COMPLETE 08<br />
COMPLIANT TO IEC 60849<br />
Rear view PSS-60849 A<br />
<br />
<br />
<br />
MODEL NO.: PSS-60849A<br />
PROLINE COMPLETE08<br />
RCS AUDIO-SYSTEMS GMBH<br />
<br />
<br />
7 empty slots for mounting the relay cards PRC-008 B, PRC-108 A or<br />
PRC-408 A.<br />
Bus connector RS-485, 3 symmetrical audio inputs, input 1 also<br />
programmable as output, 1 symmetrical audio output.<br />
Extension connector for further slave devices in order to upgrade up to<br />
224 lines and for connection with the music switch panels PMS-024.<br />
Power supply connector 24 V and emergency power input, relay 0 for<br />
special functions.<br />
8 isolated alarm inputs, 2 isolated switch inputs, freely programmable.<br />
Connector for firmware update.<br />
3 optional module slots for installment of additional modules, e.g. textand<br />
signal memory PMM-132 A.<br />
Technical Data<br />
PSS-60849 A<br />
Speaker lines<br />
8 line, max. 600 W each<br />
Fire brigade call stations<br />
PFM-308 A (table microphone),<br />
PFM-330 A (wall microphone)<br />
Digital microphone stations PDM-208 A, PRM-108 A (monitored with PMO-400 A)<br />
Signal inputs<br />
3x LINE IN: 0dB / 775 mV, balanced<br />
Signal outputs<br />
1x LINE OUT: 0dB / 775 mV, balanced<br />
Switching output 1x switchable max. 2 A (relay 0)<br />
Text memory<br />
MP3 to CompactFlash-Card, 32 text or siren,<br />
monitored<br />
Display<br />
2-line display; LEDs<br />
Power supply inputs<br />
24 V and 24 V-emergency power supply monitored<br />
Power consumption<br />
approx. 8 W<br />
Dimensions (WxHxD); Weight 483 x 89 x 270 mm, 2 RU; approx. 3,3 kg<br />
Fire Brigade Microphone Station<br />
Description<br />
Various monitored microphones are available, according to<br />
IEC 60849:<br />
● PFM-308 A is a fire brigade table microphone with<br />
integrated monitoring, 8 buttons amongst which speaker<br />
lines, texts or siren 33404 can be selected according to the<br />
text or chime module.<br />
● PFM-330 A is a fire brigade wall microphone with integrated<br />
monitoring in one lockable steel cabinet. It has illuminated<br />
buttons for the text module, reset and all-call announcements.<br />
● PRM-108 A is a digital system microphone, which can be<br />
expanded through various module buttons. It is possible to<br />
optionally monitor it with a PMO-400 A.<br />
● PDM-208 A is a digital microphone with an LCD-display,<br />
which can be expanded through various module buttons. It<br />
is possible to optionally monitor it with a PMO-400 A.<br />
Fire Brigade Microphone Station . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PFM-308 A<br />