• Leave these instructions <strong>and</strong> the ‘Benchmark’ Installation,<br />
Commissioning <strong>and</strong> Service Record with the <strong>use</strong>r.<br />
• Re-pressurise the system as instructed by your installer.<br />
• If the symbol is displayed on the screen, display the<br />
fault code memory (see chapter " Trouble-shooting ►Fault<br />
memory").<br />
• Press the reset button<br />
to restart the appliance.<br />
MAINTENANCE<br />
To ensure the continued effi cient <strong>and</strong> safe operation of the<br />
boiler it is recommended that it is checked <strong>and</strong> serviced at<br />
regular intervals. The frequency of servicing will depend upon<br />
the particular installation <strong>and</strong> usage, but in general once a year<br />
should be enough.<br />
It is the Law that any servicing is carried out by a competent<br />
person approved at the time by the Health <strong>and</strong> Safety<br />
Executive.<br />
• Be<strong>for</strong>e commencing with a service or replacement of parts<br />
isolate the boiler from the electrical supply <strong>and</strong> turn off the<br />
gas supply at the gas isolation valve.<br />
• When replacing a part on this appliance, <strong>use</strong> only spare<br />
parts that you can be assured con<strong>for</strong>m to the safety <strong>and</strong><br />
per<strong>for</strong>mance specifi cation that we require. Do not <strong>use</strong><br />
reconditioned or copy parts that have not been clearly<br />
authorised by <strong>Heatline</strong>.<br />
• If any electrical connections have been disconnected <strong>and</strong><br />
after their connection, checks to the earth continuity, polarity,<br />
short circuit <strong>and</strong> resistance to earth must be repeated using a<br />
suitable multimeter, as described in chapter "Trouble-shooting<br />
► Fault diagnosis ► Check the electrical installation".<br />
• After servicing, complete the relevant Service Interval Record<br />
section of the Benchmark Checklist located in the back pages<br />
of this document.<br />
15 Trouble-shooting<br />
• Check the functional fl ow diagram.<br />
15.1.1 Check the electrical installation<br />
2<br />
1<br />
Key<br />
1 Main board<br />
2 Neutral<br />
3 Live<br />
4 Multimeter<br />
• Remove the front casing panel<br />
V<br />
3<br />
4<br />
15.1 Fault diagnosis<br />
The following checks should be per<strong>for</strong>med be<strong>for</strong>e proceeding<br />
onto specifi c diagnostics:<br />
• Make sure that the electricity supply has not been interrupted<br />
<strong>and</strong> that the appliance is connected correctly (See chapter<br />
"Trouble-shooting ► Fault diagnosis ► Check the electrical<br />
installation")<br />
• Check the appliance’s gas supply (See chapter "Troubleshooting<br />
► Fault diagnosis ► Check the gas supply").<br />
• Ensure that the isolating valves are open.<br />
• Check the external electrical supply to the boiler is on <strong>and</strong> a<br />
supply of 230V is present at the ‘L’ <strong>and</strong> ‘N’ terminals on the<br />
main board.<br />
• Check the electrical installation <strong>and</strong> appliance, carry out tests<br />
<strong>for</strong> earth continuity, polarity, short circuit <strong>and</strong> resistance to<br />
earth, using a suitable multimeter.<br />
• Check the link FP –RT is secure or the connected control,<br />
connected at these points, is functioning correctly.<br />
• Bare metal points such as screws or rivets will act as suitable<br />
earth check points on the appliance.<br />
• Ensure that the pressure indicator displays a value of 1.0 bar<br />
(if the pressure falls below 0.4 bar, the air vent function will<br />
run automatically <strong>for</strong> a period of 5 minutes until you see 0.5<br />
bar on the pressure indicator). If not, re-charge the system.<br />
• Check that all external controls are connected correctly.<br />