3 Device types<br />
3.1 Module overview<br />
3.1.1 <strong>SMX</strong>10<br />
Type designation<br />
Device design<br />
Design of module with the following periphery:<br />
14 digital inputs<br />
2 Pulse outputs<br />
2 Relay outputs<br />
2 LOSIDE<br />
2 HISIDE<br />
2 Signal outputs<br />
1 Diagnostic and configuration interface<br />
1 Function button<br />
1 7-segment display<br />
1 Status-LED<br />
14 Status-LEDs <strong>for</strong> inputs<br />
2 Status-LEDs <strong>for</strong> pulse outputs<br />
2 Status-LEDs <strong>for</strong> relay outputs<br />
2 Status-LEDs <strong>for</strong> HISIDE<br />
1 Backplane bus interface<br />
Characteristics of the module:<br />
• Logic processing up to Pl e acc. to EN ISO 13849-1 or SIL 3 acc. to EN 61508<br />
• Open programmable small control system <strong>for</strong> up to 800 IL instructions<br />
• Logic diagram oriented programming<br />
• Pulse outputs <strong>for</strong> cross-shorting detection of digital input signals<br />
• Safety function of external contact monitoring <strong>for</strong> connected switchgear<br />
• Monitored relay outputs <strong>for</strong> safety relevant functions<br />
• Monitored HISIDE/LOSIDE outputs <strong>for</strong> safety relevant functions<br />
• CAN-communication in connection with the <strong>SMX</strong>5x <strong>for</strong> diagnose via backplane bus<br />
system<br />
Mounting on top hat rail<br />
HB-37350-810-01-10E-EN <strong>SMX</strong> installation manual.doc Page 8 of 8