When connecting jacks and<br />
plugs, do not untwist the cable more than 0.5 inches<br />
for Category 5e, 6 and 6A cable.<br />
Helpful Hint:<br />
• A half of an inch of an untwisted wire pair results<br />
in 1.5 dB of near-end crosstalk.<br />
Step 9: Insert wires down into IDC terminal slots to<br />
position them before punching down. Maintain the twist.<br />
To “future-proof” an installation, terminate all four pairs.<br />
The picture above shows an outlet being wired to the T568B<br />
wiring scheme.<br />
|34 1.800.ANIXTER