2.2: Specifications<br />

<br />

Power Supply<br />

• Range: Universal, (90 to 400)VAC @50/60Hz or (100 to 370)VDC<br />

• Power Consumption: 16 VA Maximum<br />

Voltage Inputs (Measurement Category III)<br />

(For Accuracy Specifications, see Section 2.4.)<br />

• Absolute Maximum Range: Universal, Autoranging:<br />

Phase to Reference (Va, Vb, Vc, to VRef): (20 to 576)VAC<br />

Phase to Phase (Va to Vb, Vb to Vc, Vc to Va): (0-721)VAC<br />

• Supported hookups: 3 Element Wye, 2.5 Element Wye, 2 Element Delta,<br />

4 Wire Delta<br />

• Input Impedance: 1M Ohm/Phase<br />

• Burden: 0.36VA/Phase Max at 600V, 0.014VA at 120V<br />

• Pickup Voltage: 20VAC<br />

• Connection: 7 pin 0.400” Screw Terminal Block<br />

AWG#12 - 26/(0.129-3.31)mm 2<br />

• Fault Withstand: Meets IEEE C37.90.1 (Surge Withstand Capability)<br />

• Reading: Programmable Full Scale to any PT Ratio<br />

Current Inputs<br />

(For Accuracy Specifications, see Section 2.4.)<br />

• Class 10: 5A Nominal, 10A Maximum<br />

• Class 2: 1A Nominal, 2A Maximum<br />

• Burden: 0.005VA Per Phase Max at 11 Amps<br />

• Pickup Current: 0.1% of Nominal (0.2% of Nominal if using current only mode,<br />

that is, there is no connection to the voltage inputs.)<br />

• Connections: Screw terminal - #6-32 screws (Diagram 4.1)<br />

• Fault Withstand: 20A/10sec., 60A/3sec., 100A/1sec.<br />

• Reading: Programmable Full Scale to any CT Ratio<br />

<br />

Isolation<br />

• All Inputs and Outputs are galvanically isolated and tested to 2500VAC<br />

e Electro Industries/GaugeTech Doc #: E149721 2-4