PLFY-P-NCMU-E SPECIFICATIONS<br />

Model Name PLFY-P08NCMU-E PLFY-P12NCMU-E PLFY-P15NCMU-E<br />

Power Source<br />

208 230V, 1-phase, 60Hz<br />

Cooling Capacity Btu/h *1 8,000 12,000 15,000<br />

Heating Capacity Btu/h *1 9,000 13,500 17,000<br />

Power Consumption<br />

Current<br />

Cooling W 50 60<br />

Heating W 50 60<br />

Cooling A 0.23 0.28<br />

Heating A 0.23 0.28<br />

External Finish (Munsell No.) Grille: White (6.4Y 8.9/0.4)<br />

Height Inches 8-3/16<br />

Dimensions<br />

Width Inches 22-7/16<br />

Depth Inches 22-7/16<br />

Net Weight *2 Unit/Panel Pounds 34/7 37/7<br />

Heat Exchanger<br />

Cross Fin (Aluminum Plate Fin and Copper Tube)<br />

Type x Quantity Turbo Fan x 1<br />

Fan<br />

Airflow Rate *3 CFM 280-320-350 320-350-390<br />

Motor Type<br />

Single-phase Induction Motor<br />

Motor Output kW 0.015 0.020<br />

Air Filter<br />

Polypropylene Honeycomb<br />

Refrigerant Pipe Dimensions<br />

Low Pressure (Flare) Inches 1/2<br />

High Pressure (Flare) Inches 1/4<br />

Condensate Lift Mechanism (Standard) Inches 19-11/16<br />

Drain pipe Dimension (O.D.) Inches 1-1/4<br />

Sound Pressure Levels (As Measured<br />

in an Anechoic Room) *3<br />

(Low-Mid-High) dB(A) 29-32-38 30-34-39 31-35-40<br />

Note:<br />

*1 Cooling / Heating capacity indicates the maximum value at operation under the following conditions:<br />

Cooling: Indoor: 80˚F (27˚C) DB / 67˚F (19˚C) WB; Outdoor: 95˚F (35˚C) DB<br />

Heating: Indoor: 70˚F (21˚C) DB; Outdoor: 47˚F (8˚C) DB / 43˚F (6˚C) WB<br />

*2 Net weight is shown for unit / grille<br />

*3 Airflow rate / sound pressure levels are at (Low-Mid-High).<br />

INDOOR UNITS<br />

Ventilation Air: Providing sufficient ventilation air is an important part of every building design. ASHRAE Standard 62 provides the minimum ventilation air requirements. Also check local codes.<br />

Specifications are subject to change.<br />