With thermal reset<br />

To keep the room temperature fluctuations<br />

low, the membrane sensor is heated up in<br />

combination with a thermal resistor. The<br />

interacting maximum excess temperature<br />

of 0.5 K is greater then the switching<br />

difference. Therefore the thermostat<br />

independently switches on and off even<br />

if the room temperature is constant. If the<br />

room temperature matches the preset value<br />

the on and off impulses are equally long<br />

(Switching on proportion = 0.5)<br />

When the room temperature increases the<br />

switching on impulse is shorter and the<br />

switching off impulse longer. Consequently<br />

a continuous P regulating is achieved with<br />

a P-range of Xp = 3 K and a maximum and<br />

constant control difference of Xp/2. With the<br />

impulse modulation the room temperature<br />

changes to the same value as it does<br />

with a switching period (10 minutes On,<br />

10 minutes Off). As a result the temperature<br />

fluctuation is only 0.1…0.5 K depending on<br />

the time constant.<br />

Order no. 3 F791 00 230 V~, 50 Hz.<br />

Order no. 3 F791 01 24 V<br />

Order no. 3 F791 00 230 V~, 50 Hz.<br />

With signal lamp<br />

Order no. 3 F791 00 230 V~, 50 Hz.<br />

With signal lamp and resistor for faster<br />

response time,<br />

Switching differential at 20 °C = 0.4 °K<br />

Electronic room thermostat for floor<br />

heating<br />

For controlling the room temperature<br />

via a switch for comfort. Night reduction<br />

operation via an external time switch.<br />

Temperature range 5 °C to 50 °C<br />

Switching differential at 20 °C = 0.5 °K<br />

Triac output maximum 15 W<br />

Protection category IP30<br />

Temperature sensor for floor heating<br />

Can be used as a temperature limiter for the<br />

control of floor heating.<br />

Length 3 m<br />

Order no. 3 F790 06<br />

Set with electronic room thermostat<br />

Order no. 3 F792 04 230 V<br />

Order no. 3 F792 05 24 V<br />

Electronic room thermostat<br />

<strong>HERZ</strong> control<br />

Displays the room temperature digitally<br />

and the operation mode for controlling the<br />

room temperature or the floor temperature in<br />

conjunction with a temperature sensor.<br />

With thermal night time temperature<br />

decrease<br />

The membrane is heated up in combination<br />

with a heat resistor to decrease the room<br />

temperature. Consequently the temperature<br />

level in the housing is approximately 5 K<br />

higher and the controller reacts with a<br />

corresponding room temperature decrease.<br />

The night time temperature decrease can<br />

be activated with an external timer.<br />

“BELUX” mechanical room thermostat<br />

Room temperature – target value is<br />

adjustable mechanically<br />

Temperature range 5 °C to 50 °C<br />

Switching differential at 20 °C = 0.6 °K<br />

Protection category IP30<br />

Output 2 or 3 contact ( alternator)<br />

Order no. 3 F792 00 230 V~, 50 Hz.<br />

Order no. 3 F792 01 24 V<br />

Electronic room thermostat for<br />

Underfloor heating<br />

For controlling the room temperature or<br />

floor temperature in conjunction with a<br />

temperature sensor.<br />

This temperature sensor must be designed<br />

as a temperature limiter. There is the option<br />

of connecting an external time switch for<br />

night reduction.<br />

Temperature range, 5 °C to 50 °C<br />

Switching differential at 20 °C = 0.5 °K<br />

Triac output maximum 15 W<br />

Protection category IP30<br />

This temperature sensor must be designed<br />

as a temperature limiter.<br />

There is the option of connecting an<br />

external time switch for night reduction.<br />

Temperature range, 5 °C to 50 °C<br />

Switching differential at 20 °C = 0.5 °K<br />

Triac output maximum 15 W<br />

Protection category IP30<br />

Order no. 3 F793 00 230 V~, 50 Hz.<br />

Order no. 3 F793 01 24 230 V<br />

Set with temperature sensor<br />

Order no. 3 F793 00 230 V~, 50 Hz.<br />

Order no. 3 F793 03 24 V<br />

Order no. 3 F792 00 230 V~, 50 Hz.<br />

Order no. 3 F792 03 24 V<br />

32<br />