<strong>HERZ</strong> Control<br />

<strong>HERZ</strong> Thermal actuators<br />

1 7710 51 <strong>HERZ</strong> Thermal actuator with<br />

relieve contact<br />

Closed without current, can be switched<br />

over to open without current,<br />

operating voltage 24 V,<br />

thread connection M 28 x 0.5.<br />

The relieve contact signals the <strong>system</strong><br />

status or activates a pump.<br />

1 7710 00 <strong>HERZ</strong> Thermal actuator<br />

Closed without current, can be switched<br />

over to open without current,<br />

Operating voltage 230 V,<br />

thread connection M 28 x 0.5<br />

1 7710 01 <strong>HERZ</strong> Thermal actuator<br />

Closed without current, can be switched<br />

over to open without current,<br />

operating voltage 24 V,<br />

thread connection M 28 x 0.5<br />

1 7710 80 <strong>HERZ</strong> Thermal actuator<br />

Closed without current, can be switched<br />

over to open without current,<br />

operating voltage 230 V,<br />

thread connection M 30 x 0.5<br />

1 7710 81 <strong>HERZ</strong> Thermal actuator<br />

Closed without current, can be switched<br />

over to open without current,<br />

operating voltage 24 V,<br />

thread connection M 30 x 0.5<br />

1 7711 18 <strong>HERZ</strong> Thermal actuator for<br />

continuous regulating<br />

Thermal electric continuous drive, 3 lead<br />

connection cable,<br />

operating voltage 24 V =,<br />

control voltage 0-10 V =,<br />

thread connection M 30 x 0.5<br />

1 7710 50 <strong>HERZ</strong> Thermal actuator with<br />

relieve contact<br />

Closed without current, can be switched<br />

over to open without current,<br />

operating voltage 230 V,<br />

thread connection M 28 x 0.5.<br />

The relieve contact signals the <strong>system</strong><br />

status or activates a pump.<br />

1 7710 55 Relieve contact<br />

For later installation with thermal actuator<br />

Characteristic<br />

The thermal actuator is activated by an<br />

external electric contact e.g. from a room<br />

thermostat and opens or shuts the valve.<br />

The actuating movement is achieved with an<br />

electrically heated expansion element.<br />

When the heating current is switched off, the<br />

actuator shuts or opens the valve.<br />

The <strong>HERZ</strong> thermal actuator is maintenance<br />

free and works silently.<br />

1 7990 00 Herz DDC actuator drive<br />

Thermal electric continuous drive, 3 lead<br />

Connection cable,<br />

operating voltage 24 V,<br />

Control voltage 0-10V DC<br />

Electric resistance100 kΩ<br />

For use with <strong>HERZ</strong> RTC-2 room temperature<br />

controller<br />

1 7790 00 <strong>HERZ</strong> DDC actuator drive<br />

Thermo-electronic continuous drive,<br />

3-conductor<br />

Connection cable, operating voltage 24 V,<br />

driving voltage 0-10 V DC<br />

electric resistance10 kΩ<br />

For use with <strong>HERZ</strong> RTC-2 room temperature<br />

controller<br />

Functioning principle<br />

The actuator drive contains an electrically<br />

heated expansion element. The lift is<br />

directly transmitted to the valve.<br />

While the actuator drive is under voltage<br />

(24 V) the expansion element is heated to<br />

operating temperature within 2 minutes and<br />

can then be operated.<br />

By means of an external electric signal of<br />

0-10 V from a control device, the actuator<br />

drive is moved to the appropriate position.<br />

For a movement of 1 mm lift the actuator<br />

drive takes approximately 30 seconds.<br />

The closing operation is done in<br />

synchronisation with the opening. The<br />

expansion element cools down and the<br />

valve is closed using elastic force.<br />

The actuator drive is maintenance-free and<br />

works silently.<br />

www.herz-armaturen.com 35