PKFY-P-N*MU-E SPECIFICATIONS<br />

Model Name<br />

PKFY-<br />

06NBMU-E<br />

PKFY-<br />

P08NBMU-E<br />

PKFY-<br />

P12NHMU-E<br />

PKFY-<br />

P15NHMU-E<br />

PKFY-<br />

P18NHMU-E<br />

PKFY-<br />

P24NKMU-E<br />

PKFY-<br />

P30NKMU-E<br />

Power Source<br />

208 / 230V, 1 Phase, 60Hz<br />

Cooling Capacity Btu/h *1 6,000 8,000 12,000 15,000 18,000 24,000 30,000<br />

Heating Capacity Btu/h *1 6,700 9,000 13,500 17,000 20,000 27,000 34,000<br />

Power<br />

Consumption<br />

Cooling W 30 40 60<br />

Heating W 30 40 60<br />

Current Cooling A 0.15 0.30 0.29 0.43<br />

Heating A 0.15 0.30 0.29 0.43<br />

External Finish Munsell No. 1.0Y 9.2 / 0.2<br />

Dimensions Height Inches 11-5/8 14-3/8<br />

Width Inches 32-1/8 35-3/8 46-1/16<br />

Depth Inches 8-7/8 9-13/16 11-5/8<br />

Net Weight Unit Pounds 22 29 46<br />

Heat Exchanger<br />

Cross Fin (Aluminum Plate Fin and Copper Tube)<br />

Fan Type x quantity Line Flow Fan x 1<br />

Airflow Rate *2 CFM 170-180-200-210 320-355-390 320-370-405 320-370-425 570-710 710-850<br />

Motor Type Single-phase Induction Motor Direct-driven DC Motor<br />

Motor Output W 8 30 56<br />

Air Filter<br />

Polypropylene Honeycomb<br />

Refrigerant Pipe<br />

Dimensions<br />

Low Pressure<br />

(Flare)<br />

High Pressure<br />

(Flare)<br />

Inches 1/2 5/8<br />

Inches 1/4 3/8<br />

Drain Pipe Dimension (I.D.) Inches 5/8<br />

Sound Pressure<br />

Levels *2<br />

Lo-Mid1-Mid2-Hi dB(A) 32-33-35-36 34-38-42 36-41-45 39-45 43-49<br />

*1 Cooling/Heating Capacity indicates the maximum value at operation under the following conditions:<br />

Cooling: Indoor: 80° F (27°C) DB / 67° F (19°C) WB; Outdoor 95° F (35°C) DB<br />

Heating: Indoor: 70° F (21°C) DB; Outdoor: 45° F (7°C) DB / 43° F (6°C) WB<br />

*2 Airflow rate/sound pressure levels are at Low-Mid1-Mid2-Hi, Low-Mid-Hi, or Low-Hi<br />

Ventilation Air: Providing sufficient ventilation air is an important part of very building design. ASHRAE Standard 62 provides the minimum air requirements. Also check local codes.<br />

INDOOR UNITS<br />

Specifications are subject to change.<br />

43<br />