Parameters<br />
1.132 Start protect Unit: integer<br />
Relationship to<br />
parameter:<br />
1,131<br />
Parameter manual:<br />
p. xy<br />
Transfer status:<br />
44 Operating manual <strong>FKO</strong><br />
2<br />
min: 0 own value (to<br />
be entered!)<br />
max.: 1<br />
def.: 1<br />
Selection of the behaviour in response to enable software (parameter<br />
1,131).<br />
No effect if autostart was selected.<br />
0 = immediate start when high signal is received at start input of control<br />
release<br />
1 = start only in case of rising shoulder at start input of control release<br />
2 = digital input 1 (function active at high signal)<br />
3 = digital input 2 (function active at high signal)<br />
4 = digital input 3 (function active at high signal)<br />
5 = digital input 4 (function active at high signal)<br />
1.150 Rotational direction Unit: integer<br />
Relationship to<br />
parameter:<br />
1,131<br />
Parameter manual:<br />
p. xy<br />
Transfer status:<br />
Selecting the rotational direction specification<br />
2<br />
min: 0 own value (to<br />
be entered!)<br />
max.: 7<br />
def.: 0<br />
0 = dependent on target value (depending on the plus or minus sign of the<br />
target value: positive: forward; negative: backwards)<br />
1 = forwards only (rotational direction cannot be changed)<br />
2 = backwards only (rotational direction cannot be changed)<br />
3 = digital input 1 (0 V = forwards, 24 V = backwards)<br />
4 = digital input 2 (0 V = forwards, 24 V = backwards)<br />
5 = digital input 3 (0 V = forwards, 24 V = backwards)<br />
6 = digital input 4 (0 V = forwards, 24 V = backwards)<br />
7 = reference from <strong>FKO</strong> Soft-PLC