SCOPE OF WORK (ELECTRICAL) - CIDCO Maharashtra Ltd.
SCOPE OF WORK (ELECTRICAL) - CIDCO Maharashtra Ltd.
SCOPE OF WORK (ELECTRICAL) - CIDCO Maharashtra Ltd.
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
<strong>CIDCO</strong> <strong>OF</strong> MAHARASHTRA LTD<br />
C.A.No.03/<strong>CIDCO</strong>/EE(Elect)/2011-12 Sr. Page No.<br />
Sr. Indian Standard<br />
Title<br />
No. Spec. No.<br />
4. IS:3975 Mild steel wires, strips and tapes for<br />
armouring of cables.<br />
5. IS:2633 Methods of testing weight, thickness and<br />
uniformity of coating on hot dipped<br />
galvanized articles.<br />
6. IS:209 Specification for Zinc<br />
7. IS:1753 Aluminium conductors for insulated cables.<br />
8. IEC:502 Extruded solid dielectric insulated power<br />
cables for rated voltages form 1KV upto 30<br />
KV.<br />
9. IEC:540 & 540A Test methods for insulation and sheaths of<br />
electric cables and cords.<br />
ANNEXURE-II<br />
11KV XLPE CABLES<br />
DESIRED TECHNICAL PARTICULARS<br />
Sr. Description Unit 11kV<br />
No.<br />
Particulars<br />
1. Cable Size Core x Sq.mm. 3C x 300 sq.mm.<br />
2. System Voltage kV 11 KV<br />
3. Type of cable XLPE Insulated<br />
4. Conductor material Aluminium<br />
5. Minimum No. of<br />
strands<br />
No. 30<br />
6. Nominal thickness of<br />
XLPE insulation<br />
mm 3.6<br />
7. Minimum thickness of<br />
common covering<br />
mm 0.7<br />
8. Armouring 4mm x 8 mm