SECUR®LeanStreamer, NH in-line disconnectors<br />
for fuses IEC 60269-2 / VDE 0636-2 size 00<br />
VDE 0660 part 107 / EN 60 947-3 / IEC 60 947-3<br />
3-pole switching<br />
Outgoing connection top and bottom.<br />
Arc chamber.<br />
Shock-protected ev<strong>en</strong> with lid op<strong>en</strong> and in park position.<br />
Mechanical fuse ret<strong>en</strong>tion.<br />
Degree of protection IP30 (front side), degree of protection near terminal dep<strong>en</strong>ds on installation.<br />
Connection contacts:<br />
– M8 screw; 2x M5 clamp, 12mm clear width<br />
– Prism clamp terminal Cu, Al* 16 - 70mm 2 s(r), s(s), f +AE<br />
(* Connections with aluminium conductors are not maint<strong>en</strong>ance-free (see page 8/2)<br />
For 60mm distance betwe<strong>en</strong> busbar c<strong>en</strong>tres:<br />
– screwless busbar contacting<br />
For 100mm distance betwe<strong>en</strong> busbar c<strong>en</strong>tres:<br />
– screw-on connection to drilled busbars, screw M8<br />
– mounting without drilling using a terminal clamp<br />
For 185mm distance betwe<strong>en</strong> busbar c<strong>en</strong>tres:<br />
– with an adapter<br />
for screwing onto undrilled busbars, screw M12<br />
mounting without drilling using a terminal clamp<br />
– with a double adapter<br />
for screwing onto drilled busbars, screw M12<br />
Type 3-pole switching<br />
Type of curr<strong>en</strong>t AC (50 - 60Hz)<br />
Rated operating voltage (Ue)** 690V AC<br />
Rated insulation voltage (Ui)** 1000V<br />
Rated surge withstand capacity (Uimp) without fuse monitoring** 8kV<br />
Rated operating curr<strong>en</strong>t (Ie)* 160A<br />
Utilisation categories AC-22B (690V)<br />
without fuse monitoring** AC-23B (400V)<br />
AC-23B (500V 125A)<br />
Conditional rated short-circuit curr<strong>en</strong>t*** 50kA<br />
For VDE 0636-2 NH fuses of all operating classes with power dissipation per phase<br />
* During continuous operation, the rated load factor specifi ed according to<br />
VDE 0660 part 500/EN 60 439-1, table 1, must be observed.<br />
12W<br />
For AC-23B, the distance to earthed parts must be at least 50mm at the top and 25mm at the side.<br />
** Fuse monitoring Ue, Ui 400V AC, Uimp 4kV, level of soiling: 2 (mains connections)<br />
*** Type tested with fuses of characteristic gL/gG.<br />
Pilot switch for lid position indication:<br />
2 (changeover) switches can be used<br />
Rated operating voltage (rated operating curr<strong>en</strong>t) 250V AC (5A), 30V DC (4A)<br />
Electronic fuse monitoring:<br />
2 LEDs<br />
with latching properties or remote reset, programmable using<br />
2 changeover switches<br />
2 x Cu 2.5mm 2 solid conductors, DIN 46 288 or<br />
2 x Cu 1.5mm 2 stranded conductors with sleeves, DIN 46 228-1/-2/-3<br />
The internal resistance of the measuring needle lies above the MOhm level and thereby meets<br />
VDE requirem<strong>en</strong>ts regarding contact voltage (>1000 Ohm/V.)<br />
To release turn off the upstream main switch.<br />
Circuit diagram on page 9/25<br />
8<br />
33