RMQ-111D:<br />

Setting: Excitation loss: 10%<br />

Delay:<br />

10 s<br />

Connect nominal supply voltage:<br />

Connect measuring voltage and<br />

current in the right coupling.<br />

Voltage set to nominal value.<br />

Current set to 5% of nominal value.<br />

Sin(ϕ) = -1:<br />

Current set to 15%, Sin(ϕ) = -1:<br />

Green “<strong>Power</strong>” LED is lit.<br />

Yellow -Q> LED is not lit.<br />

Yellow -Q> LED is lit immediately, red -Q> LED for the relay is lit and the relay is<br />

activated after 10 s.<br />

RMQ-121D:<br />

Setting: Overexcitation: 100%<br />

Delay:<br />

10 s<br />

Connect nominal supply voltage:<br />

Connect measuring voltage and<br />

current in the right coupling.<br />

Voltage set to nominal value.<br />

Current set to 90% of nominal value.<br />

Sin(ϕ) = 1:<br />

Current set to 110%, Sin(ϕ) = 1:<br />

Green “<strong>Power</strong>” LED is lit.<br />

Yellow Q> LED is not lit.<br />

Yellow Q> LED is lit immediately, red Q> LED for the relay is lit and the relay is<br />

activated after 10 s.<br />

Possible fail in RMP-111/112/121D and RMQ-111/121D:<br />

No light in “<strong>Power</strong>” LED:<br />

Setpoints are not correct:<br />

Relay functions are not correct:<br />

(Energised/de-energised/latch)<br />

RMF-112D:<br />

Setting: Underfrequency: 95%<br />

Delay:<br />

5 s<br />

Overfrequency: 105%<br />

Delay:<br />

5 s<br />

Wrong auxiliary voltage module is mounted, or it is not mounted correctly.<br />

Wrong voltage module or current module, or the internal reference voltage is not<br />

adjusted correctly.<br />

Jumper settings for relays are not set correctly.<br />

Connect nominal supply voltage:<br />

Connect nominal measuring voltage -<br />

nominal frequency:<br />

Adjust “Underfrequency” to 100%:<br />

Adjust “Overfrequency” to 100%:<br />

Green “<strong>Power</strong>” LED is lit.<br />

Yellow f< and f> LEDs are not lit.<br />

Yellow f< LED is lit immediately, red f< LED for the relay is lit and the relay is<br />

activated after 5 s.<br />

Yellow f> LED is lit immediately, red f> LED for the relay is lit and the relay is<br />

activated after 5 s.<br />

Possible fail in RMF-112D:<br />

No light in “<strong>Power</strong>” LED:<br />

Wrong auxiliary voltage module is mounted, or it is not mounted correctly.<br />

f< or f> will not activate: DIP switch for nominal frequency is not set correctly, or the frequency of the<br />

measuring voltage is not exactly 50.0 or 60.0 Hz. If the frequency is e.g. 50.5 Hz, it<br />

may not be possible to activate the f< setpoint, when it is adjusted to 100%.<br />

Setpoints have no function:<br />

Wrong voltage module, or it is not mounted correctly.<br />

Relay functions are not correct:<br />

Jumper settings for relays are not set correctly.<br />

(Energised/de-energised/latch)<br />

LMR-111D/LMR-122D/G59:<br />

Setting: Delay: 5 s (Not in G59)<br />

Sens: 10 deg./ 2.5 Hz/s (2.5 Hz/s not in LMR-111D)<br />

f: 105% (Only in G59)<br />

Connect nominal supply voltage:<br />

Connect nominal measuring voltage:<br />

Green “<strong>Power</strong>” LED is lit.<br />

Yellow “Supervision” LED (LEDs in LMR-122D) is/are lit after 5 s. Red “Mains fail”<br />

LED is not lit, and the relays are not activated.<br />

“f>, f