Important information<br />

1.4.3 Commissioning<br />

WARNING<br />

Danger of injury through electric shock.<br />

Non-observance of warnings can result in serious injury or damage.<br />

� Only hard-wired network connections are permitted. The device must be<br />

grounded (DIN EN 61140; VDE 0140-1).<br />

� <strong>Frequency</strong> <strong>converter</strong>s of the <strong>FKO</strong> series can contain contact currents<br />

(leakage currents) > 3.5 mA. According to chapter 4.3.5.5.2 of DIN EN<br />

61800-5-1, a reinforced protective ground wire (at least 10 mm 2 Cu or<br />

16 mm 2 Al) must be used.<br />

� If three-phase frequency <strong>converter</strong>s are in use, it is not permitted to use<br />

standard type A FI protection switches, or RCDs (residual currentoperated<br />

protective devices) to protect from direct or indirect contact.<br />

According to DIN VDE 0160, section 5.5.2 and EN 50178, section<br />

5.2.11.1, the FI protection switch must be universal current sensitive<br />

(RCD type B).<br />

� The following terminals can lead to dangerous currents even when the<br />

motor is not running:<br />

– Supply terminals X1: L1, L2, L3<br />

– Motor connection terminals X2: U, V, W<br />

– Connecting terminals X6, X7: Relay contacts for relays 1 and 2<br />

� If different voltages are in use (e.g. +24 V/230 V), crossing cable runs<br />

are never permitted. The operator must also ensure compliance with the<br />

applicable regulations (e.g. double or strengthened insulation acc. to DIN<br />

EN 61800-5-1).<br />

� The drive control contains components susceptible to electrical<br />

discharge. These components can be destroyed through improper<br />

handling; therefore, precautionary measures against electrostatic<br />

charges must be taken when work is performed on these components.<br />

10 Operating manual <strong>FKO</strong>