Mitsubishi CityMulti Catalog - Salvex
Mitsubishi CityMulti Catalog - Salvex
Mitsubishi CityMulti Catalog - Salvex
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
79 ˚F<br />
79 ˚F<br />
82 ˚F<br />
CENTRALIZED CONTROLLER GB-24<br />
ETHERNET<br />
GB-24<br />
PAC-SC51KUA<br />
DIDO Board<br />
Function<br />
Description<br />
Max No. of Indoor Units<br />
Up to 24 indoor units can be connected<br />
ON/OFF<br />
Operation Mode<br />
Temperature Setting<br />
Fan Speed Setting<br />
Air Flow Direction Setting<br />
Permit/Prohibit Function<br />
Indoor Return Air Temperature<br />
Error Indication<br />
Ventilation Interlock<br />
Schedule Operation<br />
External Input/Output<br />
Power Supply<br />
On/Off operation for a single group and batch operation<br />
Cool/Dry/Auto/Fan/ Heat/Setback.<br />
Auto mode is available with only R2 and WR2 systems<br />
Set temperature from 57˚ F - 87˚ F depending on operation mode and indoor unit<br />
Hi/Mid-2/Mid-1/Low/Auto<br />
Available fan speed settings depending on indoor unit<br />
Air flow angles: 100˚ - 80˚ - 60˚ - 40˚ and swing<br />
Air flow direction settings vary depending on indoor unit model<br />
Individual prohibit operations for each remote controller function<br />
(ON/OFF, Set Temperature, Operation Mode and Filter reset)<br />
Displays the measured return air temperature from each group<br />
Displays a 4 digit code and the affected unit address<br />
Allows the group to be interlocked with Lossnay unit<br />
Weekly schedule can be set by groups based on operation pattern<br />
*requires PC Monitoring (SW-Mon) and PC Scheduling (SW-Sch)<br />
Inputs: Level Signal-Batch Start/Stop, Batch Emergency Stop<br />
Outputs: Start/Stop Status, Error/Normal Status<br />
PAC-SC51KUA<br />
CONTROLS<br />
Dimensions - (W x D x H) 9-7/8" x 1-1/2" x 5-1/8"<br />
GB-24 Software Options (details on optional software on page 53)<br />
Pre-Licensed Software<br />
SW-Mon<br />
PC monitoring<br />
SW-Sch<br />
PC scheduling<br />
SW-Email Error email<br />
SW-Maint Online Maintenance Tool<br />
67