Parameters<br />
2.153 MOP response time Unit: s<br />
Relationship to<br />
parameter:<br />
Parameter manual:<br />
p. xy<br />
Transfer status:<br />
48 Operating manual <strong>FKO</strong><br />
2<br />
min: 0.02 Own value (to<br />
be entered!)<br />
max.: 1000<br />
def.: 0.3<br />
Indicates the time for which the signal is considered permanent.<br />
2.154 MOP reference memory Unit: integer<br />
Relationship to<br />
parameter:<br />
Parameter manual:<br />
p. xy<br />
Transfer status:<br />
2<br />
min: 0 Own value (to<br />
be entered!)<br />
max.: 1<br />
def.: 0<br />
Defines whether the target value of the motor potentiometer is retained<br />
even after power outage.<br />
0 = deactivated<br />
1 = activated<br />
5.3.4 PID process controller<br />
This mode has to be selected in parameter 1,100,<br />
the target value source has to be selected in parameter 1,130,<br />
see also chapter 5.2.1, “Explanation of operating modes – preset speed”.<br />
3.050 PID proportional gain Unit:<br />
Relationship to<br />
parameter:<br />
1,100<br />
1,130<br />
Parameter manual:<br />
p. xy<br />
Transfer status:<br />
proportional share of PID controller<br />
2<br />
min: 0 own value (to<br />
be entered!)<br />
max.: 100<br />
def.: 1<br />
3.051 PID integral gain Unit: 1/s<br />
Relationship to<br />
parameter:<br />
1,100<br />
1,130<br />
Parameter manual:<br />
p. xy<br />
Transfer status:<br />
integral share of PID controller<br />
2<br />
min: 0 own value (to<br />
be entered!)<br />
max.: 100<br />
def.: 1