PWFY-P-NMU-E-AU/BU SPECIFICATIONS<br />
Model Name PWFY-P36NMU-E-AU PWFY-P72NMU-E-AU PWFY-P36NMU-E-BU<br />
Power Source<br />
208/230V, 1-phase, 60Hz<br />
Cooling Capacity *1 Btu/h 36,200 72,000 -<br />
Heating Capacity *1 Btu/h 39,900 79,800 39,900<br />
Power<br />
Consumption<br />
Current<br />
External Finish<br />
Cooling W 15 N/A<br />
Heating W 15 2,480<br />
Cooling A 0.072 / 0.065 N/A<br />
Heating A 0.072 / 0.065 12.30 /11.12<br />
Galvanized-steel Sheet<br />
Height In. 31-1/2<br />
Dimensions<br />
Width In. 17-3/4<br />
Depth In. 11-13/16<br />
Net Weight Unit Pounds 78 84 133<br />
Operating Inlet Water<br />
Temp. Range<br />
Cooling 50° F to 95° F -<br />
Heating 50° F to 105° F 50° F to 160° F<br />
Circulating Water Operation Volume Range GPM (L/m) 3-9 (10-35) 5-18 (20-72) 3-9 (10-35)<br />
Circulating Water Design Pressure MPa (psi) 1 (145)<br />
Water Piping<br />
Dimensions<br />
Inlet In. 3/4 FPT 1 FPT 3/4 FPT<br />
Outlet In. 3/4 FPT 1 FPT 3/4 FPT<br />
Refrigerant Pipe<br />
Dimensions<br />
Low Pressure (Brazed) In. 5/8 3/4 5/8<br />
High Pressure (Brazed) In. 3/8 3/8 3/8<br />
Drainpipe Dimensions (O.D.) In. 1-1/4<br />
Sound Pressure Levels dB(A) 29 44<br />
Connectable Outdoor Units<br />
PURY-P72~240T/Y(S)HMU (-BS),<br />
PURY-P72~288T/Y(S)JMU (-BS),<br />
PQRY-P72~240T/Y(S)HMU (-BS),<br />
PUHY-P72~P360T/Y(S)HMU (-BS),<br />
PUHY-P72~360T/Y(S)JMU (-BS),<br />
PQHY-P72~360T/Y(S)HMU (-BS)<br />
PURY-P72~240T/Y(S)HMU (-BS),<br />
PURY-P72~288T/Y(S)JMU (-BS),<br />
PQRY-P72~240T/Y(S)HMU (-BS)<br />
*1 Cooling/Heating Capacity indicates the maximum value at operation under the following conditions:<br />
Cooling: Inlet water temperature : 74° F; Outdoor: 95° F (35°C) DB; Water flow rate: 9.25 GPM<br />
Heating: Inlet water temperature: 86° F (30°C); Outdoor: 47° F (8°C) DB / 43° F (6°C) WB; Water flow rate: 9.25 GPM<br />
*2 Airflow rate/sound pressure levels are at Low-Mid1-Mid2-Hi, Low-Mid-Hi, or Low-Hi<br />
Ventilation Air: Providing sufficient ventilation air is an important part of very building design. ASHRAE Standard 62 provides the minimum air requirements. Also check local codes.<br />
Specifications are subject to change.<br />
WATER HEATING<br />
PURY-P120YHMU-A<br />
BC CONTROLLER<br />
PWFY-P38NMU-E-BU<br />
PWFY-P36NMU-E-BU<br />
PWFY-P36NMU-E-BU PEFY-P15NMHU-E PEFY-P24NMSU-E<br />
Water Supply<br />
Cold Water Tank<br />
Hot Water Tank<br />
For Cooling<br />
(AHU, FCU, etc)<br />
For Heating<br />
(AHU, FCU,<br />
Floor Heating, etc)<br />
Water Supply<br />
For Sanitary Use<br />
(Shower, Bath, etc)<br />
39