Parameters<br />
5.3 Application parameters<br />
5.3.1 Basic parameters<br />
1.020 Low speed Unit: Hz<br />
Relationship to<br />
parameter:<br />
1,150<br />
3,070<br />
Parameter manual:<br />
p. xy<br />
Transfer status:<br />
40 Operating manual <strong>FKO</strong><br />
2<br />
min: 0 own value (to<br />
be entered!)<br />
max.: 400<br />
def.: 0<br />
The low speed is the frequency provided by the drive control as soon as it<br />
released and no additional target value is pending.<br />
This frequency is not reached if<br />
a) acceleration is carried out while the drive is not moving.<br />
b) the frequency inverter is blocked. The frequency is then reduced to 0 Hz<br />
before it is blocked.<br />
c) the frequency inverter reverses (1,150). The revolving field is reversed<br />
at 0 Hz.<br />
d) the stand-by function (3,070) is active.<br />
1.021 High speed Unit: Hz<br />
Relationship to<br />
parameter:<br />
1,050<br />
1,051<br />
Parameter manual:<br />
p. xy<br />
Transfer status:<br />
2<br />
min: 5 own value (to<br />
be entered!)<br />
max.: 400<br />
def.: 50<br />
The high speed is the frequency produced by the inverter in dependence<br />
on the reference.<br />
1.050 Deceleration 1: Unit: s<br />
Relationship to<br />
parameter:<br />
1,021<br />
1,054<br />
Parameter manual:<br />
p. xy<br />
Transfer status:<br />
2<br />
min: 0,1 own value (to<br />
be entered!)<br />
max.: 1000<br />
def.: 5<br />
Deceleration 1 is the time that the inverter takes to brake to 0 Hz from the<br />
high speed (1,021).<br />
If the set deceleration time cannot be reached, the fastest possible<br />
deceleration time is implemented.