<strong>HERZ</strong> Distributor Engineering<br />
Control station ready for<br />
connection, <strong>HERZ</strong> compact floor<br />
Control station ready for connection of<br />
3 – 12 heating circuits for surface heating<br />
and two radiators. The flow temperature<br />
for the underfloor heating is mechanically<br />
controlled by a temperature limiter.<br />
Including circulator pump for underfloor<br />
heating and control of heating circuits.<br />
Differential control by means of mechanical<br />
overflow valve. Two multi-function valves<br />
guarantee the flushing of the underfloor<br />
heating circuits and the draining and<br />
bleeding. The valves are also equipped<br />
with a temperature dial which indicates flow<br />
and return temperatures. All electrical parts<br />
are mounted in a splash-proof switch box<br />
(IP54).<br />
The control station is mounted in a<br />
distributor cabinet made of galvanized<br />
steel sheet. The front door and front frame<br />
are white powder coated (RAL 9003) and<br />
shut by means of bolts. A cabinet door with<br />
cylinder lock is available upon request.<br />
The connection of the supply pipes for the<br />
control station is located on the right hand<br />
side with an external thread 1" (G). It is<br />
for direct connection to the <strong>HERZ</strong> plastic<br />
pipe connections 1 6198 xx or the <strong>HERZ</strong><br />
compression adapter 1 6273 01.<br />
The pipe connection for non-regulated<br />
heating circuits and surface heating is<br />
accessed from below. The distributions<br />
are supplied with G 3/4 external threads<br />
(eurocone). The connection with the pipe<br />
connections is carried out using <strong>HERZ</strong><br />
compression adapters or <strong>HERZ</strong> plastic pipe<br />
connections. We recommend <strong>HERZ</strong> plastic<br />
angle pipe sleeves 3 F110 0x to insert the<br />
pipes into the control station.<br />
The integrated switch box is to be<br />
connected with a power supply of 230 V ~,<br />
50 Hz (AC) IP54. All necessary electrical<br />
cables of the control station are already<br />
mounted and tested. The connection is only<br />
to be done by authorised staff.<br />
The multi-function valves serve to flush<br />
the entire station or single heating circuits.<br />
These valves are intended for flushing and<br />
can be mounted underneath the cover<br />
using a 1 ¼" external thread or a 1" female<br />
thread. The flow or return temperature is<br />
displayed at the hand wheels.<br />
An additional electrical safety thermostat<br />
switches the pump off as soon as it reaches<br />
excess temperature.<br />
Maximum operating temperature 110 °C<br />
Minimum operating temperature - 25 °C<br />
with glycol-based frost protection of<br />
maximum 45%<br />
Maximum operating pressure 10 bar<br />
Electrical connection: AC 230 V~, 50 Hz.<br />
Differential pressure, factory setting:<br />
Set point of 1<br />
Differential pressure can be set:<br />
Set range 0.5 - 5<br />
Heating water quality according to ÖNORM<br />
H5195 or VDI guideline 2035.<br />
Number of pipe connections: 3-12,<br />
<strong>HERZ</strong> order number 3 F533 xx<br />
Control station ready for connection<br />
230 V~, 50 Hz,<br />
As previously described however without<br />
radiator distributor, number of pipe<br />
connections: 3 – 12,<br />
<strong>HERZ</strong> order number 3 F532 xx<br />
Normal<br />
operation<br />
Rinsing of<br />
heating circuit<br />
Rinsing of<br />
<strong>system</strong><br />
In order to control the room temperature<br />
of the corresponding heating circuits, a<br />
distributor is installed in the switch box<br />
which is wired with the actuators and<br />
the <strong>HERZ</strong> distributor circulating pump.<br />
The setting of the room thermostats with<br />
the corresponding heating circuits at the<br />
distributor is done during the installation<br />
of the <strong>system</strong>s. The power supply of the<br />
control station should be 1 ~ 230 V, 50 Hz<br />
www.herz-armaturen.com 39