2<br />

– Type DL 40<br />

1. Provide openings (round holes) in duct.<br />

2. From the duct side, slide the steam distribution pipe through the prepared<br />

openings. Make sure not to damage the steam pipe ends.<br />

3. Mount the connection unit with connecting flange to the side of the<br />

duct. Make sure not to damage O-rings. To improve sliding, slightly<br />

moisten O-rings with water. Never use oil or grease.<br />

4. Secure the distribution pipe with the bolt.<br />

5. Install the steam and condensate connections. Make sure that the<br />

condensate line has a down slope of approx. 0.5 - 1%.