2.4 Function<br />

1<br />

On the inlet side, the steam humidification systems <strong>Condair</strong> <strong>Esco</strong> DR 73 and<br />

DL 40 are connected to the live steam supply. The steam on hand, when<br />

the ceramic rotary-disk control valve is closed, is continuously drained by<br />

means of the primary condensate drain (spheric float) float). Thus, the humidifier<br />

is operable any time. The steam distributor, however, remains cold and<br />

does not heat the air current; no energy is wasted.<br />

With the ceramic rotary-disk control valve open, the steam passes through<br />

the strainer into the water separator. As a result of the multiple steam deflection<br />

in the water separator, the condensate, carried along, is reliably<br />

eliminated and drained via primary condensate drain.<br />

In the DR 73 type, the dried steam exits the water separator through the<br />

ceramic rotary-disk control valve to flow via main distribution pipe into the<br />

vertically arranged secondary pipes. The hot, dry steam is tapped at the<br />

centre of the steam distribution pipes and discharged under pressure on<br />

both sides, by means of special nozzles, at an angle to the air current.<br />

Condensate, accumulating in the vertical pipes, slides along the inside of<br />

the pipe down into the horizontally attached main distribution pipe (= collector).<br />

This spaciously designed pipe is drained by way of an externally<br />

mounted thermal secondary condensate drain.<br />

In the DL 40 type, the steam is directly routed into the steam distribution<br />

pipe, tapped at the centre of it and discharged under pressure, by means of<br />

special nozzles, into or against the air current. Condensate, accumulating<br />

along the inside of the pipe, is drained via condensate return line by way of<br />

an externally mounted thermal secondary condensate drain.<br />

Any condensate accumulating during system start-up is immediately drained<br />

by the primary steam trap. The pre-dried steam is led via control valve into<br />

the distribution system, where it is taken from the dry center of the pipe<br />

and introduced uniformly into the volume flow by means of the differential<br />

pressure. Thanks to this dependable system, there is no need for a start-up<br />

protection and jacket heating.<br />

Condensate-related backpressure is an impossibility in both lines of products<br />

even in a pressureless state, because the steam distributor pipe is<br />

drained via condensate return line with inherent down gradient.