26.10.2012 Views

Frequency converter FKO - Brinkmann Pumps

Frequency converter FKO - Brinkmann Pumps

Frequency converter FKO - Brinkmann Pumps

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Parameters<br />

Preset speed:<br />

In this operating mode, preset speed references are transferred to the<br />

motor control. There are 7 preset speeds (2,051 to 2,057) that are BCD<br />

coded and attached fixedly to digital inputs 1 to 3. These seven preset<br />

speeds can be released in three groups via the “preset speed mode”<br />

(2,050) parameter:<br />

0 = preset speed 1, 1 = preset speed 1 to 3, 2 = preset speed 1 to 7.<br />

DI 3 DI 2 DI 1 Selection Parameters Presetting<br />

0 0 0 Min. frequency 1.020 0 Hz<br />

0 0 1 preset speed 1 2.051 10 Hz<br />

0 1 0 preset speed 2 2.052 20 Hz<br />

0 1 1 preset speed 3 2.053 30 Hz<br />

1 0 0 preset speed 4 2.054 35 Hz<br />

1 0 1 preset speed 5 2.055 40 Hz<br />

1 1 0 preset speed 6 2.056 45 Hz<br />

1 1 1 preset speed 7 2.057 50 Hz<br />

Tab. 7: Logic table of fixed frequencies<br />

38 Operating manual <strong>FKO</strong>

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!