Figure 1:<br />

Terminals<br />

X3<br />

IP1<br />

”1”<br />

”0”<br />

IP2<br />

Jumpers on X3 on PCB 1044450210 are placed for the wanted option according to the scheme below. (See Figure 2).<br />

HAS-111DG<br />

Jumper<br />

1 = Mounted<br />

0 = Not mounted<br />

No option<br />

Option B1, B2, B3<br />

Dead bus<br />

Option C<br />

Deactivation of<br />

df/dt function<br />

Option D<br />

Continuous pulse<br />

Option E<br />

Voltage difference,<br />

analogue output<br />

B1 B2 B3<br />

X3-1 0 1<br />

X3-2 0 1<br />

X3-3 0 1<br />

X3-4 0 1 1<br />

X3-5 0 1<br />

X3-6 0 0 0 0<br />

X3-7 0 0 0 0<br />

X3-8 0 0 0 0<br />

B1: Dead bus; only busbar side.<br />

B2: Dead bus; busbar side or generator side.<br />

B3: Dead bus; busbar side and generator side. (Please notice that B2 is also included in B3).<br />

Figure 2:<br />

Jumpers X3-1 to X3-8. (Note: Only X3-1…-5 are used).<br />

X3-1<br />

Terminals<br />

/D/<br />

Wenn das HAS-111DG auf SMD-Bauelementen basiert, siehe unten.<br />

Die folgende Information bezieht nur auf das HAS-111DG mit den Platinenummern 1044450210 und 1044450220 (Revision C und<br />

höher).<br />

Schaltdrahteinstellung für Wahlmöglichkeiten:<br />

A: Erhöhtes Phasenfenster<br />

B: Tote Sammelschiene<br />

C: Deaktivierung der df/dt-Schutzfunktion<br />

D: Dauersynchronisierimpuls<br />

E: Spannungsdifferenz Analogausgang<br />

<strong>DEIF</strong> A/S • Tel: +45 9614 9614 • Fax: +45 9614 9615 • E-mail:deif@deif.com<br />