COMPLETE 08<br />

COMPLIANT TO IEC 60849<br />

Rear view PSS-60849 A<br />

<br />

<br />

<br />

MODEL NO.: PSS-60849A<br />

PROLINE COMPLETE08<br />

RCS AUDIO-SYSTEMS GMBH<br />

<br />

<br />

7 empty slots for mounting the relay cards PRC-008 B, PRC-108 A or<br />

PRC-408 A.<br />

Bus connector RS-485, 3 symmetrical audio inputs, input 1 also<br />

programmable as output, 1 symmetrical audio output.<br />

Extension connector for further slave devices in order to upgrade up to<br />

224 lines and for connection with the music switch panels PMS-024.<br />

Power supply connector 24 V and emergency power input, relay 0 for<br />

special functions.<br />

8 isolated alarm inputs, 2 isolated switch inputs, freely programmable.<br />

Connector for firmware update.<br />

3 optional module slots for installment of additional modules, e.g. textand<br />

signal memory PMM-132 A.<br />

Technical Data<br />

PSS-60849 A<br />

Speaker lines<br />

8 line, max. 600 W each<br />

Fire brigade call stations<br />

PFM-308 A (table microphone),<br />

PFM-330 A (wall microphone)<br />

Digital microphone stations PDM-208 A, PRM-108 A (monitored with PMO-400 A)<br />

Signal inputs<br />

3x LINE IN: 0dB / 775 mV, balanced<br />

Signal outputs<br />

1x LINE OUT: 0dB / 775 mV, balanced<br />

Switching output 1x switchable max. 2 A (relay 0)<br />

Text memory<br />

MP3 to CompactFlash-Card, 32 text or siren,<br />

monitored<br />

Display<br />

2-line display; LEDs<br />

Power supply inputs<br />

24 V and 24 V-emergency power supply monitored<br />

Power consumption<br />

approx. 8 W<br />

Dimensions (WxHxD); Weight 483 x 89 x 270 mm, 2 RU; approx. 3,3 kg<br />

Fire Brigade Microphone Station<br />

Description<br />

Various monitored microphones are available, according to<br />

IEC 60849:<br />

● PFM-308 A is a fire brigade table microphone with<br />

integrated monitoring, 8 buttons amongst which speaker<br />

lines, texts or siren 33404 can be selected according to the<br />

text or chime module.<br />

● PFM-330 A is a fire brigade wall microphone with integrated<br />

monitoring in one lockable steel cabinet. It has illuminated<br />

buttons for the text module, reset and all-call announcements.<br />

● PRM-108 A is a digital system microphone, which can be<br />

expanded through various module buttons. It is possible to<br />

optionally monitor it with a PMO-400 A.<br />

● PDM-208 A is a digital microphone with an LCD-display,<br />

which can be expanded through various module buttons. It<br />

is possible to optionally monitor it with a PMO-400 A.<br />

Fire Brigade Microphone Station . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PFM-308 A<br />