4. Motor Frames.<br />
5. Non-current carrying metallic parts of electrical equipment such as<br />
switchgear, switch rocks, panel boards, motor control centers,<br />
lighting, power and instrument panels, push button stations, cable<br />
trays, pipes conduits, terminal boxes etc.<br />
6. All fences/enclosures housing electrical equipment.<br />
7. All still structures, rails etc. including bonding between sections.<br />
8. Shield Wire.<br />
9. Structural steel Columns of building etc.<br />
10. Loading racks.<br />
5.3 System shall be earthed by two distint conductors directly connected to<br />
independent earth electrodes which in turn, shall be connected to the<br />
earth loop. The earth connection shall be properly made. A small flexible<br />
aluminium cable loops to bridge the top cover of the transformer and the<br />
tank shall be provided to avoid earth fault current passing through<br />
fastening bolts when there is lightning surge, high voltage surge or failure<br />
of the bushings.<br />
5.4 Each Lightening Arrestor shall be connected to a separate electrode<br />
located as close as possible to it and within he fenced area for each set of<br />
arrestors shall be spaced such that they are all within the enclosing fence.<br />
Each of these electrodes shall be connected to the main earth grid.<br />
5.5 The shield wire shall be connected with the main grid solidly and net<br />
through supporting steel structures.<br />
5.6 All paint, scale and enamel shall be removed from the contact surface<br />
before the earthing connections are made.