Parameters<br />
1.054 Ramp section Unit: integer<br />
Relationship to<br />
parameter:<br />
1,050 to 1,053<br />
Parameter manual:<br />
p. xy<br />
Selection of used ramp pair<br />
Transfer status:<br />
42 Operating manual <strong>FKO</strong><br />
2<br />
min: 0 own value (to<br />
be entered!)<br />
max.: 6<br />
def.: 0<br />
0 = deceleration 1 (1.050) / acceleration 1 (1.051)<br />
1 = deceleration 2 (1.052) / acceleration 2 (1.053)<br />
2 = digital input 1 (false = ramp pair 1 / True = ramp pair 2)<br />
3 = digital input 2 (false = ramp pair 1 / true = ramp pair 2)<br />
4 = digital input 3 (false = ramp pair 1 / true = ramp pair 2)<br />
5 = digital input 4 (false = ramp pair 1 / true = ramp pair 2)<br />
6 = <strong>FKO</strong> Soft-PLC<br />
1.100 Control mode Unit: integer<br />
Relationship to<br />
parameter:<br />
1,130<br />
1,131<br />
2,051 to 2,057<br />
3,050 to 3,071<br />
Parameter manual:<br />
p. xy<br />
Selecting the operating mode.<br />
Transfer status:<br />
2<br />
min: 0 own value (to<br />
be entered!)<br />
max.: 4<br />
def.: 0<br />
After SW release (1,131) and hardware release, the drive control runs as<br />
follows:<br />
0 = frequency control mode, with the target value of the selected reference<br />
channel (1,130)<br />
1 = PID process control, with the target value of the PID process control<br />
(3,050–3,071)<br />
2 = preset speed mode, with the frequencies specified by parameters<br />
2,051–2,057<br />
3 = selection from <strong>FKO</strong> Soft-PLC