14.04.2013 Views

phb2013_complete_en.pdf [18.3 MB] - Wöhner

phb2013_complete_en.pdf [18.3 MB] - Wöhner

phb2013_complete_en.pdf [18.3 MB] - Wöhner

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

CAPUS®EasyUse<br />

Changeover switch, 3-pole, 3-pole switching<br />

Changeover switch, 3-pole + N, 4-pole switching<br />

To IEC/EN 60947-3 125A 160A 200A 250A 315A 400A 630A 800A 1000A<br />

Thermal curr<strong>en</strong>t (lth) [A] 40°C 125 160 200 250 315 400 630 800 1000<br />

in control cabinet – – – 250 315 400 630 800 1000<br />

Rated insulation voltage (Ui) [V] 1000 1000 1000 1000 1000 1000 1000 1000 1000<br />

Electric str<strong>en</strong>gth (50 Hz, 1 min) [V] 4000 4000 4000 6000 6000 6000 8000 8000 8000<br />

Rated surge withstand capacity (Uimp) [kV] 8 8 8 8 8 8 12 12 12<br />

Nominal operating AC-23A (Ue 400V) 125 160 160 – – – – – –<br />

curr<strong>en</strong>t AC (le) [A] AC-23B (Ue 400V) – – – 180 200 250 500 630 1000<br />

AC-23A (Ue 500V) 100 125 125 – – – – – –<br />

AC-23B (Ue 500V) – – – 150 160 200 315 400 800<br />

AC-22A (Ue 690V) 100 125 160 200 250 315 4 500 630 4 800<br />

AC-23A (Ue 690V) 80 80 – – – – – – –<br />

AC-23B (Ue 690V) – – – 100 125 160 250 315 630<br />

AC-20A (Ue 800V) 125 160 200 250 315 400 630 800 1000<br />

AC-20A(Ue 1000V) 125 160 200 – – – 630 800 1000<br />

Working capacity AC 1 (Pe) [kW] AC-23A (3 x 400V) 69.2 88.6 88.6 90.0 100.0 125.0 250.0 315.0 501.0<br />

AC-23A (3 x 500V) 69.2 86.6 86.6 94.0 100.0 125.0 197.0 250.0 501.0<br />

AC-23A (3 x 690V) 76.4 76.4 76.4 86.0 108.0 138.0 216.0 272.0 544.0<br />

Reactive power [kVAR] 400V – – – 1040 131.0 166.0 261.0 333.0 416.0<br />

Rated breaking<br />

capacity [A]<br />

AC-23 400V – – – 1440 1600 2000 4000 4000 8000<br />

Rated making<br />

capacity [A]<br />

AC-23 400 V – – – 1800 2000 2500 5000 5000 10000<br />

Short-circuit behaviour 125A 160A 200A 250A 315A 400A 630A 800A 1000A<br />

Conditional short-circuit curr<strong>en</strong>t<br />

(peak value)<br />

13 13 13 12 12 12 20 20 32<br />

2 (lcm) [kA]<br />

Rated short-time withstand<br />

curr<strong>en</strong>t (1s)<br />

7 7 7 8 8 8 13 13 25<br />

2 (lcw) [kA] rms<br />

Mechanical service life without load<br />

[switching operations]<br />

30000 30000 30000 10000 10000 10000 10000 10000 10000<br />

Mechanical service life with load<br />

AC-22 A (400 V) [switching cycles]<br />

– – 1000 1000 1000 200 1000 100 500<br />

Operating frequ<strong>en</strong>cy [cycles per hour] – – – 120 120 60 60 20 20<br />

Tight<strong>en</strong>ing torque 3 [Nm] – – – 11/13 11/13 11/13 25/30 25/40 50/62<br />

Weight (3P) [kg] 1.8 1.8 1.9 4.8 5 5 11.5 11.9 22.5<br />

Weight (3P+N) [kg] 2.1 2.1 2.2 5.3 5.5 5.5 12.6 13.2 25<br />

Types of connection 125A 160A 200A 250A 315A 400A 630A 800A 1000A<br />

Cable (Cu) [mm 2] 95 95 120 240 240 240 2x240 2x240 –<br />

Laminated copper busbars (thickness/width) [mm] 5/25 5/25 5/30 2x5/30 2x5/30 2x5/30 2x6/45 2x6/45 2x10/60<br />

Tight<strong>en</strong>ing torque [Nm] 4/12 4/13 13/18 24 24 24 45 45 55<br />

1 Values for guidance only. The respective curr<strong>en</strong>t dep<strong>en</strong>ds on the motor manufacturer<br />

2 Without limiting protective device (short-circuit duration: 50 … 100 ms).<br />

3 Typical value for switches that work with continuous curr<strong>en</strong>t in an uninterrupted state.<br />

4 AC-22 B.<br />

8<br />

41

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!