Dimensioning<br />
Average heating excess temperature for standard floor coverings<br />
Limit curve for<br />
edge areas 15 K<br />
Heat flow density in W/m 2<br />
Limit curve for living<br />
areas 9 K<br />
RI = 0.0 – 0.02 (m 2 .K)/W no covering or tiles<br />
RI = 0.05 (m 2 .K)/W parquet, Melan (melamine resin) and PVC<br />
RI = 0.10 (m 2 .K)/W carpet<br />
RI = 0.15 (m 2 .K)/W deep pile carpet<br />
Excess temperature (K)<br />
Average heating low temperature for room air conditioning<br />
5) Calculation of the flow temperature:<br />
Cooling capacity in W/m 2<br />
t VL<br />
t i<br />
t mH<br />
σ<br />
Example:<br />
Flow temperature (°C)<br />
Room internal temperature (°C)<br />
Heating water excess<br />
temperature (°K)<br />
Temperature Difference<br />
(flow – return flow temperature)<br />
Heating water excess temperature:<br />
t mH<br />
= 18.5 K<br />
Room temperature:<br />
t i<br />
= 20 °C<br />
Temperature Difference:<br />
σ = 5 K<br />
Flow temperature:<br />
t VL<br />
= t i<br />
+ t<br />
σ<br />
mH<br />
+ = 20 + 18.5 +<br />
5<br />
= 41 (°C)<br />
2 2<br />
6) Calculation of the temperature<br />
difference for all other heating circuits<br />
As with the standard room the heating water<br />
excess temperature is calculated using the<br />
specific heating requirement and the pipe<br />
spacing.<br />
The temperature difference is calculated<br />
using this heating water excess temperature<br />
and flow temperature.<br />
Low temperature (K)<br />
7) Border zones<br />
If the heating requirement is not enough<br />
using the maximum floor temperature of<br />
29 °C and the minimum pipe installation<br />
spacing, the calculation for peripheral<br />
zones is required. The calculation uses<br />
a maximum floor temperature of 35 °C in<br />
the peripheral zones to reach the required<br />
heating output. If the minimum pipe spacing<br />
of 100 mm is not sufficient, then flow<br />
temperature is increased for all rooms.<br />
The <strong>system</strong> limits for the design are to<br />
follow.<br />
This flow temperature is valid for all heating<br />
circuits. To apply the correct heat output<br />
to each heating circuit the temperature<br />
difference (flow-return temperature<br />
difference) is varied.<br />
t VL<br />
t i<br />
t mH<br />
σ<br />
Flow temperature (°C)<br />
Room temperature (°C)<br />
Heating water excess<br />
temperature (°K)<br />
Temperature difference<br />
(flow- return temperature difference)<br />
8<br />
Room heating and cooling for floors, walls and ceilings