General<br />

This boiler is designed <strong>for</strong> <strong>use</strong> as part of a sealed water central<br />

heating system with fully pumped circulation. The pump,<br />

expansion vessel <strong>and</strong> associated safety devices are all fi tted<br />

within the boiler.<br />

Safety valve<br />

The safety valve is an integral part of the boiler <strong>and</strong> it cannot<br />

be adjusted. The pipe from the safety discharge valve must<br />

discharge safely in accordance with st<strong>and</strong>ards.<br />

• Ensure all cleanser is removed from the whole system be<strong>for</strong>e<br />

adding an inhibitor.<br />

For long-term corrosion protection after fl ushing, an inhibitor<br />

suitable <strong>for</strong> stainless steel heat exchangers can be <strong>use</strong>d. Either<br />

Sentinel X100 or Fernox F1 inhibitor can be <strong>use</strong>d.<br />

The boiler is suitable <strong>for</strong> <strong>use</strong> on systems using softened water.<br />

7.3 Dimensions<br />

Expansion vessel<br />

130<br />

The boiler has an integral expansion vessel with a capacity of 8<br />

litres (1.76 gallons), with a charge pressure of 0.75bar.<br />

The heating system volume should be calculated to<br />

ensure that the expansion vessel is suitable, it may<br />

be necessary to add an additional vessel.<br />

- In GB, Guidance on vessel sizing is also given in the current<br />

issue of BS5449 <strong>and</strong> BS7074 Part 1.<br />

740<br />

- In IE, current edition of I.S.813 “Domestic Gas Installations”.<br />

Bypass<br />

The boiler is fi tted with an automatic bypass.<br />

425<br />

<strong>24</strong>kW=310<br />

<strong>28</strong>kW=340<br />

• Ensure that under no circumstances does the fl ow rate drop<br />

below the fi gure specifi ed, refer to chapter "Technical data".<br />

Filling the sealed system<br />

Suitable external fi lling systems are shown diagrammatically,<br />

see diagram - Heating circuit design.<br />

The system should be pressurised to 1.0bar, indicated on the<br />

digital display with no heating dem<strong>and</strong>.<br />

7.4 Mounting<br />

• Make sure that the equipment <strong>use</strong>d <strong>for</strong> implementing the<br />

installation is compatible with that of the appliance.<br />

• Determine the assembly location. See the "Appliance<br />

location" chapter.<br />

Drain points<br />

Drain taps must be provided at all low points of the system,<br />

which will allow the entire system to be drained.<br />

Drain taps shall be to the current issue of BS<strong>28</strong>79.<br />

Water treatment<br />

Existing system- It is essential that prior to installing the new<br />

boiler the system is thoroughly fl ushed.<br />

New system- For optimum per<strong>for</strong>mance after installation, the<br />

boiler <strong>and</strong> its associated central heating system should also be<br />

fl ushed.<br />

Flushing shall be carried out in accordance with BS 7593, a<br />

chemical cleanser can be <strong>use</strong>d either Sentinel X300, X400 or<br />

Fernox F3 are suitable.<br />

It is recommended to fl ush existing systems fi rst be<strong>for</strong>e fi tting<br />

the new boiler.<br />

- 10 - Service Call 0844 736 9042, Technical Help (Chargeable) Call 0906 802 0253