Y-SERIES SPECIFICATIONS (continued)<br />
Power source<br />
Model Name<br />
Capacity (Nominal) *1<br />
Fan<br />
Compressor<br />
Refrigerant<br />
External finish<br />
Dimensions H x W x D<br />
Net Weight<br />
208/230V<br />
460V<br />
PUHY-P288TSJMU-A (-BS) *2 PUHY-P312TSJMU-A (-BS) *2 PUHY-P336TSJMU-A (-BS) *2 PUHY-P360TSJMU-A (-BS) *2<br />
With 2 PUHY-P144TJMU-A<br />
(-BS) *3<br />
With 1 PUHY-P72TJMU-A (-BS)<br />
and 2 PUHY-P120TJMU-A<br />
(-BS) *3<br />
With 1 PUHY-P96TJMU-A (-BS)<br />
and 2 PUHY-P120TJMU-A<br />
(-BS) *3<br />
With 1 PUHY-P96TJMU-A (-BS),<br />
1 PUHY-P120YJUM-A (-BS),<br />
and 1 PUHY-P144TJMU-A<br />
(-BS) *3<br />
PUHY-P288YSJMU-A (-BS) *2 PUHY-P312YSJMU-A (-BS) *2 PUHY-P336YSJMU-A (-BS) *2 PUHY-P360YSJMU-A (-BS) *2<br />
With 2 PUHY-P144YJMU-A<br />
(-BS) *3<br />
With 1 PUHY-P72YJMU-A (-BS)<br />
and 2 PUHY-P120YJMU-A<br />
(-BS) *3<br />
With 1 PUHY-P96YJMU-A (-BS)<br />
and 2 PUHY-P120YJMU-A<br />
(-BS) *3<br />
With 1 PUHY-P96YJMU-A (-BS),<br />
1 PUHY-P120YJMU-A (-BS), and<br />
1 PUHY-P144YJMU-A (-BS) *3<br />
208 / 230V, 3-Phase, 60Hz / 460V, 3-Phase, 60Hz<br />
BTU / h 288,000 312,000 336,000 360,000<br />
Cooling<br />
kW 25.59 *3 25.82 *3 28.58 *3 31.18 *3<br />
A 78.9 / 71.3 / 35.6 *3 79.6 / 72.0 / 36.0 *3 88.1 / 79.7 / 39.8 *3 96.1 / 86.9 / 43.4 *3<br />
BTU / h 320,000 350,000 378,000 403,000<br />
Heating<br />
kW 26.94 *3 27.3 *3 30.24 *3 32.99 *3<br />
A 83.0 / 75.1 / 37.5 *3 84.1 / 76.1 / 38.0 *3 93.2 / 84.3 / 42.1 *3 101.7 / 92.0 / 46.0 *3<br />
Type x Quantity<br />
Refer to PUHY-P96TJMU-A<br />
Air flow rate cfm<br />
Refer to PUHY-P72TJMU-A Refer to PUHY-P96TJMU-A (-BS) / PUHY-P120TJMU-A (-BS)<br />
Direct-drive<br />
Refer to PUHY-P144TJMU-A (-BS) / PUHY-P120TJMU-A (-BS) (-BS) / PUHY-P120TJMU-A (-BS) / PUHY-P144TJMU-A (-BS)<br />
INVERTER kW (-BS) and PUHY-P144YJMU-A and PUHY-P72YJMU-A (-BS) and PUHY-P96YJMU-A (-BS) and PUHY-P96YJMU-A (-BS)<br />
Motor Output<br />
(-BS) Specifications on page 23 / PUHY-P120YJMU-A (-BS) / PUHY-P120YJMU-A (-BS) / PUHY-P120YJMU-A (-BS)<br />
External static pressure<br />
Specifications on page 23 Specifications on page 23 / PUHY-P144YJMU-A (-BS)<br />
Specifications on page 23<br />
Type x Quantity<br />
Operating Range 7% to 100% 4% to 100% 7% to 100% 6% to 100%<br />
Direct-drive<br />
INVERTER kW<br />
Motor output<br />
Crankcase<br />
heater<br />
Lubricant<br />
Type<br />
Height<br />
Width<br />
Depth<br />
W<br />
In.<br />
In.<br />
In.<br />
Pounds<br />
Refer to PUHY-P144TJMU-A<br />
(-BS) and PUHY-P144YJMU-A<br />
(-BS) Specifications on page 23<br />
Refer to PUHY-P72TJMU-A<br />
(-BS) / PUHY-P120TJMU-A (-BS)<br />
and PUHY-P72YJMU-A (-BS)<br />
/ PUHY-P120YJMU-A (-BS)<br />
Specifications on page 23<br />
Refer to PUHY-P96TJMU-A<br />
(-BS) / PUHY-P120TJMU-A (-BS)<br />
and PUHY-P96YJMU-A (-BS)<br />
/ PUHY-P120YJMU-A (-BS)<br />
Specifications on page 23<br />
Refer to PUHY-P96TJMU-A<br />
(-BS) / PUHY-P120TJMU-A (-BS)<br />
/ PUHY-P144TJMU-A (-BS)<br />
and PUHY-P96YJMU-A (-BS)<br />
/ PUHY-P120YJMU-A (-BS)<br />
/ PUHY-P144YJMU-A (-BS)<br />
Specifications on page 23<br />
Sound pressure level (measured in<br />
anechoic room)<br />
dB(A) 64.0 64.5 65.0<br />
High Pressure Protection<br />
High pressure sensor, High pressure switch<br />
Protection devices Compressor / Fan<br />
Over-heat protection / Thermal switch<br />
Inverter<br />
Overheat and Overcurrent Protection<br />
Refrigerant Pipe<br />
Dimensions<br />
Indoor unit<br />
connectable<br />
Operating Temperature<br />
Range<br />
Low Pressure<br />
(Brazed)<br />
In. 1-3/8 1-5/8<br />
High Pressure<br />
(Brazed)<br />
In. 3/4<br />
Total capacity<br />
50 to 130% of outdoor unit capacity<br />
Model / Quantity P06-P96 / 2 to 50<br />
Cooling D.B. *Outdoor: 23 to 115° F<br />
Heating W.B. Outdoor: -4 to +60° F<br />
OUTDOOR UNITS<br />
*1 Rating Conditions: *1 Cooling: Indoor: 80˚F (27˚C) DB / 67˚F (19˚C) WB;<br />
Outdoor: 95˚F (35˚C) DB. Heating: Indoor: 70˚F (21˚C) DB;<br />
Outdoor: 47˚F (8˚C) DB / 43˚F (6˚C) WB.<br />
*2 Twinning Kit is required for combining two or three individual outdoor units in the field<br />
for PUHY-P-T(S)SJHMU combined systems.<br />
*3 Each individual outdoor unit requires a separate electrical connection.<br />
Reference electrical data for each individual outdoor unit.<br />
-BS indicates Seacoast Protection option.<br />
LIMITED WARRANTY | Seven-year warranty on compressor. One-year warranty on parts.<br />
See our website for details on specific additional application installation coverage.<br />
Specifications are subject to change.<br />
** For details on extended ambient cooling operation range down to -10 FDB see<br />
Low Ambient Cooling section.<br />