SECUR®LeanStreamer, NH in-line disconnectors<br />

for fuses IEC 60269-2 / VDE 0636-2 size 00<br />

VDE 0660 part 107 / EN 60 947-3 / IEC 60 947-3<br />

3-pole switching<br />

Outgoing connection top and bottom.<br />

Arc chamber.<br />

Shock-protected ev<strong>en</strong> with lid op<strong>en</strong> and in park position.<br />

Mechanical fuse ret<strong>en</strong>tion.<br />

Degree of protection IP30 (front side), degree of protection near terminal dep<strong>en</strong>ds on installation.<br />

Connection contacts:<br />

– M8 screw; 2x M5 clamp, 12mm clear width<br />

– Prism clamp terminal Cu, Al* 16 - 70mm 2 s(r), s(s), f +AE<br />

(* Connections with aluminium conductors are not maint<strong>en</strong>ance-free (see page 8/2)<br />

For 60mm distance betwe<strong>en</strong> busbar c<strong>en</strong>tres:<br />

– screwless busbar contacting<br />

For 100mm distance betwe<strong>en</strong> busbar c<strong>en</strong>tres:<br />

– screw-on connection to drilled busbars, screw M8<br />

– mounting without drilling using a terminal clamp<br />

For 185mm distance betwe<strong>en</strong> busbar c<strong>en</strong>tres:<br />

– with an adapter<br />

for screwing onto undrilled busbars, screw M12<br />

mounting without drilling using a terminal clamp<br />

– with a double adapter<br />

for screwing onto drilled busbars, screw M12<br />

Type 3-pole switching<br />

Type of curr<strong>en</strong>t AC (50 - 60Hz)<br />

Rated operating voltage (Ue)** 690V AC<br />

Rated insulation voltage (Ui)** 1000V<br />

Rated surge withstand capacity (Uimp) without fuse monitoring** 8kV<br />

Rated operating curr<strong>en</strong>t (Ie)* 160A<br />

Utilisation categories AC-22B (690V)<br />

without fuse monitoring** AC-23B (400V)<br />

AC-23B (500V 125A)<br />

Conditional rated short-circuit curr<strong>en</strong>t*** 50kA<br />

For VDE 0636-2 NH fuses of all operating classes with power dissipation per phase<br />

* During continuous operation, the rated load factor specifi ed according to<br />

VDE 0660 part 500/EN 60 439-1, table 1, must be observed.<br />

12W<br />

For AC-23B, the distance to earthed parts must be at least 50mm at the top and 25mm at the side.<br />

** Fuse monitoring Ue, Ui 400V AC, Uimp 4kV, level of soiling: 2 (mains connections)<br />

*** Type tested with fuses of characteristic gL/gG.<br />

Pilot switch for lid position indication:<br />

2 (changeover) switches can be used<br />

Rated operating voltage (rated operating curr<strong>en</strong>t) 250V AC (5A), 30V DC (4A)<br />

Electronic fuse monitoring:<br />

2 LEDs<br />

with latching properties or remote reset, programmable using<br />

2 changeover switches<br />

2 x Cu 2.5mm 2 solid conductors, DIN 46 288 or<br />

2 x Cu 1.5mm 2 stranded conductors with sleeves, DIN 46 228-1/-2/-3<br />

The internal resistance of the measuring needle lies above the MOhm level and thereby meets<br />

VDE requirem<strong>en</strong>ts regarding contact voltage (>1000 Ohm/V.)<br />

To release turn off the upstream main switch.<br />

Circuit diagram on page 9/25<br />

8<br />

33