Advantages of CITY MULTI two-pipe systems<br />

The advantages of the two-pipe CITY MULTI system become very obvious when it comes to installation. The illustration s<br />

below compare the minimum number of connections required for simultaneous cooling and heating system with four indoor<br />

units. The CITY MULTI system requires only 20 connections versus 58 for a three-pipe system. As the number of indoor units<br />

grow, so do the two-pipe installations savings, in terms of connections (refrigerant and electrical) as well as maintenance access.<br />

CITY MULTI<br />

Two-Pipe Heat<br />

Recovery System<br />

Outdoor Unit<br />

BC Controller<br />

Outdoor Unit<br />

OUTDOOR UNITS<br />

Indoor Units<br />

Refrigerant<br />

Distribution<br />

Units<br />

OTHER MANUFACTURERS SYSTEM<br />

BC Controller<br />

The BC Controller is the technological heart of the CITY MULTI<br />

R2-/WR2-Series. It works in unison with the outdoor unit to<br />

provide simultaneous cooling and heating, something no other<br />

two-pipe system can do.<br />

The Single BC Controller is<br />

connected to the outdoor unit<br />

by two refrigerant pipes, and<br />

to each indoor unit by a series<br />

of two pipes, depending on<br />

BC Controller<br />

the indoor unit count.<br />

The Main BC Controller and up<br />

to two optional Sub BC Controllers connect the outdoor<br />

unit to the system’s indoor units. A Single or Main BC Controller<br />

is required for each CITY MULTI R2-/WR2-Series installation.<br />

The BC Controller model and size selected depends on how<br />

many indoor units will be operated from each outdoor unit,<br />

your total capacity requirements, and your installation needs.<br />

Each set of ports supports up to 54,000 Btu/h of capacity.<br />

• Single BC Controller:<br />

Used when only one BC controller is required. For systems<br />

with up to 120,000 Btu/h nominal cooling capacity.<br />

• Main BC Controller:<br />

For systems with up to 288,000 Btu/h nominal cooling<br />

capacity and when use of Sub BC Controllers is desired.<br />

• Sub BC Controller:<br />

Used with a Main BC controller to connect additional<br />

indoor units. A maximum of two Sub BC Controllers can<br />

be connected to one Main BC Controller per system.<br />

Increased pipe length<br />

The R2-Series system offers flexibility and reduced costs<br />

for refrigerant piping. The system may have a maximum total<br />

length of refrigerant piping from 1,804 to 2,624 feet one way,<br />

depending on outdoor unit model.<br />

Refrigerant piping lengths<br />

Maximum feet<br />

Total length ..........................................................1,804 - 2,624<br />

- Maximum total length is dependent on the outdoor<br />

unit model and distance between BC controller.<br />

Farthest Indoor from Outdoor ............................541 (623 equivalent)<br />

Maximum length between outdoor<br />

and single/main BC controller ............................360<br />

Maximum length between single/main<br />

BC controller and indoor ...................................131-196<br />

Vertical differentials between units<br />

Indoor/outdoor (outdoor higher) .........................164*<br />

Indoor/outdoor (outdoor lower) ..........................131<br />

Indoor/BC controller (single/main) ......................49<br />

- Maximum length between single/main BC controller and<br />

indoor is dependent upon the vertical differential between<br />

the single/main BC controller and the indoor unit.<br />

Indoor/indoor .......................................................49<br />

Controller/Sub BC Controller ..............................49<br />

Maximum feet<br />

*Can be extended. Ask your local <strong>Mitsubishi</strong> Electric representative for more details.<br />