3. Two-channel sensor with cross-shorting test<br />
Cross-shorting as well as connections to DC 24 V and DC 0 V can be detected by using two<br />
independent clock signals on the homogeneous sensor. Only normally closed contacts<br />
should be used <strong>for</strong> safety related applications.<br />
DI1<br />
DI2<br />
DI3<br />
DI4<br />
.<br />
.<br />
.<br />
DI13<br />
DI14<br />
P1<br />
P2<br />
P1<br />
P2<br />
L+<br />
L-<br />
X14<br />
X12<br />
Fig.: two-channel sensor, homogeneous with clock<br />
4.7.2 Expansion module EAE1 … EAE10<br />
Digital inputs Per<strong>for</strong>mance Level Comment<br />
- Single-channel static signal -> auxiliary<br />
EAE1 … EAE10<br />
input<br />
- Two-channel static signal<br />
EAE1 … EAE10 PL e<br />
- Minimum one request/day<br />
- Fault detection only upon request<br />
EAE1 … EAE10 PL d - Less than one request/day<br />
- Single-channel with pulse<br />
EAE1 … EAE10 PL e<br />
- Minimum one request/day<br />
- Fault detection only upon request<br />
- Single-channel with pulse<br />
EAE1 … EAE10 PL d<br />
- Less than one request/day<br />
EAE1 … EAE10 PL e - Two-channel with 2 pulses<br />
HB-37350-810-01-10E-EN <strong>SMX</strong> installation manual.doc Page 24 of 24