3.2 Connection unit and ceramic rotary-disk control valve<br />
Steam connection unit <strong>Esco</strong> 20<br />
Valve admission pressure p1 (bar)<br />
Valve size<br />
Humidification capacity m D [kg/hr]<br />
Selection diagram for dimensioning the<br />
connection unit <strong>Esco</strong> 20 with the corresponding<br />
valve size.<br />
Steam connection unit <strong>Esco</strong> 30<br />
Valve admission pressure p1 (bar)<br />
Valve size<br />
Selection diagram for dimensioning the<br />
connection unit <strong>Esco</strong> 30 with the corresponding<br />
valve size.<br />
• Connection unit <strong>Esco</strong> 10, 20 and 30<br />
• Ceramic rotary-disk control valve<br />
Characteristic curve for 18 different valve sizes, depending on humidification<br />
capacity and steam pressure<br />
Example:<br />
– Required humidification capacity: 100 kg/hr<br />
– Available steam pressure: 1.5 bar<br />
The intersection of the two “search lines” for the connection unit is located<br />
in the <strong>Esco</strong> 10 diagram between the characteristic curves 10/7 and<br />
10/8.<br />
– <strong>Esco</strong> 10 with valve size 10/7 provides 76 kg/hr<br />
– <strong>Esco</strong> 10 with valve size 10/8 provides 120 kg/hr<br />
The HVAC engineer will select one of the two possible valves:<br />
a) the <strong>Esco</strong> 10-10/7, if it is permissible for the “comfort” humidification<br />
to be somewhat lower, in favour of optimal controllability during<br />
the remainder of the operating time.<br />
b) the <strong>Esco</strong> 10-10/8, if the humidity requirements were calculated<br />
rather tightly, or if a certain application in process technology<br />
requires the max. steam capacity.<br />
With the rotary control valve actuator CA 150, the steam output can<br />
be limited to the actual system requirement. Without this limitation, the<br />
steam boiler output must be dimensioned to correspond with the max.<br />
steam capacity of the ceramic rotary-disk control valve.<br />
Note:<br />
The computer dimensioning program will always select the larger valve<br />
size.<br />
Steam connection unit <strong>Esco</strong> 10<br />
Valve size<br />
Humidification capacity m D [kg/hr] Humidification capacity m D [kg/hr]<br />
Valve admission pressure p1 (bar)<br />
Selection diagram for dimensioning the connection unit <strong>Esco</strong> 10 with the corresponding<br />
valve size.<br />