<strong>CIDCO</strong> <strong>OF</strong> MAHARASHTRA LTD<br />

C.A.No.03/<strong>CIDCO</strong>/EE(Elect)/2011-12 Sr. Page No.<br />

3.0 It is not the intent to specify herein all the details of design and<br />

construction of the equipment. However the equipment offered shall<br />

confirm in all respects to high standard of engineering design and<br />

workmanship. The installation of the infrastructure shall be executed in a<br />

neat manner and as per good engineering practices. The shop tests as<br />

well as pre-commissioning tests at site shall be conducted as per relevant<br />

IS and as per requirements of individual equipment as well as the set<br />

norms.<br />

4.0 The ratings, performance, testing at works, installation, testing at site,<br />

pre-commissioning checking and commissioning of all the equipment<br />

required shall conform to the latest revisions of all the relevant IS<br />

specifications.<br />

5.0 Site Conditions:<br />

All the equipments offered shall be suitable for following site conditions:-<br />

a) Maximum Temperature : 45 Deg. C<br />

b) Minimum Temperature : 6 Deg. C<br />

c) Design Ambient Temperature : 40 Deg. C<br />

d) Maximum Humidity : 96%<br />

e) Seismic Condition : As per IS 1893<br />

f) Atmosphere : Corrosive as found near as sea<br />

shore.<br />

5.1 The equipment to be supplied by the contractor shall be designed/<br />

suitable for following supply system.<br />

5.1.1 Voltage stepped down to 11KV<br />

Voltage : 11 KV<br />

Frequency : 50 Hz<br />

Fault level : 350 MVA