Parameters<br />

2.153 MOP response time Unit: s<br />

Relationship to<br />

parameter:<br />

Parameter manual:<br />

p. xy<br />

Transfer status:<br />

48 Operating manual <strong>FKO</strong><br />

2<br />

min: 0.02 Own value (to<br />

be entered!)<br />

max.: 1000<br />

def.: 0.3<br />

Indicates the time for which the signal is considered permanent.<br />

2.154 MOP reference memory Unit: integer<br />

Relationship to<br />

parameter:<br />

Parameter manual:<br />

p. xy<br />

Transfer status:<br />

2<br />

min: 0 Own value (to<br />

be entered!)<br />

max.: 1<br />

def.: 0<br />

Defines whether the target value of the motor potentiometer is retained<br />

even after power outage.<br />

0 = deactivated<br />

1 = activated<br />

5.3.4 PID process controller<br />

This mode has to be selected in parameter 1,100,<br />

the target value source has to be selected in parameter 1,130,<br />

see also chapter 5.2.1, “Explanation of operating modes – preset speed”.<br />

3.050 PID proportional gain Unit:<br />

Relationship to<br />

parameter:<br />

1,100<br />

1,130<br />

Parameter manual:<br />

p. xy<br />

Transfer status:<br />

proportional share of PID controller<br />

2<br />

min: 0 own value (to<br />

be entered!)<br />

max.: 100<br />

def.: 1<br />

3.051 PID integral gain Unit: 1/s<br />

Relationship to<br />

parameter:<br />

1,100<br />

1,130<br />

Parameter manual:<br />

p. xy<br />

Transfer status:<br />

integral share of PID controller<br />

2<br />

min: 0 own value (to<br />

be entered!)<br />

max.: 100<br />

def.: 1