29.08.2014 Views

Mitsubishi CityMulti Catalog - Salvex

Mitsubishi CityMulti Catalog - Salvex

Mitsubishi CityMulti Catalog - Salvex

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

PCFY SPECIFICATIONS<br />

Model Name PCFY-P15NKMU-E PCFY-P24NKMU-E PCFY-P30NKMU-E PCFY-P36NKMU-E<br />

Power Source<br />

208 / 230V, 1 Phase, 60Hz<br />

Cooling Capacity Btu/h *1 15,000 24,000 30,000 36,000<br />

Heating Capacity Btu/h *1 17,000 27,000 34,000 40,000<br />

Power Consumption Cooling W 30 40 90 110<br />

Heating W 30 40 90 110<br />

Current Cooling A 0.35 0.41 0.83 0.97<br />

Heating A 0.35 0.41 0.83 0.97<br />

External Finish Munsell No. 6.4Y 8.9 / 0.4<br />

Dimensions Height Inches 9-1/16<br />

Width Inches 37-13/16 50-3/8 63<br />

Depth Inches 26-3/4<br />

Net Weight Unit Pounds 53 71 79 84<br />

Heat Exchanger<br />

Cross Fin (Aluminum Plate Fin and Copper Tube)<br />

Fan Type x quantity Sirocco Fan x 2 Sirocco Fan x 3 Sirocco Fan x 4<br />

Airflow Rate *2 CFM 353-388-424-459 494-530-565-636 703-777-883-989 742-847-953-1,095<br />

Motor Type<br />

Direct-driven DC Motor<br />

Motor Output W 90 95 160<br />

Air Filter<br />

Polypropylene Honeycomb<br />

Refrigerant Pipe<br />

Dimensions<br />

Low Pressure (Flare) Inches 1/2 5/8<br />

High Pressure (Flare) Inches 1/4 3/8<br />

Drain Pipe Dimension (O.D.) Inches 1<br />

Sound Pressure<br />

Levels<br />

Lo-Mid1-Mid2-Hi dB(A) 29-32-34-36 31-33-35-37 34-37-40-43 36-39-42-44<br />

*1 Cooling/Heating Capacity indicates the maximum value at operation under the following conditions:<br />

Cooling: Indoor: 80° F (27°C) DB / 67° F (19°C) WB; Outdoor 95° F (35°C) DB<br />

Heating: Indoor: 70° F (21°C) DB; Outdoor: 45° F (7°C) DB / 43° F (6°C) WB<br />

*2 Airflow rate/sound pressure levels are at Low-Mid1-Mid2-Hi.<br />

Ventilation Air: Providing sufficient ventilation air is an important part of very building design. ASHRAE Standard 62 provides the minimum air requirements. Also check local codes.<br />

INDOOR UNITS<br />

Specifications are subject to change.<br />

51<br />

51

Hooray! Your file is uploaded and ready to be published.

Saved successfully!