Commissioning<br />

4.4 Start-up steps<br />

Parameterising is possible prior to installation.<br />

Parameterisation can be performed before the drive<br />

control is installed in the engine.<br />

The drive control has a 24 V low-voltage input for this<br />

purpose, which can supply the electric system without<br />

requiring mains power.<br />

The start-up can be performed using a PC communication cable USB at<br />

plug M12 with integrated interface <strong>converter</strong> RS485/RS232 (article no.<br />

6UMZU0AA-K07324) or using the <strong>FKO</strong> manual control unit MMI with<br />

connection cable RJ11 at plug M12 (article no. 6UMZU0AA-K07323).<br />

Start-up using the PC:<br />

� Install the <strong>FKO</strong>pc software (you can obtain programming software from<br />

BRINKMANN free of charge).<br />

� Connect the PC to the M12 plug M1 with the optional connection cable.<br />

� Load or determine the motor data record (parameters 33,030 to 33,050);<br />

it may be necessary to optimise the speed control (parameters 34,100 to<br />

34,101).<br />

� Make the application settings (ramps, inputs, outputs, target values etc.).<br />

� Optional: Define an access level (1 – MMI, 2 – user, 3 – manufacturer).<br />

Please see also the quickstart guide in chapter 9.5.<br />

In order to ensure an ideal operating structure for the PC software, the<br />

parameters are classified into different access levels. There are the<br />

following levels:<br />

1. Manual control unit: – the drive control is programmed using the manual<br />

control unit<br />

2. User: – the basic parameters can be programmed into the drive control<br />

using the PC software<br />

3. Manufacturer: – an extended selection of parameters can be<br />

programmed into the drive control using the PC software<br />

34 Operating manual <strong>FKO</strong>

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!