3.2 Connection unit and ceramic rotary-disk control valve<br />

Steam connection unit <strong>Esco</strong> 20<br />

Valve admission pressure p1 (bar)<br />

Valve size<br />

Humidification capacity m D [kg/hr]<br />

Selection diagram for dimensioning the<br />

connection unit <strong>Esco</strong> 20 with the corresponding<br />

valve size.<br />

Steam connection unit <strong>Esco</strong> 30<br />

Valve admission pressure p1 (bar)<br />

Valve size<br />

Selection diagram for dimensioning the<br />

connection unit <strong>Esco</strong> 30 with the corresponding<br />

valve size.<br />

• Connection unit <strong>Esco</strong> 10, 20 and 30<br />

• Ceramic rotary-disk control valve<br />

Characteristic curve for 18 different valve sizes, depending on humidification<br />

capacity and steam pressure<br />

Example:<br />

– Required humidification capacity: 100 kg/hr<br />

– Available steam pressure: 1.5 bar<br />

The intersection of the two “search lines” for the connection unit is located<br />

in the <strong>Esco</strong> 10 diagram between the characteristic curves 10/7 and<br />

10/8.<br />

– <strong>Esco</strong> 10 with valve size 10/7 provides 76 kg/hr<br />

– <strong>Esco</strong> 10 with valve size 10/8 provides 120 kg/hr<br />

The HVAC engineer will select one of the two possible valves:<br />

a) the <strong>Esco</strong> 10-10/7, if it is permissible for the “comfort” humidification<br />

to be somewhat lower, in favour of optimal controllability during<br />

the remainder of the operating time.<br />

b) the <strong>Esco</strong> 10-10/8, if the humidity requirements were calculated<br />

rather tightly, or if a certain application in process technology<br />

requires the max. steam capacity.<br />

With the rotary control valve actuator CA 150, the steam output can<br />

be limited to the actual system requirement. Without this limitation, the<br />

steam boiler output must be dimensioned to correspond with the max.<br />

steam capacity of the ceramic rotary-disk control valve.<br />

Note:<br />

The computer dimensioning program will always select the larger valve<br />

size.<br />

Steam connection unit <strong>Esco</strong> 10<br />

Valve size<br />

Humidification capacity m D [kg/hr] Humidification capacity m D [kg/hr]<br />

Valve admission pressure p1 (bar)<br />

Selection diagram for dimensioning the connection unit <strong>Esco</strong> 10 with the corresponding<br />