Distribution<br />
<strong>G3</strong> <strong>Series</strong> <strong>PROFIBUS</strong>‐<strong>DP</strong> <strong>Technical</strong><br />
<strong>Manual</strong><br />
Distribution of I/O capability can be easily achieved with the <strong>G3</strong> platform by means of Sub-Bus modules.<br />
I/O modules, valve manifolds and/or a combination of both can be simply separated from the main manifold<br />
and distributed via a sub-bus communication cable. The <strong>G3</strong> platform uses the same I/O modules on the<br />
main manifold as on the distribution chain. The main communication module can control up to 16 I/O<br />
modules either on the main manifold or as part of the sub-bus connections. To utilize the sub-bus<br />
distribution capabilities the Sub-Bus OUT module must be located on the end of the main communication<br />
manifold and a Terminator Module must be located at the last sub-bus component.<br />
Example 1<br />
2<br />
6<br />
10<br />
5<br />
5<br />
5<br />
7<br />
7<br />
7<br />
Power<br />
Supply<br />
1<br />
Detail No. Description<br />
1 Main Communication Module (Node)<br />
2 Sub-Bus Power Cable (Can be connected to separate power supply for isolated power control)<br />
3 Distributed Sub-Bus Valve Module<br />
4 Sub-Bus IN module<br />
5 Sub-Bus OUT module<br />
6 Sub-Bus Communication Cable<br />
7 I/O Modules<br />
8 Terminator Module (Used to terminate sub-bus)<br />
9 Aux. Power IN (Used to augment Input power and/or supply power to Output modules)<br />
10 Aux. Power OUT (Can be used to supply power to distributed modules)<br />
3<br />
4 8<br />
7<br />
9<br />
TD<strong>G3</strong>PTTM1-2EN 02/09<br />
Subject to change without notice<br />
www.numatics.com/g3<br />
Fieldbus network<br />
4<br />
9<br />
Main Fieldbus<br />
Valve<br />
Manifold with<br />
I/O<br />
Distributed<br />
Sub-Bus<br />
Valve<br />
Manifold<br />
Distributed<br />
Sub-Bus<br />
I/O<br />
Modules<br />