Chapter 3<br />

Installation and Wiring<br />

Spacing Requirements<br />

Adequate air space must be provided around the system (module<br />

cluster). Minimum recommended clearances:<br />

• 15 mm (0.6 in.) above<br />

• 15 mm (0.6 in.) below<br />

• 2…3 mm (0.08…0.12 in.) between modules at ambient<br />

temperatures higher than 40 °C (104 °F).<br />

Mount the MSR57P Relay Follow these steps to mount the MSR57P relay to an EN50022 -35 x 7.5<br />

DIN rail.<br />

1. Hook the top slot over the DIN rail.<br />

2. Snap the bottom of the relay into position while pressing the<br />

relay down against the top of the rail.<br />

Slot<br />

DIN Rail<br />

Latch<br />

3. Attach end plates on each end of the DIN rail.<br />

To remove the relay from the DIN rail, use a flathead screwdriver to<br />

pull down the latch and lift the relay from the rail.<br />

Power Supply<br />

Requirements<br />

The external power supply must conform to the Directive 2006/95/EC<br />

Low Voltage, by applying the requirements of EN61131-2<br />

Programmable Controllers, Part 2 - Equipment Requirements and Tests<br />

and one of the following:<br />

• EN60950- SELV (<strong>Safe</strong>ty Extra Low Voltage)<br />

• EN60204 - PELV (Protective Extra Low Voltage)<br />

• IEC 60536 <strong>Safe</strong>ty Class III (SELV or PELV)<br />

• UL 508 <strong>Limited</strong> Voltage Circuit<br />

To meet EN60204 - PELV, 24V DC + 10% - 20% has to be supplied by<br />

a power supply that complies with IEC/EN60204 and IEC/EN 61558-1.<br />

32 Publication 440R-UM004A-EN-P - December 2008