Possible fail in RMV-142D:<br />

No light in “<strong>Power</strong>” LED:<br />

Setpoints are not correct:<br />

Relay functions are not correct:<br />

(Energised/de-energised/latch)<br />

Wrong auxiliary voltage module is mounted, or it is not mounted correctly.<br />

Wrong voltage modules are mounted, or they are not mounted correctly. Please<br />

note that two voltage modules have to be mounted.<br />

Jumper settings for relays are not set correctly.<br />

RMC-111D:<br />

Setting: Short circuit: 200%<br />

Delay:<br />

50% of T1<br />

Connect nominal supply voltage:<br />

Connect current – 175% of nominal<br />

current to L1:<br />

Set current to 225%:<br />

Green “<strong>Power</strong>” LED is lit.<br />

Yellow I>> LED is not lit.<br />

Yellow I>> LED is lit immediately, red I>> LED for the relay is lit and the relay is<br />

activated after 50% of the maximum delay. (50% of 1, 5 or 10 s).<br />

RMC-122D:<br />

Setting: Short circuit: 200%<br />

Delay:<br />

50% of T1<br />

Overcurrent: 100%<br />

Delay:<br />

50% of T2<br />

Connect nominal supply voltage:<br />

Connect current – 90% of nominal<br />

current to L1:<br />

Set current to 110%:<br />

Set current to175%:<br />

Set current to 225%:<br />

Green “<strong>Power</strong>” LED is lit.<br />

Yellow I> LED is not lit.<br />

Yellow I> LED is lit immediately, red I> LED for the relay is lit and the relay is<br />

activated after 50% of the maximum delay. (50% of 20, 60 or 120 s).<br />

Yellow I>> LED is not lit.<br />

Yellow I>> LED is lit immediately, red I>> LED for the relay is lit and the relay is<br />

activated after 50% of the maximum delay. (50% of 1, 5 or 10 s).<br />

RMC-132D:<br />

Setting: Overcurrent1: 100%<br />

Delay:<br />

50% of T1<br />

Overcurrent2: 100%<br />

Delay:<br />

50% of T2<br />

Connect nominal supply voltage:<br />

Connect current – 90% of nominal<br />

current to L1:<br />

Set current to 110%:<br />

Green “<strong>Power</strong>” LED is lit.<br />

Yellow I>1 and I>2 LEDs are not lit.<br />

Yellow I>1 and I>2 LEDs are lit immediately, red I>1 and I>2 LEDs for the relay are<br />

lit and the relays are activated after 50% of the maximum delay. (50% of 20, 60 or<br />

120 s).<br />

RMC-131D:<br />

Setting: Diff. current: 20%<br />

Delay:<br />

50% of T1<br />

Connect nominal supply voltage:<br />

Connect current – 15% of nominal<br />

current to L1:<br />

Set current to 25%:<br />

Green “<strong>Power</strong>” LED is lit.<br />

Yellow I’> LED is not lit.<br />

Yellow I’> LED is lit immediately, red I’> LED for the relay is lit and the relay is<br />

activated after 50% of the maximum delay (50% of 1, 5 or 10 s).<br />

<strong>DEIF</strong> A/S • Tel: +45 9614 9614 • Fax: +45 9614 9615 • E-mail:deif@deif.com<br />