30.10.2014 Views

NOVAR 1106 / 1114 / 1206 / 1214 NOVAR 1xxx / S400 NOVAR ...

NOVAR 1106 / 1114 / 1206 / 1214 NOVAR 1xxx / S400 NOVAR ...

NOVAR 1106 / 1114 / 1206 / 1214 NOVAR 1xxx / S400 NOVAR ...

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

<strong>NOVAR</strong> <strong>1xxx</strong> EPM Elektropřístroj s. r. o.<br />

Fig. 2.2 : <strong>NOVAR</strong><strong>1214</strong> Controller – Connectors<br />

Serial / vers.:<br />

Product. date :<br />

U 100 ÷ 275 VAC, 7VA, 43 ÷ 67 Hz<br />

IP 4X<br />

Made in Czech Republic<br />

/<br />

/<br />

1 2 3 4 5 6 7 8 9 10 11 12 13 14<br />

ALARM<br />

k l L N<br />

Rx Tx GND<br />

L N L L/N<br />

RS 232/485<br />

max. 100÷275 VAC 58÷690 VAC 2. TARIF<br />

TR A B GND<br />

5A<br />

10A<br />

(1A)<br />

max. 6A<br />

max. 6A<br />

SUPPLY<br />

LOAD<br />

L1<br />

L2<br />

L3<br />

N<br />

2.2.1.2 “/<strong>S400</strong>” Version Controllers<br />

Controllers of the ―/<strong>S400</strong>‖ version can be supplied with higher voltage – up to 500 V, either AC or DC.<br />

The power demand is the same as those of standard version.<br />

The supply voltage connects to terminals 3 (L1) and 5 (L2/N). In case of DC supply voltage the<br />

polarity of connection is generally free, but for maximum electromagnetic compatibility grounded pole<br />

should be connected to the terminal 5 (L2/N); see connection examples below.<br />

Power supply voltage need to be externally protected ( see following chapter).<br />

Despite of standard version, power supply terminal 3 (L) is not internally connected to the common<br />

pole of output relays. Terminals 4 and 6 are not used.<br />

Fig. 2.3 : <strong>NOVAR</strong><strong>1114</strong>/<strong>S400</strong> Controller – Connectors<br />

<strong>NOVAR</strong> <strong>1106</strong> <strong>1114</strong> / <strong>S400</strong> / 232 485<br />

Serial No / Fw. vers.: /<br />

Production date :<br />

U 75 ÷ 500 V AC, 7 VA, 43 ÷ 67 Hz<br />

IP 4X<br />

Made in Czech Republic<br />

/<br />

1 2 3 4 5 6 7 8 9 10 11 12 13 14<br />

ALARM<br />

k l L1 L2/N<br />

Rx Tx GND<br />

max.<br />

RS 232/485<br />

500<br />

TR A B GND<br />

5A<br />

VAC<br />

(1A)<br />

1A<br />

SUPPLY<br />

LOAD<br />

L1<br />

L2<br />

L3<br />

N<br />

Formatted: Bullets and<br />

Numbering<br />

2.2.1.3 <strong>NOVAR</strong> 1005 / 1007 Controllers<br />

The supply voltage connects to terminals 4 (L1) and 3 (N). In case of DC supply voltage the polarity of<br />

connection is free. Power supply voltage need to be externally protected ( see chapter Protection<br />

below ).<br />

Power supply terminal 4 ( L1 ) is internally connected to the common pole of output relays. It is<br />

necessary to dimension the power supply protection in consideration of output contactors’ power as<br />

well.<br />

16