If modules of the same length are to be connected<br />

together, lamps of the same wattage should be<br />

used in order to ensure uniform illumination.<br />

FH/HE lamps of similar light density<br />

which can be combined in one system<br />

of modules with differing lengths:<br />

The max. number of luminaires per power supply<br />

feed is 28 per group. Also, a maximum load of<br />

4 Amps per group must not be exceeded.<br />

FH lamps (Osram terminology) or HE lamps (Philips<br />

terminology) have the same light density regardless<br />

of wattage or length of lamp.<br />

Module length L1 Lamp<br />

666 mm T16 14 W<br />

966 mm T16 21 W<br />

1266 mm T16 28 W<br />

1566 mm T16 35 W<br />

Lamp wattage Max. no. of modules (per group) Operating current per module in A<br />

14 W 28 0.08<br />

21 W 28 0.11<br />

28 W 26 0.15<br />

35 W 23 0.17<br />

24 W 28 0.12<br />

39 W 21 0.19<br />

49 W 16 0.24<br />

54 W 14 0.27<br />

80 W 10 0.39<br />

*figures are valid for use with a Type B 16 Amp circuit breaker<br />