PLFY-P-NCMU-E SPECIFICATIONS<br />
Model Name PLFY-P08NCMU-E PLFY-P12NCMU-E PLFY-P15NCMU-E<br />
Power Source<br />
208 230V, 1-phase, 60Hz<br />
Cooling Capacity Btu/h *1 8,000 12,000 15,000<br />
Heating Capacity Btu/h *1 9,000 13,500 17,000<br />
Power Consumption<br />
Current<br />
Cooling W 50 60<br />
Heating W 50 60<br />
Cooling A 0.23 0.28<br />
Heating A 0.23 0.28<br />
External Finish (Munsell No.) Grille: White (6.4Y 8.9/0.4)<br />
Height Inches 8-3/16<br />
Dimensions<br />
Width Inches 22-7/16<br />
Depth Inches 22-7/16<br />
Net Weight *2 Unit/Panel Pounds 34/7 37/7<br />
Heat Exchanger<br />
Cross Fin (Aluminum Plate Fin and Copper Tube)<br />
Type x Quantity Turbo Fan x 1<br />
Fan<br />
Airflow Rate *3 CFM 280-320-350 320-350-390<br />
Motor Type<br />
Single-phase Induction Motor<br />
Motor Output kW 0.015 0.020<br />
Air Filter<br />
Polypropylene Honeycomb<br />
Refrigerant Pipe Dimensions<br />
Low Pressure (Flare) Inches 1/2<br />
High Pressure (Flare) Inches 1/4<br />
Condensate Lift Mechanism (Standard) Inches 19-11/16<br />
Drain pipe Dimension (O.D.) Inches 1-1/4<br />
Sound Pressure Levels (As Measured<br />
in an Anechoic Room) *3<br />
(Low-Mid-High) dB(A) 29-32-38 30-34-39 31-35-40<br />
Note:<br />
*1 Cooling / Heating capacity indicates the maximum value at operation under the following conditions:<br />
Cooling: Indoor: 80˚F (27˚C) DB / 67˚F (19˚C) WB; Outdoor: 95˚F (35˚C) DB<br />
Heating: Indoor: 70˚F (21˚C) DB; Outdoor: 47˚F (8˚C) DB / 43˚F (6˚C) WB<br />
*2 Net weight is shown for unit / grille<br />
*3 Airflow rate / sound pressure levels are at (Low-Mid-High).<br />
INDOOR UNITS<br />
Ventilation Air: Providing sufficient ventilation air is an important part of every building design. ASHRAE Standard 62 provides the minimum ventilation air requirements. Also check local codes.<br />
Specifications are subject to change.<br />
47